Loading…
Loading…
Tender Value
₹32.6 L
EMD Value
₹65,200
Closing Date
15 Jul 2026, 3:00 pmClosed
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
TENDER
44 conditions · 6 needing a document upload
Valid copy of PAN and GSTIN needs to be furnished along with the documents.
Tenderer should fill up the Tender Form (First Sheet) as per 'Annexure-I' of GCC. Incomplete or partial fill up the Tender Form (First Sheet) by the Tenderer will be liable to reject.
For Sole Proprietorship firm a)Affidavit as per 'Annexure'. b)Special power of Attorney as per proforma given in 'Annexure' to be submitted by sole proprietor firm duly notarized.(Not required if tender documents are submitted by proprietor himself) (Mandatory)
For Partnership firm a)Self/Notary attested copies of Partnership deed. b)Special Power of Attorney as per proforma given in 'Annexure' to be submitted by Partnership firm. (Not required if one or more partners are authorized in Parternership deed to sign on behalf of the firm.)
For Limited Company a) Copy of Memorandum & Articles of Association of Company. b)Self /Notary attested copy of resolution passed by Board of Directors authorizing its Director/Employee to deal with tender on behalf of company. c) Attested copy of Notarized Special Power of Attorney including ratification clause duly signed by person authorized by the company.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The tenderer is advised to study the uploaded tender document in www.ireps.gov.in portal carefully
The Conditions of tender shall be read in conjunction with General Condition of Contract/2022 subject to modification, additions or supersessions by Special Condition of Contract and Specification if any.
The tenderers are required to observe the website to find out if any correction slips issued subsequent to uploading of the Tender. Railway reserves the right to make any additions/alterations to the tender uploaded and issue corrigendum to the same effect. In case the tenderer fails to take note of the above corrigendum, the additions and alterations entered/effected in the corrigendum shall be binding upon the tenderer and no claim whatsoever will be entertained by Railway.
No manual tenders sent by post/Fax/courier or in person shall be accepted.
At RNY Division:- Electrical works in connection with sump and pumping arrangement along with drainage arrangement at 7 nos. LHS (RUB no. NN-171, NN-173, NN-184, NN-187, NN- 188, NN-192 & NN 194) in BG-ll section of Rangiya Division for avoiding water logging.
RNY-EL-T-19-2025-26-RT
RNY-EL-T-19-2025-26-RT
Open
Works - General
180 Days
Kamrup, Assam
₹0
₹65,200
15 Jul 2026
22 Jun 2026
1 Jul 2026
63 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 32,58,776.85 | ||
| — | 1200.00 | — | — | ||
| Supply, fixing, testing & commissioning of LT Aerial Bunch cable of size phase 1 core x 25sq mm + Messenger cum Neutral 1x25 sq mm (Insulated) as per direction of EIC at site. | — | — | — | 63,000 | |
| — | 350.00 | — | — | ||
| Supply, testing and drawing of 10 sq mm 2 core round copper conductor PVC insulated FR PVC sheathed multistranded cables with bright annealed electrolytic bare copper conductor for voltage grade up to 1100 volt conforming to IS-694:2010 as per direction of EIC at site. | — | — | — | 1,42,100 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing & commissioning of 2+14 way SPN distribution double door board consisting 63A, MCB DP - 1 no, 40A, MCB DP - 2 nos, 25A, MCB DP - 1 nos & 10A MCB SP - 2 nosand with enclosure and necessary fixing arrangements as per direction of EIC at site. | — | — | — | 30,280 | |
| — | 29.00 | — | — | ||
| Supply of Galvanised tubular pole 7.5 mtr long , Type-410 SP-08 having weight 103 kgs, 4.5/1.5/1.5 mtr having sectional outer dia 139.7/114.3/88.9 mm and sectional thickness 4.85/3.65/3.25 mm respectively as per IS:2713-1980 including suitable size base plate & cap. The work includes Carrying, loading/unloading and erection of tubular pole 7.5 mtr long by contactor own arrangement by digging the pit to 1/5th of the pole height. Execution of CC foundation work of size 45cmx45m in ratio 1:2:4 by cement, sand and chips of size 19 mm and down upto full depth & 1ft above the GL as per direction of EIC at site. | — | — | — | 3,36,792.66 | |
| — | 29.00 | — | — | ||
| Supply, installation, testing & commissioning of 45-watt LED Street light fittings complete including single arm with all accessories as per direction of EIC at site. The LED fittings should be warranted for 5 years. | — | — | — | 2,12,512 | |
| — | 22.00 | — | — | ||
| Supply and erection of LT galvanized pole stay set comprising of 16 mm dia, 1.68 mtrs. Long stay rod anchor plate of size 15cm x 15 cm x6mm, 12mm dia turn buckle thimble, stay clamp, 7/12 SWG GI stay wire, Guy insulator etc. in CC foundation with ratio 1:3:6 including excavation and refilling. | — | — | — | 10,887.36 | |
| — | 22.00 | — | — | ||
| Supply and erection of earthing by made of B class GI pipe of 3000 mm length, 50 mm diameter & 3.6 mm thickness. The GI Strip ( should be welded with the earth pipe. The pipe is provided with a tapered casing at the lower end in order to facilitate the driving. A funnel with perforated plate to be provided at the top of the pipe for pouring water during dry season to have an effective earth value. The connecting conductor from earth electrode to the distribution panel board should not be thinner than 8 SWG GI wire to carry the fault current. The earth fill shall be of homogeneous layer of common earth soil. Where soil restivity is high, earth restivity enhancing material may be used, Bentonite or similar earth enhancing material may be used in rocky soil. Earth box to be precasted RCC and The values of earth resistance measured should be painted on the Earth pit cover/lid along with the date of measurement. As per Drg. No. DRG NO: PCEE/ELG/DRG/2024/1 dated 30.09.2024 & as per Technical circular no. EL/PS/2024/1 (EARTHING SYSTEM). | — | — | — | 37,103 | |
| — | 42.00 | — | — | ||
| Supply, erection, testing and commissioning of Anchor clamp (3-bolt/2-bolt type) with all required accessories as per direction of EIC at site. | — | — | — | 10,798.62 | |
| — | 42.00 | — | — | ||
| Supply and fitting of I-hook for anchor with suspension clamp assembly and all required accessories as per direction of EIC at site. | — | — | — | 2,289 | |
| — | 42.00 | — | — | ||
| Supply and fitting of GI clamp for rail /tubular pole with all required accessories as per direction of EIC at site. | — | — | — | 4,174.38 | |
| — | 42.00 | — | — | ||
| Supply and fitting of Insulation piercing connectors with cover or P.G. connectors with insulation cover-35-50 sqmm with all required accessories as per direction of EIC at site. | — | — | — | 2,906.4 | |
| — | 42.00 | — | — | ||
| Supply and erection of LT suspension clamp assembly with bracket and all required accessories as per direction of EIC at site. | — | — | — | 11,051.04 | |
| — | 21.00 | — | — | ||
| Supply and erection of Dead Clamp with bracket for AB Cable with all required accessories as per direction of EIC at site. | — | — | — | 5,732.37 | |
| — | 700.00 | — | — | ||
| Laying of above LT XLPE insulated armoured aluminium cables as per instruction of site engineer (Cable will be supplied by Railway). | — | — | — | 9,037 | |
| — | 630.00 | — | — | ||
| Excavation of cable trench 0.75 mtrs. below the GL with laying of armored cable and refilling the same by supply of 70mm sand and soil after digging the earth. The laying of armoured cable should be done as per direction of Engineer at site. (Cable will be supplied by Railway). | — | — | — | 83,997.9 | |
| — | 7.00 | — | — | ||
| Supply. Installation, testing and commissioning of outdoor MS cubical type LT feeder pillar box of suitable size and suitable for 415 V, 50 Hz AC supply made out of CRCA sheet not less than 14 SWG. The panel shall be totally enclosed, dust and vermin proof, neoprene gasket of thickness not less than 2 mm shall be used between all adjacent units and beneath all covers so that the joints are effectively dust vermin proof. The busbar chamber shall have three phase & neutral copper busbar of same ratings. The drawing of panel board should be approved by the competent authority before fabrication and commissioning. The panel shall be painted with two coats of primer & two coats of exterior coating by spray painting and shall consists of the following:- (i) 125A, 4P, 36kA, Ics=100%Icu, Adjustable over load Setting & Short circuit setting, MCCB - 1 Nos. (ii) 63A, 4P, 36kA, Ics=100%Icu, Adjustable over load Setting & Short circuit setting, MCCB - 4 Nos (iii) 40A, TPN, 'C' Series, MCB - 1 Nos (iv) Fabrication of Panel board with 14SWG CRCA sheet including CC foundation and 200A TPN Copper busbar), cable alley, C C Foundation etc and all accessories - 1 job | — | — | — | 4,88,932.57 | |
| — | 7.00 | — | — | ||
| Supply installation, testing and commissioning of Single Phase Smart Prepaid meter System : - 240VAC, 1 phase 2 wire, (IS: 16444, IS 15884 & IS: 15959) Marked, 5-30 Amps, in a suitable tamper proof hinge type Box. The communication module (Cellular based) with inbuit NBIoT GPRS/4G/5G enabled modem along with SIM card should be supplied with the meter. Optical Port for local communication/WAN (Cellular) communication for data acquisition. Meter will have connect/disconnect functionality operated through prepaid billing software. Warranty of meter should be 10 years from date of Supply. Make should be - Secure/ HPL/ L&T/ Bentec. Implementation of cloud hosted head end and meter data management software (including prepaid feature) . All Smart Prepaid meters should be provided with integrated cloud system. Android/iOS mobile app should be provided along with provision of payment gateway for online Vending token process including mobile network charges for each Meter for five year and Annual comprehensive maintenance (five year) support for the hardware and, software, Software hosting, network monitoring and maintenance, Tarrif Revision etc. with 24*7 customer support in toll free number for Customer support for each supplied meter & reconfiguration of the replacement of meters in case of any defect. | — | — | — | 91,833 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing & commissioning of SPN distribution board 8 way double door metal SPN DB consisting 63A, MCB DP - 1 no, 20A, MCB DP - 2 nos, 6A, MCB SP - 2 nos with enclosure and necessary fixing arrangements as per direction of EIC at site. | — | — | — | 10,302.48 | |
| — | 3.00 | — | — | ||
| Supply, testing & commissioning of 25A, 2 pole, 30mA, 10kA RCCB as per direction of EIC at site. | — | — | — | 5,156.91 | |
| — | 9.00 | — | — | ||
| Supply, installation, testing & commissioning of 1.8Kw/2.5HP, 1 phase having discharge capacity 330 - 120 LPM, Head - 6 to 10 Mtr sewage pump as per direction of EIC at site. | — | — | — | 4,51,638 | |
| — | 9.00 | — | — | ||
| Supply, installation, testing & commissioning of DOL starter for single phase 2.5HP 1 phase sewage pump as per direction of EIC at site. | — | — | — | 23,597.64 | |
| — | 260.00 | — | — | ||
| Supply & fixing of PVC pipe for inlet & outlet and suction of above pump as per direction of EIC at site. | — | — | — | 46,020 | |
| — | 35.00 | — | — | ||
| Supply and surface wiring of light/FL point by PVC insulated & un-sheathed FRLSH multi strand copper single core 1.5 sq.mm cable through PVC casing & caping including ceiling rose. Cable connection to be done through 6 A flush type controlling switch installed in suitable size PVC board & connected by Cu flexible wire from ceiling rose to fittings as per direction of EIC at site. | — | — | — | 8,821.75 | |
| — | 42.00 | — | — | ||
| Supply and surface wiring of 6A 5 pin plug point by PVC insulated & un-sheathed FRLSH multi strand copper single core 2.5 sq.mm cable through PVC casing & caping, with earth continuity by single core 1.0 sq mm copper cable including suitable size PVC board. Cable connection to be done through 6 A flush type controlling switch, socket installed in PVC board hylum sheet on top and as per direction of EIC at site. | — | — | — | 14,616 | |
| — | 14.00 | — | — | ||
| Supply and surface wiring of 16 A, 6-pin Plug point/geyser point by PVC insulated and un- sheathed FRLS multi stranded copper cable, single core 4.0 sq.mm with earth continuity by 1.0 sq.mm multistrand copper cable through PVC casing & caping including suitable size PVC board. Cable connection to be done through 16 A flush type controlling switch, 16A socket installed in board and as per direction of EIC at site. | — | — | — | 8,414 | |
| — | 750.00 | — | — | ||
| Supply & surface wiring of earth continuity for Main line/ Submain line by 1.0 sq mm PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable through suitable size PVC casing & caping as required through the circuit as per direction of EIC at site. | — | — | — | 7,732.5 | |
| — | 750.00 | — | — | ||
| Supply & surface wiring of Submain line by 2.5 sq mm PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable through suitable size PVC casing & caping as required as per direction of EIC at site. | — | — | — | 18,817.5 | |
| — | 380.00 | — | — | ||
| Supply & surface wiring of Submain/Main line by 4.0 sq mm PVC insulated & unsheathed, single core, multi stranded FRLS copper conductor cable through suitable size PVC casing & caping as required as per direction of EIC at site. | — | — | — | 14,459 | |
| — | 380.00 | — | — | ||
| Supply & fixing of PVC casing & caping for drawing of Main/Submain line as required as per direction of EIC at site. | — | — | — | 19,353.4 | |
| — | 35.00 | — | — | ||
| Supply, fitting, fixing of 30Watt , LED tunnel light luminaries complete for pit lighting suitable for 220V AC (Model No.LTLL-30-CDL of Make Cromton or Similar of India Bull/Havell's/Syska) input voltage to be provided after dismantling the existing one. Fixture shall be made from pressure die cast aluminum housing with toughened glass cover, secured properly with Teflon gasket to ensure IP: 67 & IK10 ANTI-THEFT KEY protections. LEDs shall be of SMD type (Cree/Nichia/Osram/Seoul). Luminaries and ballast shall be of same make. The LED fittings should be warranted for 5 years. | — | — | — | 2,56,900 | |
| — | 7.00 | — | — | ||
| Supply, Installation Testing and Commissioning of Intelligent Field Device (IFD) having inbuilt energy metering, Analog Inputs, Digital Inputs, Digital Outputs, GPRS communication/ethernet, LAN, WiFi, etc., display along with filter power circuit having fuses, AC to DC power supply providing adequate DC Supply options (Viz. 5V/12V/24V etc) with battery back for monitoring and control of Pumps, 30-70% Lighting, Street Light(s), Lift(s), Escalator(s), Substation , etc. capable of monitoring & control electrical parameters, sensors parameters with necessary control capability through internet cloud computing along with integration with CRIS Software as per specifications IFD (1 x 1) and all accessories as per direction of EIC at site. | — | — | — | 8,29,520.37 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TD-192025-26-RT.pdf
ATTACHMENT
GCCUpdateduptoACS-7.pdf
ATTACHMENT
ACS-8.pdf
ATTACHMENT
ACS-09.pdf
ATTACHMENT
ACS-10.pdf
ATTACHMENT
GCCACS11.pdf
ATTACHMENT
AnnexureNEW.pdf
ATTACHMENT
TechCircularwithDrgforEarthingandCableLayingUG.pdf Earthing Drawing
ATTACHMENT
TechCircularwithDrgforEarthingandCableLayingUG.pdf
ATTACHMENT
JPO8.5.24-CablediggingworksNFR.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .