CWE AF BIKANER
HQ CWE AF BIKANER
REPAIR/ MAINTENANCE TO POWER TRANSFORMER AND DISTRIBUTION TRANSFORMER, LT/ APFC AREA PANELS WITH CONNECTED ITEMS AT RESIDENTIAL AREA AT AF STN NAL
2026_MES_781425_1
81675/E8
Open Tender
Civil Works
Item Rate
270 days
GE AF NAL
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF NAL
₹80,000
Yes
29 Jul 2026
29 Jul 2026
21 Aug 2026
29 Jul 2026
19 Aug 2026
12 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for repair and servicing of HT 33KV Main Receiving power station pole structures by replacing galvanized PG clamps, GI bolts and nuts, pieces of ACSR conductor with insulation of any size as jumpers including lubricating the moving parts of AB switch and cleaning of all disc /pin insulators and applying silicon compound for prevention of arcing due to dust/ salt deposits over the surfaces including applying one coat of zinc oxide primer on rusted portions after preparation of surfaces & a coat of aluminum paint to the entire structure complete all as directed.
Note: -(1) Rate quoted shall be inclusive of two coats of white wash on exposed concrete surfaces and steel surfaces, ACSR conductor for jumpering, Bus Bar , replacement of unsv disc/pin type insulator by new, GI hard ware like nuts, bolts etc complete. (2). Contractor should visit the MRS Yard before quoting tender. | 1 | Each Job | - | - |
| 2 | Supply Fixing in repair buchloz realy for 33 KV power transformer of capacity 2.5MVA/3.15MVA with complete all as specified and directed | 1 | Each | - | - |
| 3 | Supply Fixing in repair WTI & OTI meter of 33KV / 11KV power transformer of capacity 2.5MVA/3.15MVA with complete all as specified and directed | 1 | Each | - | - |
| 4 | Servicing of Power transformer step down 33KV/ 11KV outdoor type of capacity 2.5MVA/3.15 MVA after disconnecting electrically the transformer carefully at the site, inspection/repair, top up the transformer oil, replacement of unserviceable rubber bushes and washers, replacement thimbles, replacement of silica gel and gasket set of top cover including pasting with pasting material,replacement of worn out nut and bolts , replacement of unserviceable of LT & HT bushes ,making all connection with suitable copper lugs , re-installing after cleaning conservator tank ,expulsion vent etc ,Meggering the LT and HT side of the transformer and testing complete all as specified and directed by Engineer-in-charge . Note :(i) Consumables like nuts bolts and washers are incluisive in th quoted rates,However other items shall be measured and paid separately in the respective items under. (ii) Joint shall be leak proof and any leakage noticed after repair work shall be rectified by the contractor without any extra cost to the deptt. (iii) Contractor shall provide necessary tripod, chain & pulley, T&P, etc for transportation and the rent shall deemed to be included in the quoted rate. | 2 | Each Job | - | - |
| 5 | Supply and Fixing in repair 33KV three phase elctric energy meter (trivector Energy meter), Class-0.2S accuracy, suitable for 3 Phase 4 Wire HT metering system, operating voltage 6 x 63.5V, basic current ratting 5A(lb), Max current 10A(200% of lb), 50Hz frequency, compliant with IS 14697 standard, with LCD display, pulse output facility, CT/PT operated, auxiliary supply 60-240V AC/DC+-20%, self powered and complete communication & energy monitoring feaures with testing, commissioning all as specified and directed.Make-Secure Meters Ltd, Model Apex 150, ABT type. or other equivalent make of approved make list. Note:-1. Contractor should visit the MRS Yard before quoting tender. 2. The installation, testing, commissioning and calibration of ABT meter shall be completed in pressence of JDVVNL Rep. and the above expenditure included in the above quoted rate. | 2 | Each | - | - |
| 6 | Supplying and fixing in repair, Porcelain Transformer bushing on HT (11 KV) side, including brass stems conical bush and gasket after disconnecting electrically and mechanically for outdoor transformer of capacity 2.5MVA/3.15MVA and connecting electrically and mechanically, testing complete all as specified and directed.
Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers and suitable size pad type bus bar almuminium and nut bolt washers and reconnection | 2 | Each | - | - |
| 7 | Supplying and fixing in repair, Porcelain Transformer bushing on HT (33 KV) side, including brass stems conical bush and gasket after disconnecting electrically and mechanically for outdoor transformer of capacity 2.5MVA/3.15MVA and connecting electrically and mechanically, testing complete all as specified and directed.
Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers and suitable size pad type bus bar almuminium and nut bolt washers and reconnection | 2 | Each | - | - |
| 8 | M&L for preparation of old painted surfaces steel by brushing/changing stain, greasy spots with thinner and apply two coats of spray painting with with super enameled smokes grey colour paint of approved by Dept. and writing the MES /SM No with white paint for outdoor type power transformer of capacity 2.5MVA/ 3.15MVA installed at various different locations complete all as specified and directed at site. | 2 | Each Job | - | - |
| 9 | Servicing of distribution transformer step down 11 / 0.433 KV indoor /outdoor type of capacity upto 315 KVA after dismantling the transformer carefully at the site or workshop , opening the top cover of transformer for inspection/repair, draining out the transformer oil from the housing complete,removing the carbon/sludge (which deposit in transformer housing core), replacement of unserviceable rubber bushes and washers, replacement of tap changer winding and thimbles, replacement of silica gel and gasket set of top cover including pasting with pasting material,replacement of worn out nut and bolts , replacement of unserviceable of LT & HT bushes, replacement of conservative tank glass ,making all connection with suitable copper lugs ,filling of new transformer oil , re-installing the top cover after cleaning conservator tank ,expulsion vent etc ,Meggering the LT and HT side of the transformer and testing complete all as specified and directed by Engineer-in-charge . Note :(i) Consumables like nuts bolts and washers are incluisive in th quoted rates,However other items shall be measured and paid separately in the respective items under. (ii) Joint shall be leak proof and any leakage noticed after repair work shall be rectified by the contractor without any extra cost to the deptt. (iii) Contractor shall provide necessary tripod, chain & pulley, T&P, etc for transportation and the rent shall deemed to be included in the quoted rate. | 15 | Each Job | - | - |
| 10 | All as per srl item No.9 as above but capacity of transformer more than 315 KVA and up to 630 KVA complete all as specified and directed . | 2 | Each Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
Tenderdocuments.pdf
Tender Documents • 2.46 MB
BOQ_875387.xls
BOQ • 0.45 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].