Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹43.4 CrAdmitted-Finance JAIPUR RAJASTHAN 302019 INDIA UDYAM RJ 17 0101683 | JAIPUR | RAJASTHAN | 302019 | ₹43.4 Cr | L1 | Admitted-Finance |
| 2 | L2₹44.5 CrAdmitted-Finance | ₹44.5 Cr | L2 | Admitted-Finance |
| 3 | L3₹45.4 CrAdmitted-Finance | ₹45.4 Cr | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | JK Electric Engineers Pvt. Ltd. L3 | Devyansh Construction And Developers Pvt Ltd L2 | Suncity Urja Private Limited L1 |
|---|---|---|---|---|---|---|
| 1.00SUPPLY of 132KV MAIN EQUIPMENTS | ||||||
| 1.01 | 3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 2500 Amps of 3 phase,50 c/s and 40 KA for 1 second) along with supporting structure etc. complete in all respects SS body, universal spring charging motor with mandatory sparesi.e, spring charging motor,tripping/closing coil,sf6 gas filling kit and sg6 gas for each breaker. | 6 | No | 2,50,000 ₹15 L | 19,23,105 ₹1.2 Cr | 19,91,250 ₹1.2 Cr |
| 1.02 | 145kV, 50c/s, 2500Amp SCADA compatible, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators without Earthing Switch. Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box | 12 | Set | 5,50,000 ₹66 L | 7,27,200 ₹87.3 L | 7,16,850 ₹86.0 L |
| 1.03 | 145kV, 50c/s, 2500Amp SCADA compatible, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with one Earthing Switch. Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box. | 2 | Set | 5,90,000 ₹11.8 L | 8,30,000 ₹16.6 L | 7,16,850 ₹14.3 L |
| 1.04 | 145kV, 50c/s, 2500Amp SCADA compatible, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with two Earthing Switch. Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box.. | 4 | Set | 6,75,000 ₹27 L | 9,29,000 ₹37.2 L | 7,16,850 ₹28.7 L |
| 1.05 | Single phase, 50c/s145KV Current Transformers, (600-300-150/1-1-1-1-1A or 1200-600-300/1-1-1-1-1A or 2000-1600-1200/1-1-1-1-1A or as per site specifications) 40 KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA 3 NO PS Core 01 No 5P20 01 No 0.2S Class, galvanized tank including first fill of Transformer oil plus 20% extra and all accessories, auxiliaries etc. | 18 | No | 2,65,000 ₹47.7 L | 3,06,000 ₹55.1 L | 2,86,740 ₹51.6 L |
| 1.06 | Neutral Current Transformer with Current Rating 1A/5A and VA Burden15VA. Ratio as per site specifications. 02 No PS class cores, 01 No 0.2 S Core, Galvanized tank 31.5KA for one second, rated dynamic current 31.5KA (Peak), including first fill of Transformer oil plus 20% extra and all accessories, auxiliaries etc. | 1 | No | 2,15,539 ₹2.2 L | 1,37,883 ₹1.4 L | 1,59,300 ₹1.6 L |
| 1.07 | Single Phase 50c/s, outdoor metaloxide gapless type, 120KV(rms) Surge Arrestor class 3 including Surge counters/monitors, insulating base all associated accessories, auxiliaries. | 15 | No | 79,031 ₹11.9 L | 78,375.6 ₹11.8 L | 51,772.5 ₹7.8 L |
| 1.08 | 132KV Control and Relay Panel for Line/Feeder Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/Schneider wit IEC 61850 compatibility, including Distance Recorder and under frequency relay (IST Line protection) distance protection directional O/C & E/F protection (backup protection), local breaber backup (LBB) protection. | 2 | No | 11,85,463 ₹23.7 L | 12,60,106 ₹25.2 L | 11,15,100 ₹22.3 L |
| 1.09 | 132KV Control and Relay Panel for Transformer Bay Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/Schneider wit IEC 61850 compatibility, including Differential Protection, Directional O/C & E/F protection (on HV & LV side), numerical communicable REF Protection Relay, Over Fluxing protection, local breaker backup (LBB) protection separate relay for primary and back up protection. | 1 | No | 12,21,386 ₹12.2 L | 13,50,000 ₹13.5 L | 13,54,050 ₹13.5 L |
Updated dates
Tender Value
₹48.5 Cr
EMD Value
₹97.0 L
Closing Date
3 Mar 2026, 4:00 pmClosed
Executive Engineer, TLMD-VIII, JKPTCL, Jammu.
Office of the Executive Engineer, TLMD-VIII, JKPTCL, Ambedkar Chowk, Jammu.
Construction of 1X50 MVA, 132/33 Grid Station, Mendhar, District Poonch, of U.T of J and K
2026_PDD_300832_1
E NIT no TLMD-VIII/J/T/12 of 2025-26 dated-16/01/2026
Open Tender
Electrical Works
730 days
Mendhar
Please refer Tender documents.
3 documents required · 3 mandatory
₹25,000
Executive Engineer, TLMD-VIII, JKPTCL, Jammu
₹97.0 L
Office of the Executive Engineer, TLMD-VIII, Jammu
27 Mar 2026
21 Jan 2026
5 Mar 2026
21 Jan 2026
3 Mar 2026
21 Jan 2026
28 Jan 2026
SUPPLY of 132KV MAIN EQUIPMENTS
3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 2500 Amps of 3 phase,50 c/s and 40 KA for 1 second) along with supporting structure etc. complete in all respects SS body, universal spring charging motor with mandatory sparesi.e, spring charging motor,tripping/closing coil,sf6 gas filling kit and sg6 gas for each breaker.
145kV, 50c/s, 2500Amp SCADA compatible, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators without Earthing Switch. Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box
145kV, 50c/s, 2500Amp SCADA compatible, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with one Earthing Switch. Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box.
145kV, 50c/s, 2500Amp SCADA compatible, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with two Earthing Switch. Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box..
Single phase, 50c/s145KV Current Transformers, (600-300-150/1-1-1-1-1A or 1200-600-300/1-1-1-1-1A or 2000-1600-1200/1-1-1-1-1A or as per site specifications) 40 KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA 3 NO PS Core 01 No 5P20 01 No 0.2S Class, galvanized tank including first fill of Transformer oil plus 20% extra and all accessories, auxiliaries etc.
Neutral Current Transformer with Current Rating 1A/5A and VA Burden15VA. Ratio as per site specifications. 02 No PS class cores, 01 No 0.2 S Core, Galvanized tank 31.5KA for one second, rated dynamic current 31.5KA (Peak), including first fill of Transformer oil plus 20% extra and all accessories, auxiliaries etc.
Single Phase 50c/s, outdoor metaloxide gapless type, 120KV(rms) Surge Arrestor class 3 including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
132KV Control and Relay Panel for Line/Feeder Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/Schneider wit IEC 61850 compatibility, including Distance Recorder and under frequency relay (IST Line protection) distance protection directional O/C & E/F protection (backup protection), local breaber backup (LBB) protection.
132KV Control and Relay Panel for Transformer Bay Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/Schneider wit IEC 61850 compatibility, including Differential Protection, Directional O/C & E/F protection (on HV & LV side), numerical communicable REF Protection Relay, Over Fluxing protection, local breaker backup (LBB) protection separate relay for primary and back up protection.
132KV Control and Relay Panel for Bus Coupler Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/Schneider with IEC 61850 compatibility, including Bus Bar protection suitable for min 15 No bays.
Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/√3) KV/(110/√3)V, One min power freq withstand 275KVrms galvanized tank. Acc class 0.2
132KV Post Insulators Solid Core Type/Polymer type, Power Frequency Withstand Voltage 275KV rms Dry lightning impulse withstand voltage±650(KVP)
SUPPLY OF STRUCTURES
Galvanised Steel Structures (Lattice Structure)
Galvanised Fasteners, Nuts and Bolts
SUPPLY OF POWER AND CONTROL CABLES
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
12 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,Galvanised steel wire/strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
2Core, 6sqmm, 1100V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete
4Core, 6sqmm, 1100V, PVC insulated ,PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
Marshalling kiosk with Kiosk frames stainless steel/hot dip galvanized structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. shall be provided with the degree of protection of IP:55, with Copper Bar earthing for 132 KV. I. Marshalling Box shall be outdoor type, rigidly constructed out of sheet steel or aluminium and shall be dust, water and vermin proof. Sheet steel used shall be at least 2.0 mm thick cold rolled. 2. Bay Marshilling Kiosk shall have three separate distinct compartment for the following purpose i) To receive two incoming 415V, 3 phase 63 A AC supply with auto changeover and MCB Unit and distribute minimum six outgoing 415V 3 phase 16 A, supply control by MCB with fuse failure remote indication ii) To distribute minimum 10 outgoing, 240 V, 10A supplies to be control by MCB to be drawn from 3 phase incomer. iii) 200 no. of terminal blocks in vertical formation for interlocking facilities 3. All sheet steel works shall be degreased, pickled, phosphate and then applied with two coats of Zinc chromate primer and two coats of finishing synthetic enamel paint. The colour of finishing paint shall be light admiral grey in accordance with shade no. 697 of IS:5 outside & inside shall be glossy white.
SUPPLY OF CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose (a) Aluminum = 54/3.53 mm (b)Steel= 7/3.53 mm overall diameter = 31.77 mm Approx. Wt.= 1998kg/km ultimate strength = 159.60KN
Single Tension Fittings For Single moose shall have minimum failing load of 100% ultimate strength of conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN.
Single Suspension Fittings For Single moose shall have minimum failing load of 50% ultimate strength of conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Tension Fittings For Twin moose shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120KN.
Single Suspension Fittings For Twin moose shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Disc Insulators 120 KN, Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Disc Insulators 90 KN, Ball& Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
T Clamps 0.5/0.4, made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 0.4 / Twin 0.4 , made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P I Clamps 0.2 made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps 0.4 made of Aluminum Alloy and shall comply in all respects withIS:5561-1970 (latest edition)
OPGW, dual window single-mode with mode field diameter 8.6-9.5 um, cladding diameter 125 um+_ 1um
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’shackles, jumper terminals, nuts &bolts and washers etc. slip strength shall not be less than 95% of the ultimate strength of theground wire. Conductivity shall not be less than corresponding conductivity of GSS ground wire
SUPPLY OF 33KV EQUIPMENTS
33KV VCB (36 KV, 2000 Amps of 3 phase, 50 c/s and 31.5 KA for 3 sec)outdoor type with all accessories and auxiliaries along with supporting structure etc. complete in all respects SS body, universal spring charging motor with mandatory spares..i.e, spring charging motor,tripping/closing coil, and vcb bottle for each vcb
36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box
36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with One Earthing Blades Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box
36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with two Earthing Blades Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box
Single phase, 50c/s 36 KV Current Transformers (1200-600-300/1-1-1-1A or 2000-1600-1200/1-1-1-1A or1200-800-400/1-1-1-1A or as per site specifications) ,31.5 KA for one second, rated dynamic current 31.5 KA (peak), Class A insulation, Burden 20VA, 2 NO PS Core 01 No 5P20 01 No 0.2S Class, galvanized tank including first fill of Transformer oil plus 20% extra and all accessories, auxiliaries etc
Single Phase 50c/s, outdoor metal oxide gapless type, 30 KV (rms) Surge Arrestor class 3 including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
33 KV Control and Relay Panel for Line/Feeder Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/ Schneider wit IEC 61850 compatibility, with under frequency relay E/F protection (Main protection) and O/C (Backup protection).
33 KV Control and Relay Panel for Transformer Bay Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/ Schneider wit IEC 61850 compatibility.
33 KV Control and Relay Panel for Auxillary Bay Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/ Schneider wit IEC 61850 compatibility.
33 KV Control and Relay Panel for Bus Coupler Bay with back up protection Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/ Schneider wit IEC 61850 compatibility.
33 KV Post Insulators Solid Core Type, Power Frequency Withstand Voltage 95 KV RMS Dry lightning impulse withstand voltage ± 170 (KVP)
Single phase, 50 c/s outdoor 33KV PT (33/√3) KV/ (110/√3)V with Highest System Voltage 36KV, One min power freq withstand 70KVrms, Galvanized tank. Acc Class 0.2
SUPPLY OF STRUCTURES
Galvanised Steel Structures (Lattice Structure)
Galvanised Fasteners, Nuts and Bolts
SUPPLY OF POWER AND CONTROL CABLES
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete.
10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete.
2Core, 6sqmm, 1100V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete.
4Core, 6sqmm, 1100V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete.
Marshalling kiosk with Kiosk frames stainless steel/hot dip galvanized structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. shall be provided with the degree of protection of IP:55, with Copper Bar earthing for 33 KV. I. Marshalling Box shall be outdoor type, rigidly constructed out of sheet steel or aluminium and shall be dust, water and vermin proof. Sheet steel used shall be at least 2.0 mm thick cold rolled. 2. Bay Marshilling Kiosk shall have three separate distinct compartment for the following purpose i) To receive two incoming 415V, 3 phase 63 A AC supply with auto changeover and MCB Unit and distribute minimum six outgoing 415V 3 phase 16 A, supply control by MCB with fuse failure remote indication ii) To distribute minimum 10 outgoing, 240 V, 10A supplies to be control by MCB to be drawn from 3 phase incomer. iii) 200 no. of terminal blocks in vertical formation for interlocking facilities 3. All sheet steel works shall be degreased, pickled, phosphate and then applied with two coats of Zinc chromate primer and two coats of finishing synthetic enamel paint. The colour of finishing paint shall be light admiral grey in accordance with shade no. 697 of IS:5 outside & inside shall be glossy white
SUPPLY OF CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose (a) Aluminum = 54/3.53 mm (b)Steel= 7/3.53 mm overall diameter = 31.77 mm Approx. Wt.= 1998kg/km ultimate strength = 159.60KN
Single Tension Fittings For Single moose shall have minimum failing load of 100% ultimate strength of conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN.
Single Suspension Fittings For Single moose shall have minimum failing load of 50% ultimate strength of conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Tension Fittings For Twin moose shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120KN.
Single Suspension Fittings For Twin moose shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Disc Insulators 120 KN, Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Disc Insulators 90 KN, Ball& Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
T Clamps 0.5/0.4, made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 0.4 / Twin 0.4 , made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Spacers for Twin ACSR Conductor
P I Clamps 0.2 made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps 0.4 made of Aluminum Alloy and shall comply in all respects withIS:5561-1970 (latest edition)
OPGW, dual window single-mode with mode field diameter 8.6-9.5 um, cladding diameter 125 um+_ 1um
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’shackles, jumper terminals, nuts &bolts and washers etc. slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding conductivity of GSS ground wire
SUPPLY OF POWER TRANSFORMER
Cost of 50 MVA (ONAN/ONAF), 132/33kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES, HV and LV connectors and other required accessories and fittings with online DGA monitoring Kit on line dehydration kit and maintenance free automatic breathers as per detailed technical specs. With Mandatory spares as per SBD.(Current density for HV/LV winding not more than 2.4 A/sq. mm. Core flux density not more than 1.5 T.
SUPPLY OF STRUCTURES
Galvanised Steel Structures (Lattice Structure)
Galvanised Fasteners, Nuts and Bolts
SUPPLY OF POWER AND CONTROL CABLES
3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete
SUPPLY OF CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose (a) Aluminum = 54/3.53 mm (b)Steel= 7/3.53 mm overall diameter = 31.77 mm Approx. Wt.= 1998kg/km ultimate strength = 159.60KN
Single Tension Fittings For Single moose shall have minimum failing load of 100% ultimate strength of conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN.
Single Tension Fittings For Twin moose shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120KN.
T Clamps 0.5/0.4, made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 0.4 / Twin 0.4 , made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Disc Insulators 120 KN, Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Supply of Auxillary Transformers
Cost of 33/0.433 KV, 250 KVA, 3-Phase Distribution Transformers with Bimettalic Terminal Connectors Energy Level-2 Copper wound
300 mm2 3.5 Core Cable 1.1KV Grade, Armoured, XLPE, insulated stranded conductor FRLS type
SUPPLY of COMMON MISCELLANEOUS EQUIPMENTS.
Battery Bank 110 V, 300 AH , of 55 No. cells of 2 V each, sealed maintenance free VRLA type, High impact Polyprophelene copolymer Container, flame retardant.
Battery Bank 48 V, 450AH , of 24 No. cells of 2 V each, sealed maintenance free VRLA type, High impact Polyprophelene copolymer container, flame retardant.
110V Battery charger (Three phase) :Battery charger as well as Automatic Regulators shall be of static type compatible with VRLA Batteries. Should also have necessary temperature sensors. should have both Automatic and Manual control of output voltage and current. (i) Float charging and load current ratings: 30Amp/60Amp/70Amp/ 100Amp at 220 V to 252 VD.C. Boost charging current rating: 50Amps/55Amp/60Amp/70Amp/ 80Amp / 100 Amp at 198 V to 296/302 VD.C.
48V, DCPS SMPS Based DC Power supply system of 35 Amp rating
DC Distribution Board frames shall be fabricated using mild steel structural section or pressed and shaped Cold rolled sheet steel of thickness not less than 2.0 mm and shall be provided with a degree of protection of IP-52 as per IS:2147, bus bar chamber having a degree of protection of IP-42 as per IS:2147. Finishing paint on panels shall be of shade 692 (smoke grey) of IS:5. The inside shall be properly stoved The paint thickness shall be at least 50microns.Bus bars and jumper connections shall be of high conductivity aluminum alloy or copper of adequate size.
DC Distribution Panel (110V, DC) with 1No. 10Amp. Air break ckt .Double pole for battery incoming supply with DP MCBs & indicating Lamps etc.
DC Distribution Panel (48V, DC) with 1No. 10Amp. Air break ckt. Double pole for battery incoming supply with DP MCBs & indicating Lamps etc.
AC Distribution Panel (415 V, AC) complete with ckt .Breakers, indicating Lamps etc for 132/33KV Grid Station.
250 KVA Oil cooled servo stabilizer 3-phase 4 wire copper wound indoor type, input voltage range220-460V, output 400V ± 1% having, Digital control, Response time < 10ms ,Automatic Switch-Off against:· Under/Over-Voltage· Over-Load & Short–Circuit ·Single Phasing, Class C Type Secondary surge Protection
Power cables for AC/DC network in Control room for 132/33 KV Grid Station including control desk.
Const. power with avg. 5KM 33 kV line (S/C 0.2 ACSR with 11 mtr ST Pole),, transformer and electricity charges.
RTU panel for SCADA for 132/33 KV Grid Stationas per CEA guidelines and latest IS amended upto date
Circuit Breaker Operation Analyzer as per CEA guidelines and latest IS amended upto date
Winding Resistance Measurementas per CEA guidelines and latest IS amended upto date
Micro Ohm Meteras per CEA guidelines and latest IS amended upto date
Air Conditioning /Central Heating for 132/33 KV Grid Station as per specifications and as per CEA guidelines and latest IS amended upto date
High Mast Yard Lighting 200 W LED Lamps make Havells, Bajaj) With 12 Fittings & Feeder Pillars Having Timers For Automatic On-Off including aviation light. Including monopole,laying of foundation cabling etc as pr site specification/requirement.
125 KVA DG Set, 3 phase, silent type, Rated Engine Power at 100% load KW: 114.8 rated current capacity @ 0.8 PF, 173.9 Amps including construction of foundation, canopy, local chemical earthing pit, cabling etc, as per site specificarion/requirement and as per CEA guidelines and latest IS amended upto date
SUPPLY OF ADDITIONAL EQUIPMENTS
Internal Communication-Telephone/WiFi Net work CCTV base survelliance system with HD cameras, network routers, LAN (CAT-6 cable), NVR with high capacity (2 TB or more) HDD, LCD/LED HD TV, and other works as necessary.
Rotating CCTV N/W IPIR Night Vision speed dome camera 360 along with cables and all necessary accessories as mentioned in the technical specifications with40-43 inches LED T.V with VMS.
Tan Delta & capacitance measurement kit. The test set shall be fully automatic, microprocessor based and designed for condition assessment of electrical insulation in high voltage apparatuses such as Transformers, Reactors, bushings, CTs, CVTs, Circuit Breakers, rotating machines etc with output up to 12 V at frequency 45Hz, output test current @ 12 KV: 100 mA continuous and 300 Ma intermittent or better. Along with test lead and accessories and transport case with wheels.as per latest IS amended upto date
Digital BDV oil test kit (100 KV).as per CEA guidelines and latest IS amended upto date
High Vacuum oil Filtration Plant 6000 LPH as per CEA guidelines and latest IS amended upto date
20 MT Diesel Hydraulic Rough Terrain Mobile Crane/Man lifter as per latest IS amended upto date
Fire Fighting System.Fire detection and alarm for control room building as per CEA guidelines and latest IS amended upto date
Event Logger, Disturbance Recorder & GPS System time synchronizing unit with PC
Erection,testing and commissioning of 132KV Main Equipments
3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 2500 Amps of 3 phase,50 c/s and 40 KA for 1 second) along with supporting structure etc. complete in all respects SS body, universal spring charging motor with mandatory sparesi.e, spring charging motor,tripping/closing coil,sf6 gas filling kit and sg6 gas for each breaker.
145kV, 50c/s, 2500Amp SCADA compatible, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators without Earthing Switch. Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box
145kV, 50c/s, 2500Amp SCADA compatible, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with one Earthing Switch. Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box.
145kV, 50c/s, 2500Amp SCADA compatible, 40kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with two Earthing Switch. Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box..
Single phase, 50c/s145KV Current Transformers, (600-300-150/1-1-1-1-1A or 1200-600-300/1-1-1-1-1A or 2000-1600-1200/1-1-1-1-1A or as per site specifications) 40 KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA 3 NO PS Core 01 No 5P20 01 No 0.2S Class, galvanized tank including first fill of Transformer oil plus 20% extra and all accessories, auxiliaries etc.
Neutral Current Transformer with Current Rating 1A/5A and VA Burden15VA. Ratio as per site specifications. 02 No PS class cores, 01 No 0.2 S Core, Galvanized tank 31.5KA for one second, rated dynamic current 31.5KA (Peak), including first fill of Transformer oil plus 20% extra and all accessories, auxiliaries etc.
Single Phase 50c/s, outdoor metaloxide gapless type, 120KV(rms) Surge Arrestor class 3 including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
132KV Control and Relay Panel for Line/Feeder Duplex wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/Schneider wit IEC 61850 compatibility, including Distance Recorder and under frequency relay (IST Line protection) distance protection directional O/C & E/F protection (backup protection), local breaber backup (LBB) protection.
132KV Control and Relay Panel for Transformer Bay Duplex wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/Schneider wit IEC 61850 compatibility, including Differential Protection, Directional O/C & E/F protection (on HV & LV side), numerical communicable REF Protection Relay, Over Fluxing protection, local breaker backup (LBB) protection separate relay for primary and back up protection.
132KV Control and Relay Panel for Bus Coupler Duplex wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/Schneider with IEC 61850 compatibility, including Bus Bar protection suitable for min 15 No bays.
Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/√3) KV/(110/√3)V, One min power freq withstand 275KVrms galvanized tank. Acc class 0.2
132KV Post Insulators Solid Core Type/Polymer type, Power Frequency Withstand Voltage 275KV rms Dry lightning impulse withstand voltage±650(KVP)
Erection,testing and commissioning of 132KV Structures
Galvanised Steel Structures (Lattice Structure)
Galvanised Fasteners, Nuts and Bolts
Erection,testing and commissioning of 132KV Power and Control Cables
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
12 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,Galvanised steel wire/strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
2Core, 6sqmm, 1100V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete
4Core, 6sqmm, 1100V, PVC insulated ,PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
Marshalling kiosk with Kiosk frames stainless steel/hot dip galvanized structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. shall be provided with the degree of protection of IP:55, with Copper Bar earthing for 132 KV. I. Marshalling Box shall be outdoor type, rigidly constructed out of sheet steel or aluminium and shall be dust, water and vermin proof. Sheet steel used shall be at least 2.0 mm thick cold rolled. 2. Bay Marshilling Kiosk shall have three separate distinct compartment for the following purpose i) To receive two incoming 415V, 3 phase 63 A AC supply with auto changeover and MCB Unit and distribute minimum six outgoing 415V 3 phase 16 A, supply control by MCB with fuse failure remote indication ii) To distribute minimum 10 outgoing, 240 V, 10A supplies to be control by MCB to be drawn from 3 phase incomer. iii) 200 no. of terminal blocks in vertical formation for interlocking facilities 3. All sheet steel works shall be degreased, pickled, phosphate and then applied with two coats of Zinc chromate primer and two coats of finishing synthetic enamel paint. The colour of finishing paint shall be light admiral grey in accordance with shade no. 697 of IS:5 outside & inside shall be glossy white.
Erection,testing and commissioning of 132KV Conductor and Hardware Fittings
500mm2 ACSR Moose (a) Aluminum = 54/3.53 mm (b)Steel= 7/3.53 mm overall diameter = 31.77 mm Approx. Wt.= 1998kg/km ultimate strength = 159.60KN
Single Tension Fittings For Single moose shall have minimum failing load of 100% ultimate strength of conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN.
Single Suspension Fittings For Single moose shall have minimum failing load of 50% ultimate strength of conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Tension Fittings For Twin moose shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120KN.
Single Suspension Fittings For Twin moose shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Disc Insulators 120 KN, Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Disc Insulators 90 KN, Ball& Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
T Clamps 0.5/0.4, made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 0.4 / Twin 0.4 , made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P I Clamps 0.2 made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps 0.4 made of Aluminum Alloy and shall comply in all respects withIS:5561-1970 (latest edition)
OPGW, dual window single-mode with mode field diameter 8.6-9.5 um, cladding diameter 125 um+_ 1um
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’shackles, jumper terminals, nuts &bolts and washers etc. slip strength shall not be less than 95% of the ultimate strength of theground wire. Conductivity shall not be less than corresponding conductivity of GSS ground wire
Erection,testing and commissioning of 33KV Equipments
33KV VCB (36 KV, 2000 Amps of 3 phase, 50 c/s and 31.5 KA for 3 sec)outdoor type with all accessories and auxiliaries along with supporting structure etc. complete in all respects SS body, universal spring charging motor with mandatory spares..i.e, spring charging motor,tripping/closing coil, and vcb bottle for each vcb
36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box
36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with One Earthing Blades Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box
36kV, 50c/s , 2500 Amp, 31.5 kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with two Earthing Blades Copper fixed and moving contact/ Copper current carrying parts, galvanized iron mechanism box
Single phase, 50c/s 36 KV Current Transformers (1200-600-300/1-1-1-1A or 2000-1600-1200/1-1-1-1A or1200-800-400/1-1-1-1A or as per site specifications) ,31.5 KA for one second, rated dynamic current 31.5 KA (peak), Class A insulation, Burden 20VA, 2 NO PS Core 01 No 5P20 01 No 0.2S Class, galvanized tank including first fill of Transformer oil plus 20% extra and all accessories, auxiliaries etc
Single Phase 50c/s, outdoor metal oxide gapless type, 30 KV (rms) Surge Arrestor class 3 including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
33 KV Control and Relay Panel for Line/Feeder Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/ Schneider wit IEC 61850 compatibility, with under frequency relay E/F protection (Main protection) and O/C (Backup protection).
33 KV Control and Relay Panel for Transformer Bay Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/ Schneider wit IEC 61850 compatibility.
33 KV Control and Relay Panel for Auxillary Bay Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/ Schneider wit IEC 61850 compatibility.
33 KV Control and Relay Panel for Bus Coupler Bay with back up protection Duplex completely wired including Substation automation supporting IEDs/numerical relays of make ABB/Siemens/GE Micom/ Alstom/ Schneider wit IEC 61850 compatibility.
33 KV Post Insulators Solid Core Type, Power Frequency Withstand Voltage 95 KV RMS Dry lightning impulse withstand voltage ± 170 (KVP)
Single phase, 50 c/s outdoor 33KV PT (33/√3) KV/ (110/√3)V with Highest System Voltage 36KV, One min power freq withstand 70KVrms, Galvanized tank. Acc Class 0.2
Erection,testing and commissioning of 33KV Structures
Galvanised Steel Structures (Lattice Structure)
Galvanised Fasteners, Nuts and Bolts
Erection,testing and commissioning of Power and Control Cables
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete.
10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/strip armoured stranded copper conductor control cable complete.
2Core, 6sqmm, 1100V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete.
4Core, 6sqmm, 1100V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete.
Marshalling kiosk with Kiosk frames stainless steel/hot dip galvanized structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. shall be provided with the degree of protection of IP:55, with Copper Bar earthing for 33 KV. I. Marshalling Box shall be outdoor type, rigidly constructed out of sheet steel or aluminium and shall be dust, water and vermin proof. Sheet steel used shall be at least 2.0 mm thick cold rolled. 2. Bay Marshilling Kiosk shall have three separate distinct compartment for the following purpose i) To receive two incoming 415V, 3 phase 63 A AC supply with auto changeover and MCB Unit and distribute minimum six outgoing 415V 3 phase 16 A, supply control by MCB with fuse failure remote indication ii) To distribute minimum 10 outgoing, 240 V, 10A supplies to be control by MCB to be drawn from 3 phase incomer. iii) 200 no. of terminal blocks in vertical formation for interlocking facilities 3. All sheet steel works shall be degreased, pickled, phosphate and then applied with two coats of Zinc chromate primer and two coats of finishing synthetic enamel paint. The colour of finishing paint shall be light admiral grey in accordance with shade no. 697 of IS:5 outside & inside shall be glossy white
Erection,testing and commissioning of Conductor and Hardware Fittings
500mm2 ACSR Moose (a) Aluminum = 54/3.53 mm (b)Steel= 7/3.53 mm overall diameter = 31.77 mm Approx. Wt.= 1998kg/km ultimate strength = 159.60KN
Single Tension Fittings For Single moose shall have minimum failing load of 100% ultimate strength of conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN.
Single Suspension Fittings For Single moose shall have minimum failing load of 50% ultimate strength of conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Single Tension Fittings For Twin moose shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120KN.
Single Suspension Fittings For Twin moose shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN
Disc Insulators 120 KN, Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Disc Insulators 90 KN, Ball& Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
T Clamps 0.5/0.4, made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 0.4 / Twin 0.4 , made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Spacers for Twin ACSR Conductor
P I Clamps 0.2 made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
P G Clamps 0.4 made of Aluminum Alloy and shall comply in all respects withIS:5561-1970 (latest edition)
OPGW, dual window single-mode with mode field diameter 8.6-9.5 um, cladding diameter 125 um+_ 1um
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’shackles, jumper terminals, nuts &bolts and washers etc. slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding conductivity of GSS ground wire
Erection ,testing and commissioning of Power Transformer
Cost of 50 MVA (ONAN/ONAF), 132/33kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES, HV and LV connectors and other required accessories and fittings with online DGA monitoring Kit on line dehydration kit and maintenance free automatic breathers as per detailed technical specs. With Mandatory spares as per SBD.(Current density for HV/LV winding not more than 2.4 A/sq. mm. Core flux density not more than 1.5 T.
Erection,testing and commissioning of Structures
Galvanised Steel Structures (Lattice Structure)
Galvanised Fasteners, Nuts and Bolts
Erection,testing and commissioning of Power and Control Cables
3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/strip armoured stranded copper conductor control cable complete
Erection,testing and commissioning of Conductor and Hardware Fittings
500mm2 ACSR Moose (a) Aluminum = 54/3.53 mm (b)Steel= 7/3.53 mm overall diameter = 31.77 mm Approx. Wt.= 1998kg/km ultimate strength = 159.60KN
Single Tension Fittings For Single moose shall have minimum failing load of 100% ultimate strength of conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN.
Single Tension Fittings For Twin moose shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120KN.
T Clamps 0.5/0.4, made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 0.4 / Twin 0.4 , made of Aluminum Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Disc Insulators 120 KN, Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Erection,testing and commissioning of auxialliary transformer
Cost of 33/0.433 KV, 250 KVA, 3-Phase Distribution Transformers with Bimettalic Terminal Connectors Energy Level-2 Copper wound
300 mm2 3.5 Core Cable 1.1KV Grade, Armoured, XLPE, insulated stranded conductor FRLS type
Erection ,testing and commissioning of Common Miscellaneous Equipments
Battery Bank 110 V, 300 AH , of 55 No. cells of 2 V each, sealed maintenance free VRLA type, High impact Polyprophelene copolymer Container, flame retardant.
Battery Bank 48 V, 450AH , of 24 No. cells of 2 V each, sealed maintenance free VRLA type, High impact Polyprophelene copolymer container, flame retardant.
110V Battery charger (Three phase) :Battery charger as well as Automatic Regulators shall be of static type compatible with VRLA Batteries. Should also have necessary temperature sensors. should have both Automatic and Manual control of output voltage and current. (i) Float charging and load current ratings: 30Amp/60Amp/70Amp/ 100Amp at 220 V to 252 VD.C. Boost charging current rating: 50Amps/55Amp/60Amp/70Amp/ 80Amp / 100 Amp at 198 V to 296/302 VD.C.
48V, DCPS SMPS Based DC Power supply system of 35 Amp rating
DC Distribution Board frames shall be fabricated using mild steel structural section or pressed and shaped Cold rolled sheet steel of thickness not less than 2.0 mm and shall be provided with a degree of protection of IP-52 as per IS:2147, bus bar chamber having a degree of protection of IP-42 as per IS:2147. Finishing paint on panels shall be of shade 692 (smoke grey) of IS:5. The inside shall be properly stoved The paint thickness shall be at least 50microns.Bus bars and jumper connections shall be of high conductivity aluminum alloy or copper of adequate size.
DC Distribution Panel (110V, DC) with 1No. 10Amp. Air break ckt .Double pole for battery incoming supply with DP MCBs & indicating Lamps etc.
DC Distribution Panel (48V, DC) with 1No. 10Amp. Air break ckt. Double pole for battery incoming supply with DP MCBs & indicating Lamps etc.
AC Distribution Panel (415 V, AC) complete with ckt .Breakers, indicating Lamps etc for 132/33KV Grid Station.
250 KVA Oil cooled servo stabilizer 3-phase 4 wire copper wound indoor type, input voltage range220-460V, output 400V ± 1% having, Digital control, Response time < 10ms ,Automatic Switch-Off against:· Under/Over-Voltage· Over-Load & Short–Circuit ·Single Phasing, Class C Type Secondary surge Protection
Power cables for AC/DC network in Control room for 132/33 KV Grid Station including control desk.
Const. power with avg. 5KM 33 kV line (S/C 0.2 ACSR with 11 mtr ST Pole),, transformer and electricity charges.
RTU panel for SCADA for 132/33 KV Grid Station
Circuit Breaker Operation Analyzer
Winding Resistance Measurement
Micro Ohm Meter
Air Conditioning /Central Heating for 132/33 KV Grid Station
High Mast Yard Lighting 200 W LED Lamps 9make Havells, Bajaj) With 12 Fittings & Feeder Pillars Having Timers For Automatic On-Off including aviation light. Including laying of foundation cabling etc as pr site specification/requirement.
125 KVA DG Set, 3 phase, silent type, Rated Engine Power at 100% load KW: 114.8 rated current capacity @ 0.8 PF, 173.9 Amps including construction of foundation, canopy, local chemical earthing pit, cabling etc, as per site specificarion/requirement.
Erection,testing and commissioning of additional equipments
Internal Communication-Telephone/WiFi Net work CCTV base survelliance system with HD cameras, network routers, LAN (CAT-6 cable), NVR with high capacity (2 TB or more) HDD, LCD/LED HD TV, and other works as necessary.
Rotating CCTV N/W IPIR Night Vision speed dome camera 360 along with cables and all necessary accessories as mentioned in the technical specifications with40-43 inches LED T.V with VMS.
Tan Delta & capacitance measurement kit. The test set shall be fully automatic, microprocessor based and designed for condition assessment of electrical insulation in high voltage apparatuses such as Transformers, Reactors, bushings, CTs, CVTs, Circuit Breakers, rotating machines etc with output up to 12 V at frequency 45Hz, output test current @ 12 KV: 100 mA continuous and 300 Ma intermittent or better. Along with test lead and accessories and transport case with wheels.
Digital BDV oil test kit (100 KV).
High Vacuum oil Filtration Plant 6000 LPH
20 MT Diesel Hydraulic Rough Terrain Mobile Crane/Man lifter
Event Logger, Disturbance Recorder & GPS System time synchronizing unit with PC
Fire Fighting System.Fire detection and alarm for control room building
CIVIL WORKS
Main Duct of Size 1200mm x1200mm with 6 mm M.S Chequered Trench Covers of size 500 x 1300 mm
Main Duct of Size 1200mm x 1200mm with concrete grade M15 of size 500 x1300 mm
Sub Main Duct of Size 600mm x 600mm with concrete grade M15 of size 700x500 mm
Tee off duct:150mmsandfilledHDPEpipesfromSubmaintoEquipments in the outdoor area
Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing
Concreting of yard & Laying Of Gravel
Oil sump Tank ( Stainless steel) as per approved Drawing
Construction of transformer foundation including rail track and allied works as per approved drawings
Cable trays/Racks of size 400mm X3000 mm made of MS Angle 40x40x6 mm,40x6 flat
Cable trays/Racks of size 400mm X3000 mm made of MS Angle 40x40x6 mm,40x6 flat
Construction of 132KV Yard Foundations as per approved drawings
Laying of 132KV Column foundations (as per Drawing)
Laying of 132KV Isolator foundations (as per Drawing)
Laying of 132KV SF6 Breaker foundations (as per Drawing)
Laying of 132KV CT foundations (as per Drawing)
Laying of 132KV CVT/PT foundations (as per Drawing)
Laying of 132 KV L.A foundations (as per Drawing)
Laying of 132KV Post Insulator foundations (as per Drawing)
Construction of 33KV Yard Foundations as per approved drawings
Laying of 33KV Column foundations (as per Drawing)
Laying of 33KV Isolator foundations (as per Drawing)
Laying of 33KV VCB foundations (as per Drawing)
Laying of 33KV CVT/PT foundations (as per Drawing)
Laying of 33KV CT foundations (as per Drawing)
Laying of 33KV L,A foundations (as per Drawing)
Laying of 33KV Post Insulator foundations (as per Drawing)
Construction of Cable Ducts With Covers
Main Duct of Size 900mm x 600mm with 6 mm M.S Chequered Trench Covers of size 500 x 1000 mm
Main Duct of Size 900mm x 600mm with concrete grade M15 of size 500 x1000 mm
Sub Main Duct of Size 600mm x 450mm with concrete grade M15 of size 700x500 mm
TeeoffDuct:150mmsandfilledHDPEpipesfromSubmaintoEquipments in the outdoor area
Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing
Concreting of yard & Laying Of Gravel
Foundation plateform for AUX transform( as pr approved drawing)
Construction of rail track for dragging of power transformer
Construction of Retaining walls RRM
Construction of compund walls with brick work complete job inclunding plastering ,painting MS angle and concertina wire etc( as per approved drwaing)
providing and fixing G.I. chain link mesh fencing
Development of Land Benching /Levelling
Construction of control room building as per approved drawings complete in all respects tile flooring sanitary fittings,wiring etc including trussed roof as per the directions of Engineer in Charge
Construction of AEE/AE Quarters building as per approved drawings complete in all respects tile flooring sanitary fittings,wiring etc including trussed roof as per the directions of Engineer in Charge
Construction of JE Quarters building as per approved drawings complete in all respects tile flooring sanitary fittings,wiring etc including trussed roof as per the directions of Engineer in Charge
Construction of SBA Quarters building as per approved drawings complete in all respects tile flooring sanitary fittings,wiring etc including trussed roof as per the directions of Engineer in Charge
Construction of Guest House building Duplex as per approved drawings complete in all respects tile flooring sanitary fittings,wiring etc including trussed roof as per the directions of Engineer in Charge
Construction of Store shed as per approved drawings
Construction of DG room as per approved drawings
Construction of internal roads ( complete macemadised )
Provision of water supply to control room, residential buildings, yard including Borewell, storage tanks etc.as per site requirement
Construction of scurity post as per approved drawings
Establishment of workshop facility for 132/33 KV Gris station
Providing of cabin and control desk for grid station
Construction of outdoor gantry for 33 KV feeders
Ornamental wporks and development of lawns and land scapping
Provision of furniture ,Beds, sofa, Chairs , Tables,AC s, Bedding items , Crockery items , refrigrator,water purifier, LED TVs for all buildings as per the directions of Engineer in Charge
Supply and Laying of LT Distribution And Street lightening as per site requirement
Supply, Erection ,testing and commissioning of Sub Station Automation System
Complete Sub Station Automation System including Hardware and Software for the Sub Station and Remote Control Station along with associated equipments as per technical specifications
Supply, Erection ,testing and commissioning of PLCC / SCADA
Digital Protection Coupler in PLCC
220KV/132KV/33KV BCU in SCADA
BCU Panel
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.63 MB
SBD13Mendhar.pdf
Tender Documents • 4.83 MB
BOQ_975880.xls
BOQ • 0.41 MB
Download all tender documents and submit your bid