Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.8 CrAccepted-Finance | ₹1.8 Cr | L1 | Accepted-Finance L1 |
| 2 | L2₹1.9 Cr+₹11.5 L (6.46%)Rejected-Finance I 910 JAHANGIR PURI NEAR BY ANAND MAYA HOSPITAL NORTH WEST DELHI DELHI 110033 UDYAM DL 06 0040830 | NORTH DELHI | DELHI | 110033 | ₹1.9 Cr+₹11.5 L (6.46%) | L2 | Rejected-Finance L2 |
| 3 | Rejected-Technical | - | - | Rejected-Technical no EMD |
Tender Value
Refer Docs
EMD Value
₹4 L
Closing Date
4 Jul 2022, 2:00 pmClosed
Executive Engineer ED-I Parade Jammu
Office of the Executive Engineer ED-I Parade Jammu
Supply, Erection, Testing Commissioning for execution of works for creation of infrastructure for providing air conditioners in New Secretariat, Main Building, Mini Secretariat at Jammu. Under the jurisdiction of Elect Div-I Jammu.On Turn Key basis
2022_PDD_174266_1
ED-I/e-NIT/45 of 2022-23 dt 16/06/2022
Open Tender
Electrical Works
Turn-key
45 days
ED Ist Parade Jammu
Please refer Tender documents.
7 documents required · 7 mandatory
₹10,000
Executive Engineer ED-I Parade Jammu
₹4 L
15 Jul 2023
16 Jun 2022
5 Jul 2022
16 Jun 2022
4 Jul 2022
16 Jun 2022
Amount
SUPPLYING, INSTALLATION, TESTING AND COMMISSIONING FOR ELECTRICAL INFRASTRUCTURE FOR PROVISION OF AIRCONDITIONERS AT MAIN BUILDING AT CIVIL SECRETARIAT JAMMU (KINDLY REFER ENCLOSED LIST IN SBD OF APPROVED MAKES)
Supplying, Installation, Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers, Out Goings, Bus Bars etc. as required as per the Following Description.(IP:42)Floor Distribution Panels (Main Building).The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved. The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel. Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating. INCOMER MCCB 100 Amps 4 P Adj Thermal and Adj. Magnetic Release 36 KA with Extendable ROH Mechanism (01 Nos) LED Indicating Lamps RYB (01Set) 3 Ph. LED Voltmeter with Input voltage measurement range 50-520 VAC (P-P) Class-1(01 Nos) 3Ph LED Ammeter Cl 0.5 (01 Nos) Current Transformer 100/5 A 10 VA Burden, Class-1(01 sets) Aluminium Busbar 150 Amps FP E-91 E Grade Electrolytic Aluminium Digital Load Manager with RS-485 Port Siemens Smart 7 KT or Equivalent (01 Nos) SP MCB 2 A (03Nos) LED Indicating Lamps ON OFF TRIP (01 Nos) OUTGOINGS 32 A D.P MCB "10 KA" C Curve (16 Nos) Size of wiring for CTS: - 2.5 sqmm Size of wiring for voltage sensing Metering:-4.0 Sq.mm Size of wiring of all push buttons, indicating lamps:-1.5 Sq.mm Types of wires:-PVC insulated 1100V grade, Multistrand copper conductor Flexible FR-LSH ISI Make Hinged Door Earthing:-Device mounted hinged doors connected to cubicles body by means of 2.5sqmm.green copper flexible wire. The Complete Panel Shall be made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc.with powder coating of min 75 microns thickness Gland Plates to be 3.0 mm Thick.
Supplying and Laying of Aluminium Stranded Conductor XLPE insulated,PVC inner Sheath,Armoured with Galvanised Steel Strip with Extruded PVC Outer Sheath,650/1100 Volts Grade as per IS:7098(part-1) 1988 with upto date Amendments of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe as Required.The Cable Shall be Anti Rodent and Anti termite. 3.5 C X 400 Sq.mm A2XFY
Supplying and Laying of Aluminium Stranded Conductor XLPE insulated,PVC inner Sheath,Armoured with Galvanised Steel Strip with Extruded PVC Outer Sheath,650/1100 Volts Grade as per IS:7098(part-1) 1988 with upto date Amendments of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe as Required.The Cable Shall be Anti Rodent and Anti termite. 3.5 C X 95 Sq.mm A2XFY
Supply and Making end Termination with Brass Compression Gland and Aluminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required (Comet) 3½ X 400 sq. mm (82mm)
Supply and Making end Termination with Brass Compression Gland and Aluminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required (Comet) 3½ X 95 sq. mm (45mm)
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required 300 mm width X 62.5 mm depth X 2.0 mm thickness
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
ESTIMATE FOF ELECTRICAL INFRASTRUCTURE FOR PROVISION OF AIRCONDITIONERS AT MINI SECRETARIAT JAMMU
Supplying,Installation,Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42)Floor Distribution Panels (Mini Secretariat).The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating. INCOMER MCCB 100 Amps 4 P Adj Thermal and Adj. Magnetic Release 36 KA with Extendable ROH Mechanism(01 Nos) LED Indicating Lamps RYB (01Set) 3 Ph. LED Voltmeter with Input voltage measurement range 50-520 VAC (P-P) Class-1(01 Nos) 3Ph LED Ammeter Cl 0.5 (01 Nos) Current Transformer 100/5 A 10 VA Burden, Class-1(01 sets) Aluminium Busbar 150 Amps FP E-91 E Grade Electrolytic Aluminium Digital Load Manager with RS-485 Port Siemens Smart 7 KT or Equivalent(01 Nos) SP MCB 2 A(03Nos) LED Indicating Lamps ON OFF TRIP( 01 Nos) OUTGOINGS 32 A D.P MCB "10 KA" C Curve(16 Nos) Size of wiring for CTS:- 2.5 sqmm Size of wiring for voltage sensing Metering :-4.0 Sq.mm Size of wiring of all push buttons, indicating lamps:-1.5 Sq.mm Types of wires:-PVC insulated 1100V grade ,Multistrand copper conductor Flexible FR-LSH ISI Mark Hinged Door Earthing:-Device mounted hinged doors connected to cubicles body by means of 2.5sqmm.green copper flexible wire . The Complete Panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc.with powder coating of min 75 microns thickness Gland Plates to be 3.0 mm Thick.
Supplying and Laying of Aluminium Stranded Conductor XLPE insulated,PVC inner Sheath,Armoured with Galvanised Steel Strip with Extruded PVC Outer Sheath,650/1100 Volts Grade as per IS:7098(part-1) 1988 with upto date Amendments of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe as Required.The Cable Shall be Anti Rodent and Anti termite. 3.5 C X 400 Sq.mm A2XFY
Supplying and Laying of Aluminium Stranded Conductor XLPE insulated,PVC inner Sheath,Armoured with Galvanised Steel Strip with Extruded PVC Outer Sheath,650/1100 Volts Grade as per IS:7098(part-1) 1988 with upto date Amendments of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe as Required.The Cable Shall be Anti Rodent and Anti termite. 3.5 C X 95 Sq.mm A2XFY
Supply and Making end Termination with Brass Compression Gland and Aluminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required (Comet) 3½ X 400 sq. mm (82mm)
Supply and Making end Termination with Brass Compression Gland and Aluminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required (Comet) 3½ X 95 sq. mm (45mm)
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 900 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 300 mm width X 62.5 mm depth X 2.0 mm thickness
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
SATISH & CO
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .