GE (AF) SUBROTO PARK
GE (AF) Subroto Park, Delhi Cantt Delhi-110010
As described in Bill of quantities
2026_MES_772879_1
GE/SP/TOKEN-04/2026-27
Open Tender
Miscellaneous Works
120 days
GE (AF) SUBROTO PARK
As per NIT and tender documents
9 documents required · 9 mandatory
₹500
GE (AF) SUBROTO PARK
₹87,320
Yes
17 Jun 2026
17 Jun 2026
10 Jul 2026
17 Jun 2026
7 Jul 2026
2 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply,Installation,Testing & Commissioning of UL/EN Listed Intelligent Addressable Muliticriteria Type Detector having twin LED’s for 360 degree viewing angle & hard Addressable having rotary decade addresss which is from 01-99. LED on the detector shall blink each time the sensor is scanned by the FACP. If the FACP determines the sensor is in alarm, the FACP will command the sensor LED to remain on to indicate the same. Each Sensor will be capable of being tested for alarm via command from the FACP. Each sensor shall respond to FACPs can with the Information about its type for identification all as specified and directed. | 335 | Each | - | - |
| 2 | Supply,Installation,Testing & Commissioning of UL/EN Listed Fault Isolator Module. This unit shall be placed on the loop preferably after every 20–30 devices and shall be able to isolate electrical short circuit in the wiring. All the other detectors shall remain functional because of the Class A wiring of the loop. The isolator shall not utilize an address and shall be built into the detector base wherever required all as specified and directed. | 17 | Each | - | - |
| 3 | Supply,Installation,Testing&Commissioning of Intelligent Analog Addressable Type Manual Call Point having Surface or flush mounting glass break type having Rotary Decade Switces for Addressing from 01-99 complete with Back Box for Mounting Complete as required conforming to BS5839 Standard sand Duly Approved by EN54 /LPCB /VDS /UL/ BSA complete all as specified and directed. | 9 | Each | - | - |
| 4 | Supply,Installation,Testing & Commissioning of Response Indicator for above false ceiling detectors & detectors installed inside cabins.Response indicators with all accessories shall be as per technical specification complete all as specified and directed. | 145 | Each | - | - |
| 5 | Supply,Installation,Testing & Commissioning of UL/EN Listed Intelligent addressable Output module having facility to activate AHU,Lifts etc.having option of RAIL or Surface MountingwithTri Color LED status Indicator with Built in Short Circuit Isolators having Visible Rotary Decade Address Switches from 01-99 complete as required as per specification complete all as specified and as directed. | 3 | Each | - | - |
| 6 | Supply,Installation,Testing & Commissioning of UL/EN Listed Intelligent addressable Input module for monitoring purpose having option of RAIL or Surface Mounting withTri Color LED status Indicator with Built in Short Circuit Isolators having Visible Rotary Decade Address Switches from 01-99 dully approved to GEAGE1-082 conforming to BS5839 Standards and Duly Approved by EN54/LPCB/VDS/UL/BSA complete all as specified and directed. | 3 | Each | - | - |
| 7 | Supply,Installation,Testing & Commissioning of the Alarm Repeater /Annunciator Panel shall display fire /fault messages simultaneously with the FACP. It shall be capable of interfacing with the FACP on a single RS485Bus.The panel shall be capable of operating on 24V DC supply. The panel shall have a 2x40 character back light alphanumeric LCD display, which shall display date, time & description of alarm / trouble events that are displayed in the FACP with an inbuilt buzzer to indicate fault/fire alarm.It shall have control keys for Sound, Silence,Mute and to reset the FACP from the repeater station complete all as specified and as directed. | 1 | Each | - | - |
| 8 | Supply,Installation,Testing & Commissioning of UL/EN Listed loop powered Sounder CUM Strobe complete as required as per specification Duly Approved by EN54/LPCB/VDS/UL/BSA complete all as specified and directed. NOTE: NO additional power supply and control module shall be required to trigger the sounders. | 9 | Each | - | - |
| 9 | Supply,Installation,Testing & Commissioning of UL/EN Listed Analog addressable Fire Alarm system,having the capacity of 99 devices & 99 detectors per loop.The panel shall be able to give location of all fire and More Fire /fault and Isolation conditions of addressable units via the address codes.The panel shall have the capacity of storing upto 999 events. Further,the panel must be able to automatically switch ON/OFF respective control module whenever any alarm is triggered.The panel should have in built common Alarm,Fault and monitored sounder output. The panel shall have a alphanumeric LCD display and having minimum160 Characters in the display. A minimum of two on-board sounder circuits shall be provided.The sounder out puts shall be fully programmable, monitored and short-circuit protected.The panel shall have a built in power supply and battery charger, 24V SMF batteries sufficient for 24 hour in standby and 30 minutes in alarm condition and complete as required as per specification.The fire alarm panel should be network able upto 99panel & repeater panel. A walk test option shall be provided for convenient testing of detectors and alarm initiating devices without continually having to reset the panel.The fire alarm panel shall be compatible for hardware / software integration of PA System.The panel shall provide a flexible way of performing complex cause-and-effect programming.The fire alarm control panel shall have the ability to automatically invoke different operating modes according to the time of day.The control panel shall be capable of expansion. Capacity of upto five analogue addressable detection loops,using five plug-in loop driver modules shall be available.The control panel shall support upto five analogue addressable loops with the capability to control 495 analogue sensors and 495 addressable modules giving the maximum capacity of 990 addresses in case of five loop panel. Each mode shall have adjustable startand finish times. 20number zonal fire indicators(LED’s) and 20 number zonal fault/test/disabled(LED’s) shall be provided.The fire alarm control panel shall have three user control levels. A dedicated RS232 port shall be available for both connections to a local printer and upload /download of configuration data via the manufacturer’s standard PC programming tool.The FACP shall have the provision to integrate with two way fire fighter control system.The FACP shall be able to supervise individual detectors for proper performance as well as to give pin point location of Fire or Fault alarm and initiate alarms as well as facility for cutting off of AHU’s and Electrical Power is also tobe included.The panel shall be compatible with IBMS system with MODBUS protocol. EN54/UL/LPCB approved complete all as specified and directed. | 1 | Each set | - | - |
| 10 | Supply and installation of Loop driver card complete all as specified and directed. | 4 | Each | - | - |