Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹73.1 LAccepted-AOC | ₹73.1 L | L-1 | Accepted-AOC Being lowest and reasonable |
| 2 | L-2₹76.8 L+₹3.8 L (5.14%)Rejected-Finance | ₹76.8 L+₹3.8 L (5.14%) | L-2 | Rejected-Finance Not being lowest bidder. |
| 3 | L-3₹81.3 L+₹8.2 L (11.2%)Rejected-Finance SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | ₹81.3 L+₹8.2 L (11.2%) | L-3 | Rejected-Finance Not being lowest bidder. |
| 4 | L-4₹83.9 L+₹10.8 L (14.8%)Rejected-Finance | ₹83.9 L+₹10.8 L (14.8%) | L-4 | Rejected-Finance Not being lowest bidder. |
| 5 | Rejected-Technical | - | - | Rejected-Technical Not admitted since firm is not enlisted in appropriate category i.e. c(i). |
Tender Value
₹78 L
EMD Value
₹1.4 L
Closing Date
3 Sept 2024, 6:00 pmClosed
CWE BATHINDA
HQ CWE BATHINDA , BATHINDA MIL STN
PREVENTIVE AND COMPREHENSIVE MAINT OF CENTRAL AC PLANT AND PACKAGE AC PLANT AT VARIOUS LOCATION UNDER GE (U) AT BATHINDA MIL STN
2024_MES_662340_1
CWE BTD/Token-01/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
BATHINDA MILITARY STATION
As per NIT
7 documents required · 7 mandatory
₹1,000
GE (U) Bathinda
₹1.4 L
HQ CWE BATHINDA , BATHINDA MIL STN
15 Oct 2024
26 Jun 2024
5 Sept 2024
26 Jun 2024
3 Sept 2024
19 Jul 2024
5 Jul 2024
Amount
Comprehensive maintenance and attending day to day complaints for maintain smooth functioning of all AC plants and resolving day to day complaints of Air conditioning plant (central/package), chiller units, AHU any capacity in Bhatinda cantt area and repairing / replacement of any item or component of required after resolving complaints to the entire satisfaction of Engineer-in-Charge and as directed. Note: (i) Services for MAJOR maintenance which require control circuit issues shall be carried out by SERVICE ENGINEER of respective company and the rates is included in this item. Nothing extra to be paid on this account. contractor will attend complaint regarding to leakage of refregerant gas from AC plant ,contractor will find out leakage and necessary welding work and recharging of Gas after nitrogen flushing will be carried out, refrigerant gas will be measure and paid seperately in appropriate item of schedule'A' BoQ.. (ii) Major replacement/renewal company authorised Engineer should attend the fault. (iii) Spare parts shall be measured and paid separely under appropriate items of schedule 'A' BoQ .Minor repair work which consisting of no part replacement but plant can be start like wise lugs replacement ,wire burnt etc. contactors, relays, MCCB and timer will strictly be bought as per model mentioned in schedule A. (iv) Contractor will depute a electritian and referigeration mech with suoervisor for collecting the complains ,contractor will provide vehicle to technitian.All complaints to be attended and rectified within 24 hrs if failing which Rs 500.00/day will be recovered. (iv) T&P / vehicle required for technician and semi skilled shall be arranged by the contractor at his own cost to attend complaints and carry out the repair works at various locations of cantt area and the cost is included in this item and nothing extra shall be be paid in this regard. following AC plants :-
Contiuned serial item no.1.01 (a) AC PLANT - 04 Nos Chilling Units (Existing Make - Blue Star) (b) AC PLANT - 04 Nos Chilling Units (Existing Make - Blue Star) (c) AC PLANT - 04 Nos Chilling Units (Existing Make - Blue Star) (d) AC PLANT - 04 Nos Chilling Units (Existing Make - Blue Star) (e) AC PLANT - 04 Nos Chilling Units (Existing Make - Blue Star) (f) AC PLANT- 04 Nos Chilling Unitsh (Existing Make - Blue Star) (g) AC PLANT- 04 Nos Chilling Units) (Existing Make - Blue Star) (h) AC PLANT - 02 Nos Chilling Units (Existing Make - Blue Star) (j) AC PLANT- 02 Nos Chilling Units (Existing Make - Blue Star) (k) AC PLANT 03 Nos Chilling Units (Existing Make - Blue Star)(l) AC PLANT - 02 Nos Chilling Units (Existing Make - Voltas) (m) AC PLANT - 02 Nos Chilling Units (Existing Make - Voltas)
Contiuned serial item no.1.01 (n) AC PLANT - 02 Nos Chilling Units (Existing Make - Voltas) (o)AC PLANT -100 TR -03 Nos Chilling Units (Existing Make - Blue Star) (p) AC PLANT- 100 TR -02 Chilling Units (Existing Make - Hitachi ) (q) AC PLANT -40 TR -03 Chilling Units (Existing Make - Voltas) (r) AC PLANT -25 TR -03 Nos Chilling Units (Existing Make - Voltas ) (s) AC PLANT -18 TR -03 Nos Chilling Units (Existing Make - ACCEL ) (t) AC PLANT - 5TR -03 Nos Chilling Units (Existing Make - ACCEL) (u) AC PLANT - 7.5 TR -03 Nos (package AC Plant) (Existing Make - Carrier) (v) AC PLANT - 2 TR -08 unit (Cold storage plants ) (Existing Make - Blue Star) (w) AC PLANT-13.7 -03 Nos ( Package AC Plant) (Existing Make - Blue Star) (x) AC PLANT -5.5 TR -03 Nos (package AC plant) (Existing Make - Blue Star)
Material and labour for de-scaling of AC plant which consisting of 12.5 TR compressor Scroll type compressor of Central AC Plant and cleaning of chocked pipe water circulating lines including service valves,condenser (Heat Exchanger) to cooling tower ,circulating concentrated de-scaling solution ( diluted hydrochloric acid) mixed with water in suitable proportion till the complite deposites/scale is removed or 24 hours whichever is later & as ordered, Circulating through pump,servicing of valves,cooling tower,water spray assemble ,cleaning with suitable size of drill rod ,wire brush including dismantling and connecting all desmantled components in proper position after srevicing/overhauling etc replacement of packing gasket 3mm thick,Nuts,Bolts with washer,testing of water line for leakage,complite all as specified and derected by Engineer-in Charge -complete to the entire satisfaction of Engineer-in-Charge. NOTE : (i) The spare parts required for replacement shall be measured and paid separately as supply only under:- (ii) All spare parts shall be of make Blue star (iii) Cost of minor damaged spares like washers,nut,bolts any type sensors, safety valves and dryier including cleaning agent, tools and testing equipments etc and also plants made functioning in full load shall deemed included in unit rate quoted by contractor.
Contiuned serial item no.2.00 Plants Details (a) AC PLANT - 04 Nos Chilling Units (b) AC PLANT- 04 Nos Chilling Units (c) AC PLANT- 04 Nos Chilling Units (d) AC PLANT - 04 Nos Chilling Units (e) AC PLANT - 04 Nos Chilling Units (f) AC PLANT - 04 Nos Chilling Unitsh (g) AC PLANT - 04 Nos Chilling Units) (h) AC PLANT- 02 Nos Chilling Units (j) AC PLANT - 02 Nos Chilling Units (k) AC PLANT - 03 Nos Chilling Units (l) AC PLANT- 02 Nos Chilling Units (m) AC PLANT- 02 Nos Chilling Units (n) AC PLANT - 02 Nos Chilling Units Existing Makes : M/s Blue Star and Voltas of screw type compressor, 11/12.5 TR each, single stage, 415 Volts, 3 Ph, 50 Hz, shell & tube type condenser with carbon steel plate, copper tube, incl carbon plate shell & tube flooded type chiller unit working with microprocessor base controls in sheet metal control panel, complete all as directed to entire satisfaction of Engineer-in-charge.
Material and labour for de-scaling of 100TR screw type compressor of Central AC Plant and cleaning of chocked pipe water circulating lines including service valves,condenser (Heat Exchanger) to cooling tower ,circulating concentrated de-scaling solution ( Concentrated hydrochloric acid) mixed with water in suitable proportion till the complite deposites/scale is removed or 24 hours whichever is later & as ordered, Circulating through pump,servicing of valves,cooling tower,water spray assemble ,cleaning with suitable size of drill rod ,wire brush including dismantling and connecting all desmantled components in proper position after srevicing/overhauling etc replacement of packing gasket 3mm thick,Nuts,Bolts with washer,testing of water line for leakage,complite all as specified and derected by Engineer-in Charge -complete to the entire satisfaction of Engineer-in-Charge. NOTE : (i) The spare parts required for replacement shall be measured and paid separately as supply only under:- (ii) All spare parts shall be of make Blue star (iii) Cost of minor damaged spares like washers,nut,bolts any type sensors, safety valves and dryier including cleaning agent, tools and testing equipments etc and also plants made functioning in full load shall deemed included in unit rate quoted by contractor.
All as per description item No.3.00 here-in-befoe but 25 TR
Descaling of Package type AC Plant unit (DX type) of capacity 3 x 13.7 TR at AC PLANT including outdoor unit Hermetically sealed compressor, safety devices, cooling thermostat, humidity stat kit Existing Make : M/s Blue Star incl control panel, complete all as directed to entire satisfaction of Engineer-in-charge.
Descaling of outdoor unit of Ductable Package type AC Plant factory assembled of capacity 3 x 5.5 TR at AC PLANT Hanger air cooled type with all accessories and controls each compressor Existing Make : M/s Blue Star incl control panel, complete all as directed to entire satisfaction of Engineer-in-charge.
Descaling of outdoor unit of Cold Storage Plant factory assembled of capacity 2 TR at MH air cooled type with all accessories and controls each compressor Existing Make : M/s Blue Star incl control panel, complete all as directed to entire satisfaction of Engineer-in-charge.
All as per item No 3 above but Existing Make : M/s Voltas of reciprocating compressor, 3x40 TR each at AC PLANT single stage, 415 Volts, 3 Ph, 50 Hz, shell & tube type condenser with carbon steel plate, copper tube, incl carbon plate shell & tube flooded type chiller unit
Descaling of Package type AC Plant unit of capacity 3x7.5 TR at IIT, including outdoor unit Hermetically sealed compressor, safety devices, cooling thermostat, humidity stat kit Existing Make : M/s carrier incl control panel, complete all as directed to entire satisfaction of Engineer-in-charge.
All as per item No 3 above but Existing Make : M/s Accel of reciprocating compressor, 3x18 TR each at signal centre, single stage, 415 Volts, 3 Ph, 50 Hz, shell & tube type condenser with carbon steel plate, copper tube, incl carbon plate shell & tube flooded type chiller unit complete allas directed.
All as per item No 3 above but Existing Make : M/s carrier of reciprocating compressor, 3x5 TR each at 10 TAC, single stage, 415 Volts, 3 Ph, 50 Hz, shell & tube type condenser with carbon steel plate, copper tube, incl carbon plate shell & tube flooded type chiller unit complete all as directed to entire satisfaction of Engineer-in-charge.
Material & Labour for dismantling of electric driven horizontal induction motor of capacity 2.0 HP of any type and make, by engaging sufficient man power and suitable T&P to ensure safety of pump-motor as well as working persons including disconnecting of electric connections, dismantling of motor, taking out the burnt windings, cleaning and washing of slots and rewinding the same with copper winding wire of existing gauge and quantity (as per original manufacturer design) including replacement of all damaged parts i. e. bearings, bush, thrust plate, thrust bearing, connector plate, insulating materials such as insulating sheets insulating paper (Class "F"), sealing compounds etc and reassembling the motor after varnishing, heating/drying, greasing of moving parts etc and reinstallation of the motor in original location, checking the alignment, making proper electric connection, testing for smooth operation, complete all as directed. Note : (i) The cost of winding wire and all replaced defective parts are deemed to be included in quoted rates and no extra cost shall be paid to the contractor in this effect. (ii) The cost of transportation (to and from) and other necessary equipment shall be arranged/brought by contractor to complete the job at site or at repair shop and no extra cost shall be paid to the contractor in this account.
All as per srl item no 12 here-in-above but for 3.0 HP capacity.
All as per srl item no 12 here-in-above but for 5.0 HP capacity.
All as per srl item no 12 here-in-above but for 7.5 HP capacity.
All as per srl item no 12 here-in-above but for 10.0 HP capacity.
All as per srl item no 12 here-in-above but for 15.0 HP capacity.
All as per srl item no 12 here-in-above but for 20.0 HP capacity.
All as per srl item no 12 here-in-above but for 25.0 HP capacity.
Material & Labour for complete overhauling of condenser/chiller centrifugal pumpset of 25.00/20.00/15.00 HP by engaging sufficient man power and suitable T&P to ensure safety of pump-motor as well as working persons including disconnecting suction & discharge water lines and removing of electric connection, dismantling the U/S pumpset from MS foundation, detaching the pump, opening the pump, remelting the shaft and filling of metal at decayed portions including all kind of machine works i.e. welding, turning, polishing etc as required to make the shaft of required shape and size, as original, balancing the shaft and refitting in pump body; complete replacement of impeller set with new; replacement of Cushy foot anti vibration pad with and incl carrying out complete repair / replacement of damaged parts i.e. bearings, bush, gland plate, gland packing, coupling assembly etc and reassembling the pump after greasing of moving parts and reinstallation of the pump with motor in original location using new MS stud, nut, bolt, washer and other packing material etc; checking the alignment; reconnecting the suction and delivery pipes, making proper electric connection, testing and commissioning for smooth operation at optimum efficiency, complete all as directed.
All as per srl item no 20 here-in-above but for 10 / 7.5 HP capacity.
All as per srl item no 20 here-in-above but for 5/02 HP capacity.
Supply and fix in replacement of cooling tower PVC honey comb fills in colums of size 600mm x 300mm x 150mm size and min wt 600 gram of capacity 15 TR to 150 TR complete all as specified and directed by Engineer-in-Charge. Note: Make shall be as mentioned in Appendix 'B' here-in-after and shall be approved by GE before incorporation in the work.
Material & Labour for complete cleaning of cooling tower including taking out the cooling fan motor with blade cleaning the blade with caustic soda, removing the top cover, taking out sprinkler set cleaning the holes of sprinkler, removing the fills, replacing the broken/damaged fills, cleaning the fills, cleaning the pipe line and strainers, with pressure motor and reassembling all the parts and make the cooling tower fully functional. Note : (a) The stores required for making the cooling tower will be measured and paid separately under serial item no.24.01,24.02,24.03,24.04 & 24.05 of BoQ as supply only.The labour element of serial item no.24.01,24.02,24.03,24.04 & 24.05 of BoQ is included in this item and nothing shall be paid extra on this account.
Supply only GI Clamps
Supply only Turn Buckles make as approved by GE
Supply only Tension rod make as approved by GE
Supply only Sprinkler Head make as approved by GE
Supply only Branch Pipe make as approved by GE
Supply and fix in replacement of Cooling Tower Sprinkler Assembly such as Sprinkler, Sprinkler Pipe, Elimentor, Tension bar and Turn buckle for Cooling Tower capacity 160/120/100 TR as per existing make on site complete all as specified and directed by Engineer -in- charge.
supply and fix in replacement of Cooling Tower Sprinkler Assembly such as Sprinkler, Sprinkler Pipe, Elimentor, Tension bar and Turn buckle for Cooling Tower capacity 50 TR/30/22/37.5/12.5TR nosal type /sprinklar type as per existing make on site complete all as specified and directed by Engineer -in- charge.
Material & Labour for replacement of micro processor controller panel, suitaable for voltas water cooled recirocating chillers model 5H 60/5 H 66 Digital display of all vital parameter for water cooled reciprocating pkg chiller plant 50 TR as per sample Model No-VLRP SINGLE V2A,Type -DELUX Range-6/5/4 ,Aux supply-8v &12 V, complete all as specified and directed. make as approved by GE
Material & Labour for replacement of microcomputer voltage protection device(MVPD) with display complete model-EC, Type-MVPD, Range 30-220 Amps,Aux supply-230V,Special -5 sec Curve MPD complete all as specified and directed. make as approved by GE.
Material & Labour for replacement of thermostatic expansion valve suitable for water cooled scroll chiller unit cap 25/37/50 TR all as per sample, including brazing at both ends all as required and directed.Make as approved by GE.
Material & Labour for replacement of HP/LP switch suitable for scroll compressor cap up to 12.5 TR all as per specified and directed.Make as approved by GE.
Material & Labour for replacement of Drier filter suitable for Package type AC Plant size 5/8" as directed.Make as approved by GE.
Material & Labour for replacement of chilled water sensor complete all as specified and directed.Make as approved by GE.
Material & Labour for replacement of micro processor controller panel, Digital display of all vital parameter for water cooled scroll type chiller plant as per sample Model No-SCR44TR(MPD) ,Type -DELUX Range-5-30 Amp , Make as approved by GE.
Material & Labour for replacement of microcomputer voltage protection device(MVPD) with display complete model-EC, Type-MVPD, Range 5-30 Amps,Aux supply-230V,Special -5 sec Curve MPD for 37.5 TR/50TR/25TR CHILLER .Make as approved by GE.
Supply and fix in replacement of microprocessor based computer controlled PLC .Make as approved by GE.
M&L for replacement of' V Belt of A & B Series any sizes for AHU 's as per site requiement complete all as specified and directed.Make as approved by GE.
Supply and fix in replacement of water presuure gauge 0-7 kg / cm2 including Female Stainless Steel Gauge Fittings INCLUDING ball valve 5/8", type complete all as specified and directed.Make as approved by GE.
S&F in replacement of thermometer to condenser/chiller, inlet or outlet water pipes including addition alteration to pipe line for fixing thermometer Range 0-100 degree F / degree centigrade complete all as specified and directed.Make as approved by GE.
Dismantling existing old Cooling Tower and Supply, Installation, testing and commissioning of FRP cooling tower in accordance with BS-4485 of minimum 50 TR heat rejection capacity with FRP water basin PVC fillings with integral louvers and drift eliminators complete with hot water basin either fitted with spray nozzles or having self rotating sprinklers, statically & dynamically balanced axial flow type fan direct driven or driven through reduction gear box with TEFC induction motor , suction screen, make up quick filling arrangement, over flow and drain connections with necessary valves and suitable inspection aluminium ladder of suitable length, access arrangement for cooling lower interior, installed on MS girders (MS-I sections) fixed in masonry foundations with cement concrete footing, second class brick work and cement mortor1:6; all accessories, basin fittings, fan, fan motor suitable for 415 Volt supporting structure, anti vibration mountings etc. complete and 50 HZ power supply having isolator panel with MCB of suitable capacity at cooling tower to make it fully operational and maintanable.having following technical data:- (a) Water flow/tower 200 USGPM (b) Entering Water Temperature : 97 °F (c) Basin Water Temperature : 90 ˚F (d) Type of fan: Propeller type of motor suitable capacity, 415 volt ± 10% volts, 600 RPM , Weather proof. Note: Old reterived cooling tower shall be deposted in the Store Yard of AGE E/M Referigeration of GE (U) Bathinda . The rate of this asspect is included in this itme and nothing shall be paid extra on this account.
M&L for repair in Earth continuity conductor or main earthing lead of size 25 x 4 mm galvanised of size 25mm x 4 mm fix to wall/ laid in trenches fixed in tray complete all as specified and all as directed .
Supply and fix in replacement, of CI butter fly valve, ISI marked, PN - 1.6 pressure grade, having Nitrile/EPDM rubber lining, SS stem, CS/SS disc, lever operated type, of size 50mm dia bore including all jointing material i. e. nut, bolt, washer, packing material etc, duly insulated complete all as specified and all as directed .
All as per srl item No. 41.00 here-in-before but 65 mm dia size.
All as per srl item No. 41.00 here-in-before but 80 mm dia size.
All as per srl item No. 41.00 here-in-before but 100 mm dia size.
All as per srl item No. 41.00 here-in-before but 125 mm dia size.
All as per srl item No. 41.00 here-in-before but 150 mm dia size.
Supply and fixing in replacement 200 mm dia Non Return Valve , both ends flanged heavy duty ,PN-1.6 , IS 5312 Part -I, Body Cover CI IS : 210, Gr. FG260, Body Rings - Bronce : IS 318 Gr. LTB2, Hinge Pin-SS ASTM A276 Type 410. Flage Drilling - IS 1538, Table 4 & 6. including packing materials, nut bolts washer etc and testing complete all as specified and directed.
All as per srl item No. 47.00 here-in-before but 150 mm dia size.
Supply and fix in replacement, of gun metal gate valve of 20 mm dia bore size (IS -778) Class 1 with iron wheel head, screwed inside, non-rising stem, complete all as specified and directed.
All as per srl item No 49.00 here-in-before but of 25 mm bore size.
All as per srl item No 49.00 here-in-above but of 40 mm bore size.
Supply and fix in replacement of Ball brass valves high pressure,with polythenefloat and fly nut screwed for iron pipe or brass ferrule and fixed of size 25 mm complete all as specified and as directed.
All as per srl item No 52.00 here-in-above but of 40 mm bore size.
supply and fix in replacement for insulation of MS pipe of 150 mm dia and above size with PUF slab 40 mm thick with and incl applying bituminous compound and GI cladding with 26 gauge GI sheet with and incl taking down of old insulation and preparing of pipe surface by scratching / removing rust, dust and old paints etc with wire brush, emery paper, grinder etc and making surfaces smooth, complete all as specifed and directed.make as approved by GE
All as per srl item no 54.00 here-in-before but of 100 mm bore size.make as approved by GE
All as per srl item no 54.00 here-in-before but of 80 mm bore size.make as approved by GE
All as per srl item no 54 here-in-before but of 50 mm bore size.make as approved by GE
Supply and fixing in replacement, of Single phase heating element capacity 05 KW, ISI marked of existing shape and size suitable for hot water generator and making electric connections , complete all as directed. make as approved by GE
Supply and fixing in replacement, of Single phase heating element capacity 03 KW, ISI marked of existing shape and size suitable for hot water generator and making electric connections , complete all as directed. make as approved by GE
All as per item No 59 here in before 2 KW make as approved by GE
Supply, install, Testing and Commissioning Electronic Temperature and Electric operated Actuator for motorized combination for operated control the valve of AHU near chiller line (spring return type) including taking out unserviceable controller all as specified and directed by Engr-in-Charge.make as approved by GE
Supply and fixing in replacement of flow switch suitable for AC plant perating pressure (10 Kgf/cm2) as per sample existing model.make as approved by GE
Supply & Fixing Rotational moulded poly-ethylene three layer water storage tanks (cylinderical vertical with closed top) 10000 litres capacity,hoisted and fixed in position with and including all fittings and fixtures complete all as specified and directed.
Supply & Fixing Rotational moulded poly-ethylene three layer water storage tanks (cylinderical vertical with closed top) 15000 litres capacity,hoisted and fixed in position with and including all fittings and fixtures complete all as specified and directed.
Supply & Fixing Rotational moulded poly-ethylene three layer water storage tanks (cylinderical vertical with closed top) 20000 litres capacity,hoisted and fixed in position with and including all fittings and fixtures complete all as specified and directed.
Material & Labour for Earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth strip 25mm x 4 mm , (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt around earth plate & 32 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit and 40 mm thick precast RCC cover in 1 : 2 : 4 type B-1 with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle complete all as specified, directed and as shown in plate No. 03 of MES Schedule Part-I. NOTE: Earth lead wire and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item and additional earth GI earth strip/protection pipe etc. if any required at site shall be measured and paid for separately under appropriate item of Schedule `A’ NOTE - The quoted rate is deemed to include for earth work in any type of soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B1 cover 50mm thick reinforced with 8mm dia TMT bars @ 150mm, center to center both ways, funnel with watering pipe.
Material & Labour for Sub main wiring with 2 runs of 4 sqmm, single core, PVC insulated & unsheathed FRLSH multi stranded copper cable conforming to IS-694, 1100 volt drawn in and including 20mm dian non metallic PVC grey conduit with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 4 sqmm single core PVC insulated & unsheathed FRLSH multi stranded copper cable conforming to IS-694, 1100 volt as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on complete all as specified and directed. (Note : 2 runs of 4 sqmm cable, 1 run of 4 sqmm single core copper cable and 1 run of non metalic PVC conduit shall be measured as single run).
Supply and Fixing in replacement of coaxil Fan suitable for cold storage plant and package AC plant 230v 50HZ incl connecting up with PVC three core copper conductor cable of suitable size from ceiling rose to exhaust fan complete all as specified and directed. Make as approved by GE. Note: The rate of PVC three core copper conductor cable from of suitable size ceiling rose to exhaust fan for connection is included in this item and nothing shall be paid extra on this account.
Supply and fixing in replacement LED tube light fittings 4 feet with fixture 20 watts 230v 50HZ incl connecting up with PVC two core copper conductor cable of suitable from ceiling rose to fittings complete all as specified and directed. Note: The rate of PVC two core copper conductor cable from of suitable size ceiling rose to exhaust fan for connection is included in this item and nothing shall be paid extra on this account.
Supply and fixing in replacement of motor coupling of size 095 -100 complete all as specified and directed
Material and Labour for cement plastering in cement mortar (1:2 ) setting coat 3 mm thick and smooth finish on exist hot water pipe insulation or Chilled water pipe insulation complete all as specified and directed.
supply and fixing in replacement GI pipe 25 mm dia bore medium grade with all fittings laid in floors or fixed to walls and ceiling including cutting/welding / riveting etc. complete all as specified and directed .
Supply and Fixing in replacement GI pipe 40 mm dia bore medium grade with all fittings laid in floors or fixed to walls and ceiling including cutting/welding / riveting etc. complete all as specified and directed .
Supply and Fixing in replacement MS pipe 50 mm dia bore heavy grade with all fittings laid in floors or fixed to walls and ceiling including cutting/welding / riveting etc. complete all as specified and directed.
Supply and Fixing in replacement MS pipe 65 mm dia bore heavy grade with all fittings laid in floors or fixed to walls and ceiling including cutting/welding / riveting etc. complete all as specified and directed
Supply and Fixing in replacement MS pipe 80 mm dia bore heavy grade with all fittings laid in floors or fixed to walls and ceiling including cutting/welding / riveting etc. complete all as specified and directed.
Supply and Fixing in replacement MS pipe 100 mm dia bore heavy grade with all fittings laid in floors or fixed to walls and ceiling including cutting/welding / riveting etc. complete all as specified and directed.
Supply and Fixing in replacement MS pipe 150mm dia bore heavy grade with all fittings laid in floors or fixed to walls and ceiling including cutting/welding / riveting etc. complete all as specified and directed.
Supply, installation, commissioning & testing of motorized combination fire and smoke damper (spring return type) of atleast 120 minute fire rating and all as specified. The fire damper shall be complete with electronic temperature sensor, electrically operated actuator, control panel & wiring.The fire dampers shall be located in the supply/return air ducts, at all fire rated crossovers (shafts/walls etc.) The control panel will be such located that the reset can be easily done, including Electrical spring type actuator,remote indication of the fire damper position complete.Make as approved by GE. .
Supply and fixing in position ‘Y' type strainer, CI body of size 100 mm duly insulated complete all as specified.
Supply and fixing in position ‘Y' type strainer, CI body of size 150 mm duly insulated complete all as specified.
Supply and fixing in position ‘Y' type strainer, CI body of size 80 mm duly insulated complete all as specified.
Supply of refrigerant Gas R-134a of capacity 61 kgs duly company sealed complete all as specified and as directed by Engineer-in-charge.Make as approved by GE.
Supply of refrigerant Gas R-407c of capacity 61 kgs duly company sealed complete all as specified and as directed by Engineer-in-charge.Make as approved by GE.
Supply of refrigerant Gas R-22 of capacity 61 kgs duly company sealed complete all as specified and as directed by Engineer-in-charge.Make as approved by GE.
Supply of refrigerant Gas 404a of capacity 10 kgs duly company sealed complete all as specified and as directed by Engineer-in-charge.Make as approved by GE.
Supply and fixing in repair PVC float valves, high pressure, with polythene float and fly-nut (PTMT) complete,screwed for iron pipe of brass ferrule, suitable for 25mm to 40mm bore pipe complete all as directed.
Material & Labour for applying one coat FRP painting as desired colour over a coat of red oxide primer on steel/iron surfaces of pipes after preparing surface with help of emery paper etc removing rust, dust and old paints and making surfaces smooth for achieving better grip between surface and primer all as specified.
Material & Labour for duct insulation 40MM with resin bonded fibre glass wool roll of density 24 kg/Cum, with factory laminated aluminium vapour barrier, thickness of insulation as specified and including the following:- → (a) M&L for cleaning the duct surface (to be insulated ) by scrapping carefully with wire brush etc. to make the surface completely free of millscale, dirt, dust, grease and other foreign materials, taking special care so that all duct joints are sealed against any leakage. (b) M&L for applying rubber based adhesive CPRX compound. (c) M&L for sealing of all longitudinal joints and circular overlaps with and including Aluminium foil tape 50 mm wide, to make the insulation leakproof. (d) M & L for securing the insulation with and including mechanically fastened nylon/ steel straps of size 12 mm/50 mm at maximum intervals of 1.2 mtr.as directed
Material & Labour for taking out unserviceable sealed unit (compressor) as existing and replacing the same with new packaged type sealed unit (compressor) 12.5 ton capacity ,make as approved by GE, three phase, 415 volt including necessary modification of the foundation as required to suit the compressor, flushing the sysytem by nitrogen gas and pressure testing for leakage and rectified (by brazing) and after rectification vacumacation, pressure testing, and gas charging R-407c for achieve desire pressure and testing complete to the entire satisfaction of Engineer-in-Charge NOTE :- Gas R-407c for charging shall be measured and paid separately as supply only.but the labour element of charging is included in this item and nothing shall be paid extra on this account.
Material & Labour for replacement of 25 mm dia. Auto Air Purge valve for chilled water piping complete all as specified and directed.Make as approved by GE.
Supply & Fixing in repairs worn out HRC fuses 10 Amps to 100 Amps (Cylindrical / DIN type / Bolted) conforming IS 13703 Part - II with high breaking capacity suitable for existing holders all as specified and as directed
Supply & Fixing in repairs worn out fuses 2Amps to 10 Amps (Cylindrical / DIN type / Bolted) conforming IS 13703 Part - II with high breaking capacity suitable for existing holders all as specified and as directed
Material & Labour for replacement of Indicating Lamp,LED Type Red, Yellow, Blue , 240V AC, complete all as specified and directed
Material & Labour for replacement of Mushroomhead Push Button, Press to Lock Turn To Release complete all as specified and directed.
Material & Labour for replacement of ON/OFF Push Button complete all as specified and directed
Material & Labour for replacement of repair of thermal Relay MNX 32A 3 Amp and upto 6 Amp complete all as specified and directed
Material & Labour for replacement of thermal Relay MNX 32A above 6Amp and up to 10 Amp complete all as specified and directed
Material & Labour for replacement of thermal Relay MNX 32A above10Amp and up to 16 Amp complete all as specified and directed
Material & Labour for replacement of MNX -A1 size contactor block complete all as specified and directed
Material & Labour for replacement of MNX -A2 size contactor block complete all as specified and directed
Material & Labour for replacement of MNX 32A contactor block with NO/NC switch complete all as specified and directed
Material & Labour for replacement of MNX 18A contactor with NO/NC switch complete all as specified and directed
Material & Labour for replacement of MNX 12A contactor with NO/NC switch complete all as specified and directed
Material & Labour for replacement of Timer GIC star/delta complete all as specified and directed
Material & Labour for replacement of connector for suitable to chiller panel complete all as specified and directed
Material & Labour for replacement of starter block contactor 3TF34-C3 with NO/NC switch complete all as specified and directed
Material & Labour for replacement of starter block contactor 3TF46-C3 with NO/NC switch complete all as specified and directed
Supply and fix thermometer humidity meter clock with sensor cable Temperature and Humidity Functions: With temperature range from -10 degC to +50 degC and humidity 10 % sim 99 % RH, temperature and humidity readings show directly all as per directed
Supplying and laying synthetic Rubber insulated mats of size 2.00 m x 1.00m and 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety complete all as specified and directed .
Supply and fix of multifunction meter voltage, ampere, power,power factor measureable accuracy class 1 for 3 phase panel including setting the parameter with CT as directed
Supply and Fixing in replacement of MCCB 400 Amp , 4Pole , 36 KA thermal megnatic complete all as specified and directed
Supply and Fixing in replacement of MCCB 250 Amp , 4 Pole , 25 KA thermal megnatic type complete all as specified and directed
Supply and Fixing in replacement of MCCB 200 Amp , 4 Pole , 16 KA thermal megnatic typecomplete all as specified and directed
Supply and Fixing in replacement of MCCB 160 Amp , 4 Pole , 16 KA thermal megnatic type all as specified and directed
Supply and Fixing in replacement of MCCB 100 Amp , 4 Pole , 16 KA thermal megnatic type complete all as specified and directed
Supply and Fixing in replacement of MCB TP 415 Volt ,63 Amp ,'C' Curve ,10KA complete all as specified and directed
Supply and Fixing in replacement of MCB TP 415 Volt ,32 to 40 Amp , 'C' Curve ,10KA complete all as specified and directed
Supply and fix in replacement of PVC insulated 4 Core copper Cable of size 6 Sqmm complete all as specified and directed
Supply and fix in replacement of PVC insulated 4 Core copper Cable of size 16 Sqmm complete all as specified and directed
Supply and fix in replacement of PVC insulated 4 Core copper Cable of size 25 Sqmm complete all as specified and directed
Material & Labour for replacement of Aluminium Fan blade for out door Fan motor assembly suitable for ductable AC 5.5/8.5 ton capacity . Make as approved by GE.
supply and fixing Pressure switch 0-30 BAR AKS 3000(060G1081) suction/discharge/oil pressure as directed. Make as approved by GE.
Supply and filling of compressor oil (mineral) suitable for voltas water cooled recirocating chillers model 5H 60/5 H 66
Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender from total amount of Schedule 'A'/BOQ.
HVAC Engineering Co (BID ID -3078459)
M/s Rohit Construction Co. (BID ID -3074203)
Aman Enterprises (BID ID -3073679)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .