CWE Mamun
HQ CWE Mamun Pathankot 145001
MAINT TO CERTAIN TRANSFORMER, PROTECTION SYSTEM, HT OVER HEAD AND CABLE NETWORK INCLUDING CALIBRATION OF RELAYS UNDER GE (S) MAMUN AT MAMUN MIL STN
2019_MES_308642_1
CWE/M-41/2019-20
Open Tender
Civil Works
Item Rate
180 days
GE (S) Mamun
Class E category b ii
5 documents required · 5 mandatory
₹500
Yes
GE South Mamun
₹30,000
Yes
29 Feb 2020
23 Dec 2019
28 Jan 2020
23 Dec 2019
27 Jan 2020
13 Jan 2020
Amount
Disconnecting all the electrical connections from H.T. and L.T. side of unserviceable transformer of capacity upto and including 100 KVA i.e. Jumpers/cable from the cable end box or bushings & earthing terminal of the transformers including taking down, loading, unloading of transformer & transportation by vehicle from substation to the repairing workshop & tranportation from workshop to same substation or any other substation / including reinstallation, commissioning and testing after repair complete all as specified and directed Note : Repair to transformer shall be measured & paid for seperately under relevent items of BOQ)
All as per srl item No 01 above but capacity of transformer above 100 KVA to 315 KVA ( incl. 315 KVA) complete all as specified and directed
All as per srl item No 01 above but capacity of transformer above 315 KVA to 500 KVA ( incl. 500 KVA) complete all as specified and directed
Opening the transformer cover of capacity upto & incl 100 KVA along with the conservator by removing the nuts bolts , removing the internal H.T. & L.T. connections by taking them out by removing studs, bushings, taking out the core-winding assembly out of the tank, removing out burnt HV and LV windings from the core assembly, cleaning of core assembly with Carbon Tetra Chloride solution including necessary repairs for the unserviceable transformers having ratio 11 / 0.433 KV, draining & decanting of burnt transformer oil and cleaning of sludge deposited in the tank with Carbon Tetra Chloride solution for the transformers , rewinding of HV and LV coils with suitable size super enamelled copper wire / copper / aluminium strip (As Existing) having suitable class insulation material,heating of core winding assembly in hot chamber for 48 hours and removing all the moisture present in it, removal of leakage of tank if any by welding, refilling transformer oil to tank, after putting the core-winding assembly into the tank, reassembling making the internal H.T. & L.T. connections by fixing the studs, bushing, fitting the top cover by replacing cork sheet gasket along with conservator, testing the transformer in the workshop duly filled with oil complete all as specified & directed. Note : (i) The quoted rates shall includes for labour required for S&F in replacement of unserviceable spare part & Spare parts shall be measured & paid for seperately under respective items as supply only (ii) Transformer oil with die electric strength not less than 40 KV either new or filtered shall be filled and shall be measured and paid seperately under respective items of this BOQ.
All as Per Srl item No 4 above but of capacity above 100 KVA to 200 KVA ( incl. 200 KVA) complete all as specified & directed
All as Per Srl item No 4 above but of capacity above 200 KVA to 315 KVA ( incl. 315 KVA) complete all as specified & directed
All as Per Srl item No 4 above but of capacity above 315 KVA to 500 KVA ( incl. 500 KVA) complete all as specified & directed
Opening the transformer cover upto & incl 100 KVA along with the conservator by removing the nuts bolts then after removing the internal H.T. & L.T. connections by taking them out by removing studs, bushings, taking out the core-winding assembly out of the tank of transformers having ratio 11/0.433 KV, draining & decanting of transformer oil and cleaning of sludge deposited in the tank with Carbon Tetra Chloride solution for the transformers , heating of core winding assembly in hot chamber for 48 hours and removing all the moisture present in it, removal of leakage of tank if any by welding, refilling transformer oil to tank, after putting the core-winding assembly into the tank, reassembling, making the internal H.T. & L.T. connections by fixing the studs, bushing, fitting the top cover by replacing cork sheet gasket along with conservator, testing the transformer in the workshop duly filled with oil complete all as specified & directed
All as Per Srl item No 8 above but of capacity above 100 KVA to 200 KVA ( incl. 200 KVA) complete all as specified & directed
All as Per Srl item No 8 above but of capacity above 200 KVA to 315 KVA ( incl. 315 KVA) complete all as specified & directed
All as Per Srl item No 8 above but of capacity above 315 KVA to 500 KVA ( incl. 500 KVA) complete all as specified & directed
Supply only super enamelled copper winding wire/strip of any size for H.T. coils of transformers complete all as specified & directed
Supply only aluminium winding wire/strip of any size for H.T. coils of transformers complete all as specified and as directed.
Supply only copper winding strip of any size for L.T. coils of transformers including providing insulation complete all as specified & directed
Supply only aluminium winding strip of any size for L.T. coils of transformers including providing insulation complete all as specified & directed
Reconditioning of LT coil of aluminium / copper wound transformer by turning the old paper insulations, straightening the entire LT Strip providing new paper insulations of superior quality and making coil of suitable design as original complete all as specified and directed
S&F in replacement of unserviceable LT bushings 433V of suitable size for outdoor/ indoor type transformer upto & incl 100 KVA capacity complete all as specified and directed
All as Per Srl item No 17 above but of capacity above 100 KVA to 200 KVA ( incl. 200 KVA) complete all as specified & directed
All as Per Srl item No 17 above but of capacity above 200 KVA to 315 KVA ( incl. 315 KVA) complete all as specified & directed
All as Per Srl item No 17 above but of capacity above 315 KVA to 500 KVA ( incl. 500 KVA) complete all as specified & directed
S&F in replacement of unserviceable HT bushings 11KV of suitable size for outdoor type transformer upto & incl 100 KVA capacity complete all as specified and directed
All as Per Srl item No 21 above but of capacity above 100 KVA to 200 KVA ( incl. 200 KVA) complete all as specified & directed
All as Per Srl item No 21 above but of capacity above 200 KVA to 315 KVA ( incl. 315 KVA) complete all as specified & directed
All as Per Srl item No 21 above but of capacity above 315 KVA to 500 KVA ( incl. 500 KVA) complete all as specified & directed
S&F in replacement of unserviceable HT bushings 11KV of suitable size for indoor type transformer upto & incl 100 KVA capacity complete all as specified and directed
All as Per Srl item No 25 above but of capacity above 100 KVA to 200 KVA ( incl. 200 KVA) complete all as specified & directed
All as Per Srl item No 25 above but of capacity above 200 KVA to 315 KVA ( incl. 315 KVA) complete all as specified & directed
All as Per Srl item No 25 above but of capacity above 315 KVA to 500 KVA ( incl. 500 KVA) complete all as specified & directed
S&F in replacement of unserviceable brass stud (for LT 433V side) of suitable size complete with one check nut, two nuts, washers and rubber seal, all as per sample for outdoor/indoor type transformer upto & incl 100 KVA capacity complete all as specified and directed
All as Per Srl item No 29 above but of capacity above 100 KVA to 200 KVA ( incl. 200 KVA) complete all as specified & directed
All as Per Srl item No 29 above but of capacity above 200 KVA to 315 KVA ( incl. 315 KVA) complete all as specified & directed
All as Per Srl item No 29 above but of capacity above 315 KVA to 500 KVA ( incl. 500 KVA) complete all as specified & directed
S&F in replacement of unserviceable brass stud (for HT 11KV side) of suitable size complete with one check nut, two nuts, washers and rubber seal, all as per sample for outdoor/indoor type transformer upto & incl 100 KVA capacity complete all as specified & directed
All as Per Srl item No 33 above but of capacity above 100 KVA to 200 KVA ( incl. 200 KVA) complete all as specified & directed
All as Per Srl item No 33 above but of capacity above 200 KVA to 315 KVA ( incl. 315 KVA) complete all as specified & directed
All as Per Srl item No 33 above but of capacity above 315 KVA to 500 KVA ( incl. 500 KVA) complete all as specified & directed
S&F in replacement of unserviceable oil level indicator for transformer of capacity upto 315 KVA all as per existing and having level marking 1/4, 1/2, 3/4 and full all as directed or required at site complete all as specified & directed
S&F in replacement of unserviceable breather assembly for transformer of capacity upto 500 KVA all as per existing complete all as directed by Engr-in-Charge or required at site.
S&F in replacement of unserviceable Arcing Horns of suitable size complete all as per sample for transformer of upto & incl 200 KVA capacity complete all as specified & directed
All as Per Srl item No 39 above but of capacity above 200 KVA to 500 KVA ( incl. 500 KVA) complete all as specified & directed
S&F in replacement of unserviceable Diapharm of breather assembly for transformer of capacity upto 500 KVA complete all as per existing specification and size requried at site complete all as specified & directed
Dehydration including filteration of transformer oil using dehydration filteration plant including testing of sample before and after dehydration and filteration complete all as specified and directed for the following capacity of transformer. (The dielectric strength to be achieved 40 KV at 2.5 mm gap after completion of dehydration and filteration). Note:- (i) Dehydration of transformer oil in the Transformer carried out on the site by dehydration machine and the amount quoted is deemed to be inclusive of this provison. (ii) All the Labour work like disconnection of cable and reassemble & drum etc. has to be carried out by contractor under their own arrenement & deemed included in their quoted rate)
(a) Upto 100 KVA
(b) Above 100KVA upto and including 100 KVA
(c) Above 200KVA upto and including 315 KVA
(d) Above 315KVA upto and including 500 KVA
(e) Above 500KVA upto and including 1000 KVA
M&L for Toping up/ filling of new transformer oil in different transformer complete all as specified and as directed.
M&L for Preparation of old painted surfaces and cooling coils/ fins of transformers of upto 100 KVA ( incl. 100 KVA) capacityacities by removing oil marks using chemical or hot blow lamp. Spray painting to prepared surfaces using synthetic enamel paint of superior quality of colour as approved by GE / AGE E/M as per standard engineering practice with two coats, writing SM No, MES No, Make and capacity with white paint having height of each letter not less than 2.5cm and width not less than 1cm complete all as specified & directed
All as Per Srl item No 44 above but of capacity above 100 KVA to 200 KVA ( incl. 200 KVA) complete all as specified & directed
All as Per Srl item No 44 above but of capacity above 200 KVA to 315 KVA ( incl. 315 KVA) complete all as specified & directed
All as Per Srl item No 44 above but of capacity above 315 KVA to 500 KVA ( incl. 500 KVA) complete all as specified & directed
S&F in replacement of unserviceable silica gel superior quality to transformer breather assy all as required complete all as specified and directed.
Excavating in trenches in any type of soil, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out incl retreiving/ taking out old bricks/ cable covers and stacking at site complete all as specified and directed.
Excavating in trenches in any type of soil, n exc 1.5 m wide and exc. 1.5 m but n exc 3 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out incl retreiving/ taking out old bricks/ cable covers and stacking at site complete all as specified and directed.
Removing excavated material to a distance not exceeding 50 Mtr and deposting where directed at a level not exc. 1.5 mtr above the starting point complete all as specified and directed.
Returing filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm each all as required complete all as specified and directed.
M&L for Un-reinforced precast concrete cable cover, class HV, type 1, with peak of size 300mm x 180mm x 40mm for protecton of cable abutting each laid dry flat width equal to the length of cable cover etc complete all as spd and directed.
M&L for Dry fine sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm thick after laying, stretching and testing the cable all as direted. Note : Punned thickness shall be measured & paid
M&L for detection of any type of fault in HT underground Line of any size and core. (laid in soil at plane area or forest area) with the help of HT Meggar. Seggregation of faulty span by meggering and making span serviceable by repair of cable or S&F in replacement of cable. Note : 1. Detection of one fault in faulty span will be measured as Each Job. 2. Earth work and taking out will be measured seperately. 3. Material for repair and S&F in replacement will be measured saperately.
Detection of any type of fault in HT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator with carring vehicle will be brought by the cable fault detection agencies. Span of faulty cable will be trace out by the agencies by meggering HT cable. Note : 1. Detection of fault in one span of length will be measured as Each Job. 2. Technicians will be employed by the working agencies. 3. Earth work and taking out will be measured seperately. 4. Material for repair and S&F in replacement will be measured saperately. 5. One Job shall be measured if the fault has successfully rectified by the fault locator machine and Technician.
S&F in replacement of unserviceable HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty ) with aluminium conductor, 11KV grade, suitable for earthed system, with aluminium conductor of size 95 Sqmm 3 core incuding taking down unserviceable HT cable of any type / size/ description , etc laid in trenches or fixed to wall / pole or passing through pipes or road crossing, incl testing complete all specified and directed. (Note : Excavation & Earth work shall be measured and paid sepratley.)
S&F in replacement of unserviceable HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty ) with alumn conductor, 11KV grade, suitable for earthed system, with aluminium conductor of size 120 Sqmm 3 core incuding taking down unserviceable HT cable of any type / size/ description , etc laid in trenches or fixed to wall / pole or passing through pipes or road crossing, incl testing complete all specified and directed. (Note : Excavation & Earth work shall be measured and paid sepratley.)
S&F in replacement of unserviceable HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty ) with alumn conductor, 11KV grade, suitable for earthed system, with aluminium conductor of size 300 Sqmm 3 core incuding taking down unserviceable HT cable of any type / size/ description , etc laid in trenches or fixed to wall / pole or passing through pipes or road crossing, incl testing complete all specified and directed. (Note : Excavation & Earth work shall be measured and paid sepratley.)
Dismantling cross-arms of M.S. channel or angle sections complete all as specified and directed
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one Prime coat, one under coat and one finishing coat of aluminium paint complete all as specified and directed
S&F in replacement of unserviceable Cable end termination out door, heat shrinkable type joint suitable for XLPE cable of size 50 Sqmm to 95 sqmm 3 core with working voltage 11000 volts with jointing material and accessories including testing etc complete all as specified and directed Make: Denson/ M Seal / 3 M
S&F in replacement of unserviceable cable end termination out door, heat shrinkable type joint suitable for XLPE cable of size 120 Sqmm to 185 sqmm 3 core with working voltage 11000 volts with jointing matrial and accessories including testing etc complete all as spd and directed. Make: Denson/ M Seal / 3 M
S&F in replacement of unserviceable Cable end termination out door, heat shrinkable type joint suitable for XLPE cable of size 240 Sqmm to 300 sqmm 3 core with working voltage 11000 volts with jointing matrial and accessories including testing etc complete all as spd and directed. Make: Denson/ M Seal / 3 M
S&F in replacement of unserviceable Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 sqmm 3 core with working voltage 11000 volts complete all as specified and direced Make: Denson/ M Seal / 3 M
S&F in replacement of unserviceable Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm 3 core with working voltage 11000 volts complete all as specified and direced Make: Denson/ M Seal / 3 M
S&F in replacement of unserviceable Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 400sqmm with working voltage 11000 volts complete all as specified and direced Make: Denson/ M Seal / 3 M
Restretching aluminium conductor or GI wire on existing over head lines (running on 9/11 Mtrs pole) without removing including unbinding from insulator and rebinding to insulator using aluminium binding wire , connections of incoming and out going cables, binding with spacers where required, complete all as specified. [Note :- For measurement length of set of 3 conductor including GI wire/ cradle or guarding wire shall be taken as one span (The approximate length of one span is 30 to 45m)]
S&F in replacement of unserviceable ACSR weasel conductor ( 6 x2.59 + 1 x 2.59 Al + steel) to HT/LT over head lines , stretching properly to achieve proper sag & making all connections including binding to insulators using GI/aluminium binding wire all as required at site complete all as specified and directed .
S&F in replacement of unserviceable Single disc type assembly for tension with tension clamps for conductors , working pressure 11000 Volts insulator, porcelain, vitreous having 145mm high and 255 mm dia ball and socket type and white, brown or green in color complete all as specified and directed Make :- Rashtriya / Jaipuria Brothers / BHEL.
S&F in replacement of unserviceable Two-in-series disc type assembly for tension with tension clamps for conductors , working pressure 11000 Volts insulator, porcelain, vitreous having 145mm high and 255 mm dia ball and socket type and white, brown or green in colour complete all as specified and directed Make :- Rashtriya / Jaipuria Brothers / BHEL.
S&F in replacement of unserviceable Polymer disc insulator 11KV complete all as specified and directed Make :- Rashtriya / Jaipuria Brothers / BHEL.
S&F in replacement of unserviceable Pin type porcelain vitreous insulator, white brown or green in color including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut and having 150 mm height, 150 mm dia suitable for 11000 volts complete all as specified and directed Make :- Rashtriya / Jaipuria Brothers / BHEL.
S&F in replacement of unserviceable Loop type insulator large size with overall dimensions (90 x140) mm with clearance of hole 25.5 mm vitreous white brown or green complete all as specified & directed Make :- Rashtriya / Jaipuria Brothers / BHEL.
S&F in replacement of unserviceable Composite post insulator Polymer 252 mm high & 105 mm dia complete all as specified and directed Make : Rashtriya / Japuria Brothers / BHEL.
S&F in replacement of unserviceable Composite pin insulator polymer 252 mm high & 105 mm dia complete all as specified and directed . Make : Rashtriya (Cat Pt No REE - PL -01-24F-11/33) Japuria Brothers / BHEL.
Dismantling of spares of GOD such as Male, Female, Copper belt, belt carrier and back connector plate complete all as specified and directed.
S&F in replacement of unserviceable Male Contact / moving contact blade with arching horn having brass contacts suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing on post insulator or any other indicated situation complete all as specified and directed Make : Jaipuria brothers/Rashtriya/BHEL
S&F in replacement of unserviceable Female contact spring loaded having brass contacts suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing on post insulator or any other indicated situation complete all as specified and directed . Make : Rashtriya / Japuria Brothers / BHEL.
S&F in replacement of unserviceable Tinned Copper braided flexible belt or jumper 200 Amp/400 Amp, suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing complete all as specified and directed Make : Rashtriya / Japuria Brothers / BHEL.
S&F in replacement of unserviceable MS Jumper Carrier for carrying copper braided belt , suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing complete all as specified and directed . Make : Rashtriya / Japuria Brothers / BHEL.
S&F in replacement of unserviceable Back connector plate, suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing complete all as specified and directed Make : Rashtriya / Japuria Brothers / BHEL.
Trimming up of tree branches upto 5 mtr all around HT overhead lines, removing cut branches from site complete all as specified directed. Note :- (i) The overhead lines will be kept clear from all trees by trimming of tree branches with 5 mtr all around the line. Necessary permission will be obtained from department by contractor one day prior to trimming in particular area and shut down of that area will be arranged by department accordingly. The trimming work shall be commenced once it is permitted by AGE in writing. (ii) Total length of line from supply point to load end will be measured for the purpose of payment, irrespective of the No of trees required to be trimed. (iii) only effective length i.e length where tree branches are touching HT line or neaby HT line shall only be measured & paid under this item. No claim whatsoever shall be entertained by the deptt at later stage. [The approximate length of one span is 30 to 45m]
S&F in replacement for GI tubing 150 mm bore light grade laid in trenches/floors/ fixed to wall/poles for protection of cable with necessary fittings and FI clamps duly painted complete all as specified and directed.
S&F in replacement for GI tubing 100 mm bore light grade laid in trenches/floors/ fixed to wall/poles for protection of cable with necessary fittings and FI clamps duly painted complete all as specified and directed.
KULBHUSHAN AGGARWAL
Vijay Kumar Contractor and Engineers
G.M. ENGINEERING SERVICES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .