| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹63.0 LAccepted-AOC | ₹63.0 L Quoted ₹63.7 L | L1 | Accepted-AOC Award of contract |
| 2 | L2₹73.2 LRejected-Finance 10TH FLOOR UNIT 2 TECHNIPLEX 2 VEER SAVARKAR FLYOVER S V ROAD GOREGOAN WEST MUMBAI 400 062 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400062 | ₹73.2 L | L2 | Rejected-Finance High bidding agency |
| 3 | Rejected-Technical A 99 SECTOR 4 AIROLI NAVI MUMBAI 400708 | NAVI MUMBAI | THANE | MAHARASHTRA | 400708 | - | - | Rejected-Technical Technically disqualified |
| 4 | Rejected-Technical | - | - | Rejected-Technical Technically disqualified |
| Sl No | Description | Qty | Unit | VAV Airconditioning L2 | Mr. Srinivas R Gubbala L1 |
|---|---|---|---|---|---|
| 1.00 | Supply & installation of cabinet type exhaust Air Dry Scrubber unit. package type Dry Scrubber for kitchen exhaust covers the design requirement, constructional feature, supply, installation, testing & commissioning. It shall be an electrostatic type air cleaner. The Air Cleaner shall handle the contaminated air from kitchen
exhaust hoods containing grease, smoke (aerosols) etc.
Capacity- 10300 CFM , Static pressure 75 mm.
Make of Scrubber - Air vision, Ensaviour, System Air. | 2 | Nos | 8,80,733 ₹17.6 L | 8,49,230 ₹17.0 L |
| 2.00SITC of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressors), minimum two compressors (with individual seperate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing units), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50HzAC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 7.4, Capacity > 40 and <70 ISEER 7.5, Capacity > 70 ISEER 7.6 for Super ECSBC Building) Make - Toshiba, Mitsubishi, Trane, Hisense. | |||||
| 2.01 | 10HP | 4 | No | 2,40,165.5 ₹9.6 L | 2,55,565 ₹10.2 L |
| 3.00SITC of following minimum capacity and external static pressure VRF/VRV celling mounted high ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ≤ 10%, 50 Hz complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) High Static Ductable units( minimum 78 pascal external static pressure) (CFM - 3200) Make - Toshiba, Mitsubishi, Trane, Hisense. | |||||
| 3.01 | 8 TR Ductable | 4 | No | 1,05,883.5 ₹4.2 L | 1,29,532 ₹5.2 L |
| 4.00SITC including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRVVRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required. Make - Mandev, Maxflow, Hari Om Metals. | |||||
| 4.01 | Copper Piping 9.5 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation | 225 | Rmt | 547 ₹1.2 L | 407 ₹91,575 |
| 4.02 | Copper Piping 22.2 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation | 225 | Rmt | 1,128 ₹2.5 L | 1,067 ₹2.4 L |
| 5.00SITC of Y/T/Multi Joints. Joints shall be of same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs | |||||
| 5.01 | Indoor Units | 4 | Each | 111 ₹444 | 4,254 ₹17,016 |
Tender Value
₹68.5 L
EMD Value
₹1.4 L
Closing Date
15 Sept 2025, 6:55 pmClosed
OIC, Engineering, TMC on behalf of Director, TMC
Engineering Department, 6th Floor, Service Block, TMH, Parel
Proposed renovation of Kitchen Department, ground floor, Service Block, TMH, Parel - HVAC Mechanical Works
2025_TMC_873794_1
TMC/ENG/HVAC/Kitchen/25-26/25
Open Tender
Machineries/ Mechanical Engg Items
90 days
TMH, Parel
As per tender documents
6 documents required · 6 mandatory
₹0
₹1.4 L
TMH, Parel
26 Mar 2026
21 Aug 2025
17 Sept 2025
21 Aug 2025
15 Sept 2025
5 Sept 2025
21 Aug 2025 - 25 Aug 2025
26 Aug 2025
Amount
Supply & installation of cabinet type exhaust Air Dry Scrubber unit. package type Dry Scrubber for kitchen exhaust covers the design requirement, constructional feature, supply, installation, testing & commissioning. It shall be an electrostatic type air cleaner. The Air Cleaner shall handle the contaminated air from kitchen exhaust hoods containing grease, smoke (aerosols) etc. Capacity- 10300 CFM , Static pressure 75 mm. Make of Scrubber - Air vision, Ensaviour, System Air.
SITC of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressors), minimum two compressors (with individual seperate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing units), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50HzAC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 7.4, Capacity > 40 and <70 ISEER 7.5, Capacity > 70 ISEER 7.6 for Super ECSBC Building) Make - Toshiba, Mitsubishi, Trane, Hisense.
SITC of following minimum capacity and external static pressure VRF/VRV celling mounted high ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ≤ 10%, 50 Hz complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) High Static Ductable units( minimum 78 pascal external static pressure) (CFM - 3200) Make - Toshiba, Mitsubishi, Trane, Hisense.
8 TR Ductable
SITC including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRVVRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required. Make - Mandev, Maxflow, Hari Om Metals.
Copper Piping 9.5 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation
Copper Piping 22.2 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation
SITC of Y/T/Multi Joints. Joints shall be of same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs
Indoor Units
Outdoor Multi joints
SITC of Control cable
SITC of Drain Piping with Insulation--19mm
Removing and refixing of existing hoods to the new location as per instructions of EIC.
SITC of Wall mounted type kitchen exhaust fume hood in SS (304) constuction 19SWG at flow rate of 0.5 cu mtr / sec with SS (304) oil Filters openable type to capture oil and evacuate heat smoke ,odour, steam, vapour and other contaminante generated from cooking in order to provide comforable and productive work environment for kitchen personnel. Size -60'' x 30'' x 21''
SITC of ceiling suspended island type kitchen exhaust fume hood in SS (304) constuction 19SWG at flow rate of 0.5 cu mtr / sec with SS (304) oil Filters openable type to capture oil and evacuate heat smoke ,odour, steam, vapour and other contaminante generated from cooking in order to provide comforable and productive work environment for kitchen personnel. Size -86'' x 30'' x 21''
SITC of wall mounted type kitchen exhaust fume hood in SS (304) constuction 19SWG at flow rate of 0.5 cu mtr / sec with SS (304) oil Filters openable type to capture oil and evacuate heat smoke ,odour, steam, vapour and other contaminante generated from cooking in order to provide comforable and productive work environment for kitchen personnel. Size -78'' x 30'' x 21''
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows,splitter dampers, vanes, hangers, supports etc. as per approved drawings andspecifications of following sheet thickness complete as required. Make- Jindal
22Gauge GI ducting
20 Gauge GI ducting
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc Make- Dynacraft, Cosmos, S M Sheet
Supply and Fixing of Extruded AL powder coated Linear Grill with 4 side flanges and AL Box Damper.
Supply and Fixing of Extruded AL powder coated Linear Grill with 4 side flanges without damper
S/F of canvas Piece According to Duct size.
Supply & Installation of Acoustic lining on GI Supply air ducts. The Acoustic material shall be 15 mm thick open cell elastomeric foam class '1'. The density shall be 140 to 180 kg.m3 with thermal conductivity of 0.047 W/ m2k Deg @20deg .Material shall have anti-bacterial properties The insulation shall be as per technical specification and drawings etc, All joints to be sealed with anti condensation tapes. All loose ends to be trated with nosing frames as per details provided in Typical connection details drawing. Make : Armaflex, Vidoflex, ALP
SITC of Cabinet type single skin inline fresh air fan with air filters complete with blower and direct drive motor. 2000 CFM. Make - Air vision, Ensaviour, System Air.
Structural steel work : With M.S.channel, M.S.angle, M.S. plate at all levels including supplying, cutting, fabricating, welding or bolting, errecting and fixing in position including painting with a primary coat of approved amke Zinc Chromate primer, including cost of materials labour directed by engineer in charge with two coats of enamel paint. Neccessary arrangement of scaffolding to be made by vendor. Vender shall take all safety precaution while execution of work.
Supply and application of Fire-Retardant Ductwork. Ducts shall be coated with Fire Resistance coating of minimum 600-700 micron (DFT) thickness applied over ducts to provide 2 hours Fire rating. The Fire Resistance coating shall be tested as per requirements of BS 476 : part 6 'Class O' and part 7 'Class 1' and BS 476 part 24 (Type A and B) to analyze stabiltiy, integrity,insulation performance for 2 hours, the duct sheet shall also conform to performance criteria (stability, integrity, insulation) without insulation for 2 hours. The average and maximum temperature of unexposed faces with or without insulation shall not exceed 140 deg. Cel and 180 deg. Cel respectively to ensure the insulation performance criteria . The coationg shall be free or has minimum toxic elements such as lead, mercury, arsenic and has low VOC less than 50 gm/ liter. Coated Ducts shall be treated externally with 48 Kg/m3, 50 mm thick mineral wool insulation laminated with aluminium foil. Make :- Feukem / Hilti / 3 M / Pidilite
SITC of 1100 V a.c. grade FRLS PVC armoured AL/CU cabling along with appropriate size of saddles,spacers complete with GI conduit in approved manner. Make- Polycab/RRK/Finolex
3 Core x 4 Sqmm CU Cable
3 Core x 2.5 Sqmm CU Cable
3 Core x 1.5 Sqmm CU Cable
4 Core x 4 Sqmm CU Cable
SITC of GI earthing of 8 SWG including end connections complete in all respect.
Supply and Fixing of G.I. Perforated cable tray Medium duty with proper vertical and horizontal supports. Make - Pioneer
Set of Start and Stop Push buttons with weatherproof enclosure for remote operating of scrubber.
S.I.T.C. of 4 way type Chilled water Cassette Units complete as per technical specifications and including multiple speed fan control, intelligent drain-pump mechanism to be included, built in drain pump interlock, Factory made pre-fit valve assembly box including 2 way PICV/ PIBCV and supplied with LCD corded /cordless remote control. The Fan assembly shall include fan impeller with BLDC direct drive fan motor. The motor shall be sealed and lubricated for life, the whole assembly being statically and dynamically balanced. The motor shall be of the totally enclosed, permanent split capacitor type with thermal safety cut out. The evaporator coil shall be manufactured from seamless copper tubes with internal grooving, and mechanically bonded to aluminium fins. Units shall have power plug with 1.5 mtrs cable. Capacity -4 TR / 1600 CFM. Make - Sinco, Bhutoria, Trane, Midea.