Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.0 LAdmitted-Finance | ₹2.0 L | L1 | Admitted-Finance |
| 2 | L2₹2.0 LAdmitted-Finance | ₹2.0 L | L2 | Admitted-Finance |
| 3 | Rejected-Technical | - | - | Rejected-Technical Rejected, Requisite documents not submitted |
| Sl No | Description | Qty | Unit | BUDOO ELECTRICALS AND SUPPLIERS L2 | MARS ELECTRICALS MECHNICALS & SUPPLIERS L1 |
|---|---|---|---|---|---|
| 1.00Providing of CT/PT operated HT metering at Forensic Science Laboratory falling under the jurisdiction of ESD Watalkadal ED 3rd (Turnkey Basis). | |||||
| 1.01 | Design, Fabrication, Supply, installation, testing and commissioning of 11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No MS channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door | 1 | No. | 40,000 ₹40,000 | 20,000 ₹20,000 |
| 1.02 | Supply, installation, testing and commissioning of Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5. The CT ratio shall be as under:. CT ratio:-
i. 2.5 /5 for 25kVA DT
ii. 5/5 for 63kVA DT
iii. 7.5/5 for 100kVA DT
iv. 15/5 for 200kVA DT
v. 20/5 for 250kVA DT
vi. 25/5 for 400kVA DT
vii. 50/5 for 630kVA DT
viii. 75/5 for 1MVA DT | 1 | Set | 35,000 ₹35,000 | 17,250 ₹17,250 |
| 1.03 | Supply, installation, testing and commissioning of 11kV/ 110 V, Three phase epoxy resin cast PT with rated burden 15VA per phase andaccuracy class 0.5 or better and conforming to IS:3156 (part-I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23 KV pf for one minute. | 1 | Set | 25,000 ₹25,000 | 18,000 ₹18,000 |
| 1.04 | Supply, installation, testing and commissioning of Bus Bar as per details:
CTs bus bar:- 40x6 mm copper strip or adequate size.
PTs bus bar: Copper wire 8 SWG or 30x0.6mm copper flat strip to connect PT terminal or adequate size duly insulated by the monoplast tape. | 1 | Job | 30,000 ₹30,000 | 1,000 ₹1,000 |
| 1.05 | Supply, installation, testing and commissioning of PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm2 (RYB) and for PT wiring minimum wire size shall be 2.5 mm2 (RYB). | 1 | Job | 2,000 ₹2,000 | 500 ₹500 |
| 1.06 | Supply and fixing of Copper Lugs preferably ring type duly crimped for termination of wires and tapes | 1 | Job | 1,000 ₹1,000 | 500 ₹500 |
| 1.07 | Providing and fixing of Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11 KV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm2. | 1 | job | 500 ₹500 | 500 ₹500 |
| 1.08 | Supply, installation, testing and commissioning of 3-Ph, 3 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS 232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) , Net metering etc. Meter to be provided shall be Net meter supportive with clearly showing the import and export parameters. | 1 | No. | 25,000 ₹25,000 | 40,000 ₹40,000 |
| 1.09 | Supply and fixing of Pedestal made out of G.I Channel of size 75 x 40 mm or angle iron of size (65 x 65 x 5) mm, duly painted as per site requirement for mounting of metering panel including concrete foundation wherever required including cost of nuts and bolts. | 1 | Job | 1,500 ₹1,500 | 500 ₹500 |
Updated dates
Tender Value
₹2.0 L
EMD Value
₹3,940
Closing Date
23 Dec 2025, 4:00 pmClosed
Executive Engineer, ED-3rd Srinagar
Office of Executive Engineer, ED-3rd Srinagar
Providing of CT/PT operated HT metering at Forensic Science Laboratory falling under the jurisdiction of ESD Watalkadal ED 3rd (Turnkey Basis)
2025_PDD_296892_1
ED-III /28 of 2025-26, Dated - 01-12-2025
Open Tender
Electrical Works
15 days
Office of Executive Engineer, ED-3rd Srinagar
Refer SBD, Technical Specification, Drawings
7 documents required · 7 mandatory
₹200
Executive Engineer, ED-3rd Srinagar
₹3,940
29 Dec 2025
1 Dec 2025
24 Dec 2025
1 Dec 2025
23 Dec 2025
4 Dec 2025
4 Dec 2025 - 23 Dec 2025
Amount
Providing of CT/PT operated HT metering at Forensic Science Laboratory falling under the jurisdiction of ESD Watalkadal ED 3rd (Turnkey Basis).
Design, Fabrication, Supply, installation, testing and commissioning of 11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No MS channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door
Supply, installation, testing and commissioning of Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5. The CT ratio shall be as under:. CT ratio:- i. 2.5 /5 for 25kVA DT ii. 5/5 for 63kVA DT iii. 7.5/5 for 100kVA DT iv. 15/5 for 200kVA DT v. 20/5 for 250kVA DT vi. 25/5 for 400kVA DT vii. 50/5 for 630kVA DT viii. 75/5 for 1MVA DT
Supply, installation, testing and commissioning of 11kV/ 110 V, Three phase epoxy resin cast PT with rated burden 15VA per phase andaccuracy class 0.5 or better and conforming to IS:3156 (part-I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23 KV pf for one minute.
Supply, installation, testing and commissioning of Bus Bar as per details: CTs bus bar:- 40x6 mm copper strip or adequate size. PTs bus bar: Copper wire 8 SWG or 30x0.6mm copper flat strip to connect PT terminal or adequate size duly insulated by the monoplast tape.
Supply, installation, testing and commissioning of PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm2 (RYB) and for PT wiring minimum wire size shall be 2.5 mm2 (RYB).
Supply and fixing of Copper Lugs preferably ring type duly crimped for termination of wires and tapes
Providing and fixing of Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11 KV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm2.
Supply, installation, testing and commissioning of 3-Ph, 3 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS 232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) , Net metering etc. Meter to be provided shall be Net meter supportive with clearly showing the import and export parameters.
Supply and fixing of Pedestal made out of G.I Channel of size 75 x 40 mm or angle iron of size (65 x 65 x 5) mm, duly painted as per site requirement for mounting of metering panel including concrete foundation wherever required including cost of nuts and bolts.
Supply and fixing of Independent flexible PVC pipes for CT wiring and PT wiring of appropriate size from HTcompartment to meter compartment
Supply, installation, testing and commissioning of 3 Core 11 kV Aluminium cable XLPE armoured 35 mm2 including cost of clamp for its fixing where ever required.
Supply, installation, testing and commissioning of Cable termination kits suitable for 3 x 35 mm2 XLPE Cable(indoor/outdoor)
Providing and laying of Earthing by way of 40 mm GI Pipe earthing for HT metering. Job includes , excavation, enhancement material and man Hole Chamber (500x450x600)mm with frame and cover.
BUDOO ELECTRICALS AND SUPPLIERS (BID ID -2676695)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.27 MB
Combineapprovedkpdcl.pdf
Other Document • 28.39 MB
BOQ_962218.xls
BOQ • 0.28 MB
SBD28.pdf
Tender Documents • 0.85 MB
Download all tender documents and submit your bid