| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹17.1 LAccepted-AOC | L-1 | Accepted-AOC Lowest bidder | |
| 2 | L-2₹22.2 L+₹4.1 L (22.8%)Rejected-AOC | L-2 | Rejected-AOC Other than lowest bidder | |
| 3 | L-3₹22.9 L+₹4.8 L (26.8%)Rejected-AOC | L-3 | Rejected-AOC Other than lowest bidder | |
| 4 | L-4₹23.8 L+₹5.7 L (31.4%)Rejected-AOC | L-4 | Rejected-AOC Other than lowest bidder |
Tender Value
₹23 L
EMD Value
₹46,000
Closing Date
30 Dec 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Lt Col Ram G
GE Kaluchak Pin-900673 C/O 56 APO
REPAIR MAINTENANCE TO MISC E/M EQUIPMENTS AT KALUCHAK MIL STN UNDER GE KALUCHAK
2022_MES_566804_1
GE/KC/NIT-56/2022-23
Open Tender
Civil Works
Item Rate
270 days
GE Kaluchak
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE Kaluchak
₹46,000
Yes
25 Mar 2023
2 Dec 2022
6 Jan 2023
2 Dec 2022
30 Dec 2022
16 Dec 2022
2 Dec 2022 - 9 Dec 2022
Amount
Servicing of DG Set 62.5 KVA of any make, checking entire system as per manufacturer's catalogue such as checking all parts for serviceablility, taking down defective parts such as fuel filter assy, by pass filter assembly, lub oil filter assembly, air cleaner assy, air filter, flexible hose pipe, radiator coolent, distill water, tightening the base bolt and nuts and mounting bolts and nuts etc and replacing the same with same size, make and capacity of parts, draining out the old used burnt engine oil from the sump, cleaning all serviceable filters and oil sump with cleaning solution such as petrol/ diesel and refilling new engine oil upto required level, cleaning of battery terminals with warm water, checking the radiator and radiator hose and arresting small leaks, checking the fuel pump timing and adjusting if required and including testing to DG Set to entire satisfaction of Engr-in Charge, complete all as specified & directed. Make : Kirloskar/ Crompton/ Cummins
Notes :- (i) Spare parts/ Engine oil/ Check kit/ filter shall be measured and paid for saperately under respective items of BOQ as 'Supply only'. (ii) Minimum 6 months gap/ 200 Hrs of run whichever is earlier shall be considered for next service. (iii) Repair guarantee for replaced parts/ servicing of DG Set shall be for six month/ 200 Hrs run from the date of service whichever is earlier. (iv) Cost of small spares required for maint of DG set shall be deemed to be included in the unit rate quoted by the contractor (v) Service Engineer must be skilled and must have knowledge of maintenance of DG sets and attending minor and major fault when it arise.
All as per Srl item No.01 above but DG set of capacity 40 KVA.
All as per Srl item No.01 here-in-before but DG set of capacity 30 KVA.
All as per Srl item No.01 here-in-before but DG set of capacity 25 KVA.
All as per Srl item No.01 here-in-before but DG set of capacity 20 KVA.
All as per Srl item No.01 here-in-before but DG set of capacity 15 KVA.
Supply only Air filter element (OEM manufactured) suitable for 15 KVA DG set, complete all as specified & directed.
Supply only Air filter element (OEM manufactured) suitable for 20 KVA DG set, complete all as specified & directed.
Supply only Air filter element (OEM manufactured) suitable for 25 KVA DG set, complete all as specified & directed.
Supply only Air filter element (OEM manufactured) suitable for 30 KVA DG set, complete all as specified & directed.
Supply only Air filter element (OEM manufactured) suitable for 40 KVA DG set, complete all as specified & directed.
Supply only Diesel filter (OEM manufactured) capacity 1/2 litre with 'O' ring (Primary & Secondary) suitable for 15 KVA DG set, complete all as specified & directed.
Supply only Diesel filter (OEM manufactured) capacity 1/2 litre with 'O' ring (Primary & Secondary) suitable for 20 KVA DG set, complete all as specified & directed.
Supply only Diesel filter (OEM manufactured) capacity 1/2 litre with 'O' ring (Primary & Secondary) suitable for 25 KVA DG set, complete all as specified & directed.
Supply only Diesel filter (OEM manufactured) capacity 1/2 litre with 'O' ring (Primary & Secondary) suitable for 30 KVA DG set, complete all as specified & directed.
Supply only Diesel filter (OEM manufactured) capacity 1 litre with 'O' ring (Primary & Secondary) suitable for 40 KVA DG set, complete all as specified & directed.
Supply only Diesel filter (OEM manufactured) capacity 1 litre with 'O' ring (Primary & Secondary) suitable for 62.5 KVA DG set, complete all as specified & directed.
Supply only Water Separator (OEM manufactured) capacity 1/2 litre with 'O' ring suitable for 15 KVA DG set, complete all as specified & directed.
Supply only Water Separator (OEM manufactured) capacity 1/2 litre with 'O' ring suitable for 20 KVA DG set, complete all as specified & directed.
Supply only Water Separator (OEM manufactured) capacity 1/2 litre with 'O' ring suitable for 25 KVA DG set, complete all as specified & directed.
Supply only Water Separator (OEM manufactured) capacity 1/2 litre with 'O' ring suitable for 30 KVA DG set, complete all as specified & directed.
Supply only Water Separator (OEM manufactured) capacity 1 litre with 'O' ring suitable for 40 KVA DG set, complete all as specified & directed.
Supply only Oil filter (OEM manufactured) capacity 1/2 litre with 'O' ring suitable for 15 KVA DG set, complete all as specified & directed.
Supply only Oil filter (OEM manufactured) capacity 1/2 litre with 'O' ring suitable for 20 KVA DG set, complete all as specified & directed.
Supply only Oil filter (OEM manufactured) capacity 1/2 litre with 'O' ring suitable for 25 KVA DG set, complete all as specified & directed.
Supply only Oil filter (OEM manufactured) capacity 1/2 litre with 'O' ring suitable for 30 KVA DG set, complete all as specified & directed.
Supply only Oil filter (OEM manufactured) capacity 1 litre with 'O' ring suitable for 40 KVA DG set, complete all as specified & directed.
Supply only Oil filter (OEM manufactured) capacity 1 litre with 'O' ring suitable for 62.5 KVA DG set, complete all as specified & directed.
Supply only Rocker cover / sump packing kit (OEM manufactured) suitable for 15 KVA DG set, complete all as specified & directed.
Supply only Rocker cover / sump packing kit (OEM manufactured) suitable for 20 KVA DG set, complete all as specified & directed.
Supply only Rocker cover / sump packing kit (OEM manufactured) suitable for 25 KVA DG set, complete all as specified & directed.
Supply only Rocker cover / sump packing kit (OEM manufactured) suitable for 30 KVA DG set, complete all as specified & directed.
Supply only Rocker cover / sump packing kit (OEM manufactured) suitable for 40 KVA DG set, complete all as specified & directed.
Supply only Rocker cover / sump packing kit (OEM manufactured) suitable for 62.5 KVA DG set, complete all as specified & directed.
Supply only Fuel line (OEM manufactured) complete with clamps suitable for 15 KVA DG set, complete all as specified & directed.
Supply only Fuel line (OEM manufactured) complete with clamps suitable for 25 KVA DG set, complete all as specified & directed.
Supply only Fuel line (OEM manufactured) complete with clamps suitable for 30 KVA DG set, complete all as specified & directed.
Supply only Fuel line (OEM manufactured) complete with clamps suitable for 62.5 KVA DG set, complete all as specified & directed.
Supply only Low lube oil pressure sensor (OEM manufactured) complete suitable for 15/ 20/ 25/ 30/ 40/ 62.5 KVA DG set, complete all as specified & directed.
Supply only Water hose pipe kit (OEM manufactured) complete with clamps, nuts & bolts suitable for 15/ 20/ 25/ 30/ 40/ 62.5 KVA DG set, complete all as specified & directed.
Supply only engine oil 15W/ 40, complete all as specified & directed.
Supply only water coolent suitable for DG set, complete all as specified & directed.
Supply only distilled water for filling in batteries, complete all as specified & directed.
Taking down/ Dismantling of unserviceable self starter 12 volts from engine of DG Set , opening of stator and armature for repairing by replacing the worn out carbon brushes, brush holder, bearings, ignition / solenoid coil, replacement of burnt armature, rewinding of field coils, replacement of pinion gears, bushing etc, complete servicing , varnishing of stator /armature and refixing after repair, testing / commissioning complete for DG Set of any capacity, complete all as specified & directed.
Battery terminals (positive and negative) brass heavy duty complete suitable for fixing on battery poles with bolts, nuts and washers complete including taking down old unserviceable battery terminals, complete all as specified & directed.
Supply, installation, testing and commissioning of maintenance free lead acid battery, 12V, 150 AH conforming to IS:7372 including dismantling of old unserviceable battery, complete all as specified & directed.
Supply, installation, testing and commissioning of maintenance free lead acid battery, 12V, 130 AH conforming to IS:7372 including dismantling of old unserviceable battery, complete all as specified & directed.
Supply, installation, testing and commissioning of maintenance free lead acid battery, 12V, 90 AH conforming to IS:7372 including dismantling of old unserviceable battery, complete all as specified & directed.
Servicing and maintenance of existing Chemical Dosing system suitable to inject solution upto 25 LPH comprising dosing pump coupled with three phase electric motor of capacity 0.5 HP, 1440 RPM assembly with agitator in one motor, agitator with SS sweep blade duly FRP coated, FRP tank 150 ltrs capacity, complete unit of make satya sai including replacement of unserviceable part at site chemical dosing system & changing of Teflon gland packing and cleaning of NRV set, checking the complete system complete all as specified & directed. Make of Plant : Sathya Sai Services . Notes :1. Servicing shall be carried out by the company rep and the rate for this shall deemed to be included in item. 2. Spares shall be of original manufacturer only. 3. Spares shall be paid and measured and seperately under as 'Supply only' under respective items.
Supply only PVC adopter for suction and delivery without NRV, complete all as specified & directed.
Supply only PVC strainer washer type heavy duty or Y type strainer for suction, complete all as specified & directed.
Supply only Teflon gland square type 3 mm, complete all as specified & directed.
Supply only Chemical Oil seal with cap, complete all as specified & directed.
Draining out the existing diesel from the tank from the capacity 62.5 KVA DG set, kept aside for repouring, taking down the complete fuel tank of any capacity from its position after disconnecting all the fuel lines, carryout cleaning work with solutions, removing the dust and foreign materials from the tank, drying the tank, blow with air painting and carry out recaliberation of diesel tank to the specified level including replacement of PVC level pipe, refix the tank in its original position, connecting all the removed fuel connections, refilling the kept diesel back to the tank carefully, remove air from the fuel connections, start the engine and test for satisfactory function, complete all as specified & directed .
Disconecting the existing battery of capacity 12V 92 /100 AH from the DG set, shifting it to battery workshop, draining out the complete unserviceable sulphuric acid from the battery, filling up with new sulphuric acid to the required level, charging the battery, testing the battery for correct specific gravity, bringing back to the location, connecting to DG Set, and testing for satisfactory function, complete all as specified & directed.
Disconecting the existing battery of capacity 12V 150 /180 AH from the DG set, shifting it to battery workshop, draining out the complete unserviceable sulphuric acid from the battery, filling up with new sulphuric acid to the required level, charging the battery, testing the battery for correct specific gravity, bringing back to the location, connecting to DG Set, and testing for satisfactory function, complete all as specified & directed.
Taking down existing worn out battery charging dynamo belt & water pump fan belt (V Belt) from the following capacity of DG set installed at various installations and supply and fixing with new fan belt of same specifications, complete & specified and as directed :-
15 to 30 KVA
40 to 62.5 KVA
Taking down the existing turbo charger unit from the capacity 30KVA Diesel engine, transporting to private work shop, dismantling opening including replacement of worn out bearing, bushes, fanblade, gaskets, o ring, seal etc., and reassembling testing/ connecting, complete all as specified & directed .
Taking down brunt unserviceable automatic voltage regulator assy from alternator of DG set by disconnecting its electrical connections, supply and fixing new AVR 12V suitable for 15 to 40 KVA DG Set including connecting all electrical connections, testing voltage after starting engine and setting properly complete all as specified & directed.
Disconnecting, removing and dismantling radiator assembly from the following capacity DG sets and descaling the radiator throughly with CTC solution/ any other chemical solvent agent as approved by the Engineer-in-charge, stopping of leakage at place to copper cores and tubes by brazing scrapping the existing oil paint, dusting and painting the radiator with enamelled paint etc., re-installing and commissioning complete all as specified & directed :-
7.5 to 30 KVA
40 to 62.5 KVA
Taking down existing unserviceable water pump assembly of following capacity DG sets installed at various installation and replaced with new water pump assembly (OEM Manufactured), complete all as specified & directed :-
15 to 20 KVA
25 to 40 KVA
50 to 62.5 KVA
Disconnecting electrical and mechanical connections of the following capacity alternator, 415 volts 50 HZ removing from foundations/ diesel engine coupling, transporting to private work shop, dismantling the alternator in parts and carrying out servicing, varnishing and applying the bactol on the excitor coils/ winding with super varnish, heating the windings at appropriate tempeature to achieve required insulation resistance without damaging the other parts, replacement of driving and non driving end bearings, cleaning, greasing, reassembling/ installing/ connecting and testing with megger for insulation resistance etc., complete all as specified & directed. Notes :- (i) Rewinding of alternator, repairing of main shaft replacement of unserviceable bearings, replacement of AVR will be measured and paid separately under respective items. (ii) Minor parts required to make the alternator serviceable are deemed to be included in the unit rate. Make of DG Set : Kirloskar / Ruston / CG / Sudhir
Repairing of main shaft by necessary welding / turning etc and preparing of new key way all as directed and specified by Engr-in-Charge for DG set of following capacities :-
Dismantling the alternator in parts and removing the burn out copper winding coil carefully, cleaning slots and replacing the insulation paper and re-winding 'F' class copper conductor winding wire of existing size/ shape, glass sleeves of connecting leads, binding/ tightening loose coils with binding cloths, varnishing and applying the bactol on the excitor coil/ winding with supper varnish, heating the windings at appropriate tempeature to achive required insulation resistance with out damaging the other parts, replacement of driving and non-driving end bearings, cleaning, greasing, reassembling and testing with megger for insualtion resistance etc., complete all as specified and as directed :-
Taking down existing defective injector and fuel injection pump (FIP) for the following capacity DG set installed at various installation and replacement of worn out spares like delivery valves, nozzles, bearings, fly weight, packing kit, and copper washer kit, injector element, kit injector, retainer injector cup, fixing tappit cover packing set and recalibration of FIP and refixing in same position and testing of full load checking of pressure and adjustment by dial gauge complete all as specified and as directed :-
Dismantling of unserviceable battery charging dynamo of 12 Volts from DG set of capacity 15 KVA to 62.5 KVA, repair and servicing of dynomo including replacement of bushes, bearings, carbon brushes, rectifires, rewinding of field magnet coil / rotor armeture coils and any other minor parts required for smooth functioning and refixing on DG set after repair/service including testing after commissioning, complete all as specified & directed.
Dismantling of old unserviceable battery charging dynomo of rating 12 volts and supply and fixing new battery charging dynomo of same specifications as per existing model suitable for fixing on DG set, 1500 rpm including testing after complete installation, complete all as specified & diirected.
Electronic type Starting Switch suitable for 15KVA to 62.5 KVA DG set including taking down old unserviceable switch, complete all as specified & directed.
Feed pump (OEM manufactured) suitable for 7.5 KVA to 62.5 KVA DG set including taking down old unserviceable pump, complete all as specified & directed.
Taking down the existing defective DC ammeter and volt meter from the panel and replaced with new combined DC ammeter and volt meter including necessary wiring & wiring material, complete all as specified & directed .
Engine safety unit (ESU) alongwith meter for pressure, fuel, RPM etc. with all electrical instruments and accessories including testing and taking down old unserviceable ESU, complete all as specified & directed.
Door hinges suitable for any capacity / size of DG set canopy at different locations including taking down old unserviceable/ broken hinges, complete all as specified & directed.
On load change over switch in sheet metal enclosure, 100 Amps, 415 volts, 4 pole, modular type, positive isolation, door interlock & padlock facility, conforming to IS:13947 (Part-3); IEC:60947-3 including all connecting/ jointing materials & taking down old unserviceable change over switch, complete all specified & directed.
On load change over switch in sheet metal enclosure, 160 Amps, 415 volts, 4 pole, modular type, positive isolation, door interlock & padlock facility, conforming to IS:13947 (Part-3); IEC:60947-3 including all connecting/ jointing materials & taking down old unserviceable change over switch, complete all specified & directed.
On load change over switch in sheet metal enclosure, 200 Amps, 415 volts, 4 pole, modular type, positive isolation, door interlock & padlock facility, conforming to IS:13947 (Part-3); IEC:60947-3 including all connecting/ jointing materials & taking down old unserviceable change over switch, complete all specified & directed.
MCCB of capacity 63 Amps, 4 pole, 415volt, 50Hz, breaking capacity 16 KA (minimum) or higher, adjustable thermal and fixed magnetic release, complete as per OEM standard design including taking down old unserviceable MCCB, complete all as specified & directed.
MCCB of capacity 100 Amps, 4 pole, 415volt, 50Hz, breaking capacity 16 KA (minimum) or higher, adjustable thermal and fixed magnetic release, complete as per OEM standard design including taking down old unserviceable MCCB, complete all as specified & directed.
MCCB of capacity 125 Amps, 4 pole, 415volt, 50Hz, breaking capacity 16 KA (minimum) or higher, adjustable thermal and fixed magnetic release, complete as per OEM standard design including taking down old unserviceable MCCB, complete all as specified & directed.
MCCB of capacity 160 Amps, 4 pole, 415volt, 50Hz, breaking capacity 25 KA (minimum) or higher, adjustable thermal and fixed magnetic release, complete as per OEM standard design including taking down old unserviceable MCCB, complete all as specified & directed.
MCCB of capacity 200 Amps, 4 pole, 415volt, 50Hz, breaking capacity 36 KA (minimum) or higher, adjustable thermal and fixed magnetic release, complete as per OEM standard design including taking down old unserviceable MCCB, complete all as specified & directed.
MCCB of capacity 250 Amps, 4 pole, 415volt, 50Hz, breaking capacity 36 KA (minimum) or higher, adjustable thermal and fixed magnetic release, complete as per OEM standard design including taking down old unserviceable MCCB, complete all as specified & directed.
MCCB of capacity 350 Amps, 4 pole, 415volt, 50Hz, breaking capacity 36 KA (minimum) or higher, adjustable thermal and fixed magnetic release, complete as per OEM standard design including taking down old unserviceable MCCB, complete all as specified & directed.
MCCB of capacity 400 Amps, 4 pole, 415volt, 50Hz, breaking capacity 36 KA (minimum) or higher, adjustable thermal and fixed magnetic release, complete as per OEM standard design including taking down old unserviceable MCCB, complete all as specified & directed.
Painting to existing steel tubular poles of any length including cross arms, channels, angle iron support, bracings, clamps etc. with one coat of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white/yellow and black paint alternately on external surfaceas per existing pattern above PCC benching including preparation of old painted surfaces by scraping etc, writing pole numbers. of 2 inches bold letters with black paint after painting and cutting vegetation growth all around and on the poles up to 1 metre radius, complete all as specified & directed.
Intergral LED security light luminaire 90W LED, 230 volts made up of pressure die cast aluminium housing powder coated with high power SMD LED’s lens & toughned glass IP-66, luminaire efficacy >110 Lumens per Watt, Secondary optics for better light distribution, having two nos Potted driver (OEM) (one inbult and one spare potted driver) 4KV internal +10KV SPD, THD<10%, pf>0.95, mounted on & including GI bracket made out of 40mm bore medium grade pipe of 1.70m length, bent to required shape, fixed on PCC/Steel pole with 02 Nos. clamps of flat iron (40 x 6mm), nuts, bolts and washers including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer, making connection with PVC copper conductor cable of 1.5 sqmm and taking down old unserviceable light fitting, complete all as specified & directed.
Integral LED Flood light luminaire 120W LED, 230 volts made of pressure die cast aluminium housing powder coated with high power SMD LED’s lens & toughned glass IP-66, Luminaire efficacy >110 Lumens per Watt, Secondary optics for better light distribution, having two nos Potted driver (OEM)(one inbult and one spare potted driver) 4KV internal +10KV SPD, THD<10%, pf>0.95 mounted on & including GI bracket made out of 40mm bore medium grade pipe of 1.70m length, bent to required shape, fixed on PCC/Steel pole with 02 Nos. clamps of flat iron (40 x 6mm), nuts, bolts and washers including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer, making connection with PVC copper conductor cable of 1.5 sqmm and taking down old unserviceable light fitting, complete all as specified & directed.
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out in any type of soil for foundation of pole, stay, taking up or laying of cable etc, complete all as specified & directed. Note : Due care shall be taken while deciding cable route for excavation. However any damage to Signal, BSNL, MES cable water/sewage pipe or any other service while excavation will be made good by the contractor and cost of the same for jointing material & labour is deemed to be included in the cost of excavation.
Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25cm, complete all as specifed & directed.
Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point, complete all as specified & directed.
Sand cushioning to under ground cable, laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete punned to 18cm, complete all as specified and directed. Note:- Punned thickness of sand will be measured and paid.
Brick well burnt locally available sub class 'B' laid over sand cushioning for mechanical cable protection in trenches with width of brick perpendicular to the length of cable, complete all as specified & directed.
PVC insulated weather proof twin core 2.50 sqmm (nominal area) aluminium conductor cable, 1100 volts grade, drawn in & including PVC conduit of suitable size with clamps (3 Nos), nuts, bolts etc from junction box to street light on pole/ LED aviation obstruction light fitted on over head reservoir, complete all as specified & directed.
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sqmm 4 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes, testing after completion including disconnecting and taking out old unserviceable cable, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes, testing after completion including disconnecting and taking out old unserviceable cable, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes, testing after completion including disconnecting and taking out old unserviceable cable, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 95 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes, testing after completion including disconnecting and taking out old unserviceable cable, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
Galvanised iron tube 80mm bore light grade (ISI marked) for cable protection to poles/ under floor/ under roads/ alongwith walls complete including MS clamps of flat iron 25x3mm duly painted, GI nuts, bolts and washers & sealing of pipe ends with approved sealing compound including taking down old unserviceable tube, complete all as specified and directed.
Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 3 meter (BGL), connected to galvanized iron earth strip 32x6mm size by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 50mm bore 'light grade' galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt etc including connected to test point and testing on completion, complete all as shown in electrical plate No 3 of SSR Part-I 2009 & as directed.
Repair to Voltage Stabilizer, servo type of capacity 20 KVA to 30 KVA at site including carrying out maintenance check along with the following other repairs: (i) Dismantling of voltage stabilizer by disconnecting incoming & outgoing connections, removing the top cover on site, replacing of consumble spare parts such as gasket, burnt PCBs etc unserviceable parts without lifting core assembly. (ii) Assembling of voltage stabilizer after replacement of unserviceable parts with new serviceable parts as ordered by Engr in Charge. (iii) Fixing of top cover after repair and testing up to entire satisfaction of Engr in Charge.
Notes : (a) The parts required to be replaced will be measured and paid separately as 'Supply only' against appropriate item of schedule. However labour element and painting involved in replacement are included in quoted rate against this item. (b) Any minor repairs involved to make the voltage stabilizer functional if notified by the Engr-in-Charge shall be carried out by the contractor without any extra cost to the department.
Servicing and cleaning of oil cooled servo voltage stabilizer of capacity 20 KVA to 30 KVA, 3 phase by transporting to workshop, carefully lifting of core from the tank by opening cover, cleaning of tank, removing of sediments, cleaning of coils/ electric connections, filtration of transformer oil, fixing the core back in the tank, making electrical connections by replacing the consumble spares such as gaskets, rubber oil seals complete etc but other spares as listed here-in-after shall be replaced and cost of spare parts 'Supply only' shall be measured and paid for separately under relevant item, transporting back to work site and reconnectiong with electrical connection, complete all as specified & directed by Eng-in-charge. Note : The parts required to be replaced will be measured and paid separately as 'Supply only' against relevant item of schedule. However labour element involved in replacement are included in quoted rate against this item.
Supply only the following spare parts/ components to be incorporated against Serial Item No 95 & 96 here-in-before :-
Copper dimmer stat 20A.
Servo motor 3 KG with RC network
Carbon brush 28A with holder
Controlling circuit
Aluminium arm set 28A
Pipe bush
Current collector plate copper
Indicating lamps
Toggle switch
Voltmeter 0-500V
Input output connection busbar with bakelite
Fresh transformer oil for top up
Supplying, installing, testing and commissioning of CPRI approved, factory made, LT feeder pillar box cubical, outdoor type, floor mounted double door, 3 phase 4 wire, 50 cycles, 415 Volts, made of 3.15 thick CRCA sheet for load bearing members and 16 SWG (1.6 mm thick) for doors covers and internal partitions, duly powder coated on both side, base frame of the panel shall be made of ICMC channel of size 50 x50 x 6mm duly grouted on platform made of brick work in cement mortar 1:4, 15mm thick plastering in cement mortar 1:4 having minimum height of 450mm, the panel shall be provided with separate compartments for each switch gears with hinged door including interlocking with switch gears,
the panel board shall be suitable for AC, 415 Volts, 50 Hz, 3 phase, 4 wire supply complete with epoxy insulated 250 Amps rated high conductivity aluminium bus bars, supported with DMC / SMC barriers and colour coded, prewired with copper cable, the degree of protection IP-54. the panel shall be complete with instrumentation such as LED phase indicating lamps and CT's including extended aluminium strip of rating of Incomer 200Amps and outgoing as per rating of MCCB’s, including aluminium lugs to connect the cable dismantled before etc. and taking down/ dismantling of old unserviciable LT feeder pillar box of any description, complete all as specified, directed & comprising of the followings:-
(a) MCCB 125 Amps, 4 pole with breaking capacity 25KA (Adjustable thermal & magnetic release) - 01 No (Incomer) (b) MCB DP 32 Amps, 'C' curve, breaking capacity 10KA - 08 Nos (outgoing) (c) Digital LED Voltmeter 3 ph, class 0.5. - 01 No (d) Digital LED Ammmeter 3 ph, class 0.5. - 01 No (e) Phase indication LED lamps - 01 Set (f) CT'S 200/5 - 01 Set
Aluminium socket and lugs of appropriate size after disconnecting the cable of any size of 1100 volts grade from panel, de-reeling the loop including cutting out and removing the burnt portion of cable end and relaying the serviceable portion in the existing position / layout including necessary earthwork, chases cutting in PCC work, taking out & relaying bricks and making good the disturbed surfaces and testing, complete all as specified & directed for the following sizes :-
VEE ESS ENGINEERS
DARVESH ENGINEERING WORKS
M/S SHREE KRISHANA ENERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .