Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAdmitted-Finance 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹1.3 Cr | L1 | Admitted-Finance |
| 2 | Rejected-Technical | - | - | Rejected-Technical DUE TO SHORTFALL OF REQUISTE DOCUMENTS |
| 3 | Rejected-Technical | - | - | Rejected-Technical DUE TO SHORTFALL OF REQUISTE DOCUMENTS |
| Sl No | Description | Qty | Unit | M/s Blue Star Ltd L1 |
|---|---|---|---|---|
| 1.00 | Supply, Installation, Testing and Commissioning of Air cooled scroll chillers Eurovent /AHRI certified oftotal capacity not less than135 TR in combination oftwo Working units or maximum three working units as per below given condition. However in addition to the working units one unit of highest capacity out of working units shall be provided as stand by unit thereby arriving at final configuration of either (2 working + 1 standby) or ( 3 Working +1 Standby ) . Chillers should have Eco friendly green gas refrigerant with inverter driven technology. Chiller shall be equipped with a variable frequency drive with microprocessor controller, with multiple scroll compressors, with suitable TEFC motor, Air Cooled condenser, evaporate, suction, discharge shut off valves, pressure switches, refrigerant piping, base frame, insulation, controls, vibration isolators, automatic capacity control systems if applicable, drive package and refrigerant throttling device to suit the chiller all as specified and/ or directed etc., complete. The total capacity of Air cooled inverter scroll chiller package unitsin combination oftwo Working units or maximum three working units shall not be less than 135 TR at the following specified conditions :
Chiller Selection Data
Actual total capacity of Air cooled inverter scroll chillers package units in combination of two Working units or maximum three working units≥135 TR.
However in addition to the working units one unit of highest capacity out of working units shall be provided as stand by unit thereby arriving at final configuration of either (2 working + 1 standby) or ( 3 Working +1 Standby )
Evaporator
Evaporator Leaving Water Temperature : 44° F
Evaporator Entering Water Temperature : 54° F
Evaporator Water Flow Rate : as per OEM design
Evaporator Maximum Pressure Drop : 12.8 Feet
Evaporator Fouling Factor : 0.0001 h.ft².°F/Btu
Condenser
Ambient Temperature : 43 Degree Celsius
Compressor qty per chiller : Minimum 04 nos or as per company specifications, all inverter with independent circuit.
Other requirements:
COP >3 at AHRI conditions
Condenser should have corrosion protection coating as per ASTM B117
There should not be any capacity deration up to 41 degCelcius ambient temperature, OEM selection shall be submitted for the approval.
AHRI / eurovent model selection sheet shall must be uploaded with technical document . In case of non upload of selection sheet bid shall be rejected
Layout SLD drawing shall be approved by OEM of chiller before starting of work at site.
Authorization letter in favor of Executive engineer , clearly mentioning the Tender name from OEM of chiller shall be issue for back to back support during execution of tender.In case of non upload of letter bid shall be rejected. | 1 | complete job | 0 ₹60,00,000 Lowest |
| 2.00 | Supplying, installing, testing and commissioning of Monoblock centrifugal chilled water pump ( 2 Working +1 Standby ) or( 3 Working +1 Standby ), factory mounted on a common base with electric motor for recirculation of water for the central air conditioning system. All pumps shall be provided with bronze impeller and mechanical seal aligned properly as required . The pump motor shall be suitable for 415 +1-10% volts, 50 cycles, 3 phase power supply. The quoted price shall include cost of thermal insulation and cladding of chilled water pumps.
Flow : 2.4 USGPM/ton of chiller capacity
Head : 22-27 Mtr ( As per actual calculation of pressure drop)
Casing : Cast Iron
Impeller : Bronze
Shaft : Stainless Steel
Make : Kirloskar/Crompton/KSB | 1 | complete job | 0 ₹2,60,000 Lowest |
| 3.00 | Supply, installation, testing and commissioning of Floor Mounted factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanised steel sheet outside & 0.63 mm plain alvanised steel sheet inside with blower, blower section and Blower shall be DIDW FC blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be 25 mm thick & insulated with 42 Kg/m³ density PU foam with thermal break profile . The VFD compatible motor & blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification.
AHU Capacity
25000 CFM capacity @120 mm static pressure with 6 row deep cooling coil and having 10 micron filtration.
Make : - Zeco/Edgetech/Caryair/Crystal | 2 | each | 0 ₹17,00,000 Lowest |
| 4.00 | Chilled water Piping
Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : -
125 mm Dia Pipe - 25 mm thick insulation
MS Pipe Make : Jindal/Tata/Sail
Insulation Make : K-Flex/Supreme/Aerofoam | 60 | mtrs | 0 ₹2,17,200 Lowest |
| 4.10 | Chilled water Piping
Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : -
100 mm Dia Pipe 25 mm thick insulation
MS Pipe Make : Jindal/Tata/Sail
Insulation Make : K-Flex/Supreme/Aerofoam | 36 | mtrs | 0 ₹1,06,920 Lowest |
| 4.20 | Chilled water Piping
Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : -
80 mm Dia Pipe- 25 mm thick insulation
MS Pipe Make : Jindal/Tata/Sail
Insulation Make : K-Flex/Supreme/Aerofoam | 18 | mtrs | 0 ₹39,870 Lowest |
| 4.30 | Chilled water Piping
Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : -
65 mm Dia Pipe- 25 mm thick insulation
MS Pipe Make : Jindal/Tata/Sail
Insulation Make : K-Flex/Supreme/Aerofoam | 12 | mtrs | 0 ₹21,960 Lowest |
| 4.40 | Chilled water Piping
Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : -
20 mm Dia Pipe- 25 mm thick insulation
MS Pipe Make : Jindal/Tata/Sail
Insulation Make : K-Flex/Supreme/Aerofoam | 12 | mtrs | 0 ₹8,640 Lowest |
| 5.00 | SITC of butterfly valve of PN-10 rating having Cast iron body , SG iron disc & AISI 410 shaft along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be
apply.
100 mm
Make: Castle/Advance/Honeywell/Zoloto | 14 | each | 0 ₹62,300 Lowest |
| 5.10 | SITC of butterfly valve of PN-10 rating having Cast iron body , SG iron disc & AISI 410 shaft along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be
apply.
80 mm
Make: Castle/Advance/Honeywell/Zoloto | 4 | each | 0 ₹15,000 Lowest |
Tender Value
₹1.5 Cr
EMD Value
₹3.1 L
Closing Date
8 Nov 2025, 4:00 pmClosed
Superintending Engineer, Mechanical Hospital Circ
Superintending Engineer, Mechanical Hospital Circ
Design, Supply Installation Testing and Commissioning of Centralized Heating Ventillation and Air Conditioning System at Abhinav Theatre Jammu
2025_PWDJK_293222_1
MHCJ/Tech/e-NIT/2025-26/15
Open Tender
Machineries/ Mechanical Engg Items
Turn-key
90 days
Abhinav Theatre Jammu
AS PER E NIT
2 documents required · 2 mandatory
₹3,000
Superintending Engineer, Mechanical Hospital Circ
₹3.1 L
Superintending Engineer, Mechanical Hospital Circ
11 Dec 2025
25 Oct 2025
10 Nov 2025
25 Oct 2025
8 Nov 2025
3 Nov 2025
25 Oct 2025 - 8 Nov 2025
30 Oct 2025
Amount
Supplying, installing, testing and commissioning of Monoblock centrifugal chilled water pump ( 2 Working +1 Standby ) or( 3 Working +1 Standby ), factory mounted on a common base with electric motor for recirculation of water for the central air conditioning system. All pumps shall be provided with bronze impeller and mechanical seal aligned properly as required . The pump motor shall be suitable for 415 +1-10% volts, 50 cycles, 3 phase power supply. The quoted price shall include cost of thermal insulation and cladding of chilled water pumps. Flow : 2.4 USGPM/ton of chiller capacity Head : 22-27 Mtr ( As per actual calculation of pressure drop) Casing : Cast Iron Impeller : Bronze Shaft : Stainless Steel Make : Kirloskar/Crompton/KSB
Supply, installation, testing and commissioning of Floor Mounted factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanised steel sheet outside & 0.63 mm plain alvanised steel sheet inside with blower, blower section and Blower shall be DIDW FC blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be 25 mm thick & insulated with 42 Kg/m³ density PU foam with thermal break profile . The VFD compatible motor & blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification. AHU Capacity 25000 CFM capacity @120 mm static pressure with 6 row deep cooling coil and having 10 micron filtration. Make : - Zeco/Edgetech/Caryair/Crystal
Chilled water Piping Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : - 125 mm Dia Pipe - 25 mm thick insulation MS Pipe Make : Jindal/Tata/Sail Insulation Make : K-Flex/Supreme/Aerofoam
Chilled water Piping Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : - 100 mm Dia Pipe 25 mm thick insulation MS Pipe Make : Jindal/Tata/Sail Insulation Make : K-Flex/Supreme/Aerofoam
Chilled water Piping Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : - 80 mm Dia Pipe- 25 mm thick insulation MS Pipe Make : Jindal/Tata/Sail Insulation Make : K-Flex/Supreme/Aerofoam
Chilled water Piping Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : - 65 mm Dia Pipe- 25 mm thick insulation MS Pipe Make : Jindal/Tata/Sail Insulation Make : K-Flex/Supreme/Aerofoam
Chilled water Piping Supply, laying , connecting , fixing and testing of Chilled/Hot water MS ERW class "C" pipe complete with all fitting duly insulated as mentioned theirin for closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminium cladding laid underground / floor etc complete all as specified and directed for the following pipes : - 20 mm Dia Pipe- 25 mm thick insulation MS Pipe Make : Jindal/Tata/Sail Insulation Make : K-Flex/Supreme/Aerofoam
SITC of butterfly valve of PN-10 rating having Cast iron body , SG iron disc & AISI 410 shaft along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 100 mm Make: Castle/Advance/Honeywell/Zoloto
SITC of butterfly valve of PN-10 rating having Cast iron body , SG iron disc & AISI 410 shaft along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 80 mm Make: Castle/Advance/Honeywell/Zoloto
SITC of butterfly valve of PN-10 rating having Cast iron body , SG iron disc & AISI 410 shaft along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 65 mm Make: Castle/Advance/Honeywell/Zoloto
SITC of balancing valve of PN-10 rating having Body: CI : IS : 210 FG:220 , Bonnet: SG Iron IS :1865 GR 420/7 , Seat: Nitrile/EPDM, Stem: AISI 410// Disc: EN3 along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 100 mm Make: Castle/Advance/Honeywell/Zoloto
SITC of balancing valve of PN-10 rating having Body: CI : IS : 210 FG:220 , Bonnet: SG Iron IS :1865 GR 420/7 , Seat: Nitrile/EPDM, Stem: AISI 410// Disc: EN3 along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 80 mm Make: Castle/Advance/Honeywell/Zoloto
SITC of balancing valve of PN-10 rating having Body: CI : IS : 210 FG:220 , Bonnet: SG Iron IS :1865 GR 420/7 , Seat: Nitrile/EPDM, Stem: AISI 410// Disc: EN3 along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 65 mm Make: Castle/Advance/Honeywell/Zoloto
SITC of Dual Plate Check valve of PN-10 rating having Body Cast Iron , Disc SS-304 along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 100 mm Make: Castle/Advance/Honeywell/Zoloto
SITC of Y-Strainer of PN-10 rating having Body: Cast Iron/MS fabricated , Screen: SS-304, End Connection: Flanged End Connection along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 80 mm Make :Castle/Sant/Honeywell/Zoloto
SITC of Y-Strainer of PN-10 rating having Body: Cast Iron/MS fabricated , Screen: SS-304, End Connection: Flanged End Connection along with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 100 mm Make :Castle/Sant/Honeywell/Zoloto
SITC of 3-Way valve of PN-10 rating along actuator, Thermostat & transformer with all necessary fittings like flange , nut bolts, Gasket etc. After fixing of valve insulation of pipe thicknesses along with 26 G aluminum cladding shall be apply. 80 mm Make: Honeywell/Siemens/Anergy
SITC of automatic Air purge valve of 15 mm Make : Castle/Zoloto/Advance/Anergy
SITC of ball vave 15 mm Make : Castle/Zoloto/Advance/Anergy
SITC of ball vave 25 mm Make : Castle/Zoloto/Advance/Anergy
SITC of ball vave 32 mm Make : Castle/Zoloto/Advance/Anergy
SITC of dial type pressure gauge Make : H.guru/Fiebig/Wari
SITC of Thermometer Make : H.guru/Fiebig/Wari
Supply & lay XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip or wire, heavy duty, LT cable ISI marked with aluminum /Copper conductor 1100 volt grade of following size laid in trenches / duct passing /on cable cable tray/through pipe or fixed on wall and connecting and testing etc complete all as specified & directed. 3.5 C X 70 Sqmm - Aluminum Conductor - (Chiller ) Make : Ecko/KEI/RR Kabel/Havells/Polycab
Supply & lay XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip or wire, heavy duty, LT cable ISI marked with aluminum /Copper conductor 1100 volt grade of following size laid in trenches / duct passing /on cable cable tray/through pipe or fixed on wall and connecting and testing etc complete all as specified & directed. 3C x 25 Sqmm - Aluminum Conductor (Pump) Make : Ecko/KEI/RR Kabel/Havells/Polycab
Supply & lay XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip or wire, heavy duty, LT cable ISI marked with aluminum /Copper conductor 1100 volt grade of following size laid in trenches / duct passing /on cable cable tray/through pipe or fixed on wall and connecting and testing etc complete all as specified & directed. 3C x 6 Sqmm - Aluminum Conductor (Pump) Make : Ecko/KEI/RR Kabel/Havells/Polycab
Supply and lay of PVC insulated flexible control cable 3 c x 1.5 Sqmm Make : Ecko/KEI/RR Kabel/Havells/Polycab
SITC of Water Flow Switch Make : Honeywell/Anergy/Danfoss
HVAC ELECTRICAL PANEL Designing, fabricating, transporting to site, Installation, testing and commissioning of floor mounted indoor type panel, self supported, compartmentalized LT cubical pattern (Extendable Type) metal clad switch board, fabricated from 2mm (14 G) thick CRCA sheet steel suitable 415 V, 3 phase, 4 wire, 50 HZ AC supply and equipped with PVC sleeved aluminum bus bars of specified rating and following switch gears inter connected by PVC sleeved solid conductors, including 7-tank cleaning, degreasing, phosphating process and treatment of panel with anti-corrosive zinc based primer paint and finally powder coating the panel, complete with earthing terminals, cable and bus bar alleys and hoisting hooks as required. Necessary cable alley, spare switches, int ernal wiring, control wiring / cabling shall also be included. Incomer : Busbar Chamber: (i) Al busbar of rated capacity 2000 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 01 Set (of 03 P+1 N busbars) Incoming: (i) 800 A, 415 V, 50 kA, 50 Hz, FP ACB with with adjustable overload settings, adjustable short-circuit settings and thermal Magnetic based trip- 01 Nos. (ii) LED phase indicators (Yellow, Blue, Red)- 01 Set (iii) Multifunction meter with CTs - 01 Nos. Outgoing: for all chillers proposed to be installed including standby units 325 A, 415 V, 50 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and thermal Magnetic based trip unit for chillers - for all chillers proposed to be installed including standby units Note :outgoing of chiller unit may be design as per OEM rating of chiller. Design change shall be accepted as per OEM of chiller main incoming supply requirement. Chilled Water Pump : for all pumps proposed to be installed including standby units. (iii) 63 A, 415 V, TP MCB for chilled water pumps including fully automatic starter suitable for 10 HP or higher capacity as per Chilled water motor rating complete with connector, Auto manual Selctor switch , push button,On ,Off, Trip Indicating light , over load protection,SPPR, Multifunction meter – for all pumps proposed to be installed including standby units Hot water Generator 250 KW - 1 #( 1 W) (i) 500 A, 415 V, 50 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and thermal Magnetic based trip unit for HWG - 1 Nos. Note : outgoing of HWG unit may be design as per OEM rating of unit. Design change shall be accepted as per OEM of HWG main incoming supply requirement. AHU Outgoings to AHU sub Panel - 2 # 125 AMp, 415 V, 50 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and thermal Magnetic based trip unit for chillers - 2 Nos. Switch Gear Make : L&T/ABB/Siemens
Supplying & installing following sizes of perforated Galavanised Iron cable tray with perforation more than 17.5 % in convenient sections, joined with connectors, suspended from ceiling with GI suspenders including GI Bolts & nuts etc. as required 450 mm x50mmx 2 mm Make : MEM/Slotco/Reco
Supplying & installing following sizes of perforated Galavanised Iron cable tray with perforation more than 17.5 % in convenient sections, joined with connectors, suspended from ceiling with GI suspenders including GI Bolts & nuts etc. as required 300 mm x50mm x 1.6mm Make : MEM/Slotco/Reco
Supplying & installing following sizes of perforated Galavanised Iron cable tray with perforation more than 17.5 % in convenient sections, joined with connectors, suspended from ceiling with GI suspenders including GI Bolts & nuts etc. as required 150mm x 50mm x 1.6 mm Make : MEM/Slotco/Reco
SITC of MS iron for support, stand including one coat of red oxide & one coat of black paint .
SITC of GI strip of size 25 mm x 3 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in cable tray for loop earthingetc complete all as specified and directed.
SITC of GI 8 SWG earth wire
Supply, laying and fixing of drain pipe of GI Tubing light grade with all fittings for cable protection laid in trenches or fixed to wall / laid in flooring, complete all as specified and directed. 25 mm Make : Jindal/Tata/SAIL
Supply, laying and fixing of drain pipe of GI Tubing light grade with all fittings for cable protection laid in trenches or fixed to wall / laid in flooring, complete all as specified and directed. 32 mm Make : Jindal/Tata/SAIL
Supply, laying and fixing of drain pipe of GI Tubing light grade with all fittings for cable protection laid in trenches or fixed to wall / laid in flooring, complete all as specified and directed. 50 mm Make : Jindal/Tata/SAIL
Required Duct extension in lobby area for proper air distribution withh diffuser, VCD, Insulation, support as required for proper air distribution
Civil work : civil Foundation of chiller, pump , panel etc as per the Chiller OEM approved drawing.
SITC of hot water Generator equipped with sufficient number of electrical immersion heaters.The Pressure vessel shall be constructed as per ASME standards and insulated on all sides with 50 mm thick fiber glass cladded with 0.6 mm aluminium sheet in neat and clean manner.The generator shall be equipped with all automatic and safety control such as manual reset high temperature water outlet, Microprocessor based step controller and recycling relay, ON’ OFF” switch thermostats, pilot light,low water cut off and other controls as per manufacturers recommendations. All basic control terminals shall be located in a integral control cabinet factory wild and tested.The generator shall be suitable for 415± 10% volts,50 cycle, 3 phase power supply.The entire generator shall be factory assembled and tested at 250 PSI pressure.250 KW.Make:KEPL/Rapidcool/Thermax
Dismantling of Old Equipments/Support/Accessories 1. Dismantling of Existing Central Plant & shifting it to the 150- 200 mtr to scrap yard safely . 1.1 Chiller 1.2 Pipe . 1.3 Cable. 1.4 Cable tray. 1.5 Panel. 1.6 Any Other Equipment/Support/Accessories installed with old system
Buyback of Existing system with chiller, Pipe, Pump, AHU, Electrical Panel, Cable tray & Cable etc (Minimum @5% of the estimated amount from S. No. 1 to 26) i.e Not less than 7.18 lacs
Cost of Three year CAMC after first 02 Year warranty
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.43 MB
BOQ_947233.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .