Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.6 LAccepted-AOC 7 1 3RD AND 4TH FLOOR MAGADI MAIN ROAD NEAR MAGADI ROAD METRO STATION NEAR MAGADI ROAD METRO STATION BANGALORE KARNATAKA 560023 | BENGALURU URBAN | KARNATAKA | 560023 | L1 | Accepted-AOC Being L1 | |
| 2 | Rejected-Technical S N B 4 AP NO 14 KHANDGE HOSPITAL ROAD SHITOLE NAGAR JIJAI NIWAS SANGAVI PUNE MAHARASHTRA 411027 | PUNE | MAHARASHTRA | 411027 | - | Rejected-Technical Firm does not meet all the requirements laid in NIT. |
Tender Value
₹3.8 L
EMD Value
₹7,675
Closing Date
1 Apr 2022, 6:00 pmClosed
AGM(EE)
Asstt.Gen.Manager (E-E), Airports Authority Of India, Regional Head Quarter, W/R, Integrated operational offices building, 5th floor, Parsiwada, Vile Parle (East), Mumbai-400099
Servicing and testing of HT Panel VCBs, ACBs and Transformer installed at Power House of ATC Sky Tower, New Airport Colony and Integrated Operational Offices Building, Mumbai.
2022_AAI_107173_1
AAI/MUM/AGM-EE/06/21-22/222
Open Tender
Electrical Works
Item Rate
365 days
Mumbai
As per tender document.
22 documents required · 22 mandatory
₹1,120
Yes
₹7,675
Yes
29 Apr 2022
10 Mar 2022
4 Apr 2022
11 Mar 2022
1 Apr 2022
11 Mar 2022
11 Mar 2022 - 27 Mar 2022
Amount
SH-I : OVERHAULING /SERVICING (LOCATION : ATC SKY TOWER, MUMBAI)
Servicing and testing of following 11 KV, HT Panels including Overhauling/Servicing of all VCBs, maintainance of complete HT panel including checking all operational mechanisms, functions, positions, tripping actions, calibration of protective relays and checking their proper operation by secondary current injection technique and submitting the test reports accordingly etc.complete as required. Incomer Panel:- 630A, TP VCB :- 03 Nos Outgoing Panel:- 630A, TP VCB :- 03 Nos Bus Coupler :-630A, TP VCB 02 Nos Make & Model : L&T-EBG & EDO type
Overhauling /servicing of following L& T make 415V electrical draw out type ACBs (MODEL -C Power ) integrated in Main LT Panel & AMF panel including checking all operational mechanisms, functions, positions, tripping actions as per OEM guidelines & submitting test reports accordingly etc.complete as required. 1600 Amp, FP (Microprocessor Based Release - SR18G)
Overhauling /servicing of following L& T make 415V electrical draw out type ACBs (MODEL -C Power ) integrated in Main LT Panel & AMF panel including checking all operational mechanisms, functions, positions, tripping actions as per OEM guidelines & submitting test reports accordingly etc.complete as required. 1600 Amp, TPN (Microprocessor Based Release - SR18G)
Servicing & Testing of following 11/0.433 KV, Dry type cast resin transformers of 1000 KVA, Kirloskar Make by carrying out preventive maintenance activity of transformer as per OEM recommendations to keep the transformer in serviceable condition. Work includes opening the complete enclouser, bus bars, HT & LT side boxes, cable etc. checking of all the safety equipment’s, cleaning, servicing & Testing and submission of service reports accordingly after completion of the work as per the requirement.
LOCATION : INTEGRATED OPERATIONAL OFFICES BUILDING, MUMBAI
Servicing and testing of following 11 KV, HT Panels including Overhauling/Servicing of all VCBs, maintainance of complete HT panel including checking all operational mechanisms, functions, positions, tripping actions, calibration of protective relays and checking their proper operation by secondary current injection technique and submitting the test reports accordingly etc.complete as required. Incomer Panel:- 630A, TP VCB :- 01 Nos Outgoing Panel:- 630A, TP VCB :- 03 Nos Make & Model : Schneider & HVX-X type
Overhauling /servicing of following L&T make 415V electrical draw out type ACB (MODEL -U-power Omega) integrated in Main PCC Panel, APFC panel & synchronizing panel including checking all operational mechanisms, functions, positions, tripping actions as per OEMs guidelines & submitting test report accordingly etc. complete as required. 2500 Amp, FP (Matrix releases - MTX 3.5)
Overhauling /servicing of following L&T make 415V electrical draw out type ACB (MODEL -U-power Omega) integrated in Main PCC Panel, APFC panel & synchronizing panel including checking all operational mechanisms, functions, positions, tripping actions as per OEMs guidelines & submitting test report accordingly etc. complete as required. 1600 Amp, TP, (Matrix releases - MTX 3.5)
Overhauling /servicing of following L&T make 415V electrical draw out type ACB (MODEL -U-power Omega) integrated in Main PCC Panel, APFC panel & synchronizing panel including checking all operational mechanisms, functions, positions, tripping actions as per OEMs guidelines & submitting test report accordingly etc. complete as required. 1250 Amp, TP, (Matrix releases - MTX 3.5)
Overhauling /servicing of following L&T make 415V electrical draw out type ACB (MODEL -U-power Omega) integrated in Main PCC Panel, APFC panel & synchronizing panel including checking all operational mechanisms, functions, positions, tripping actions as per OEMs guidelines & submitting test report accordingly etc. complete as required. 800A, TP, (Matrix releases - MTX 3.5)
Servicing & Testing of following 11/0.433 KV, Dry type cast resin transformers of 1500 KVA, Voltamp Make by carrying out preventive maintenance activity of transformer as per OEM recommendations to keep the transformer in serviceable condition. Work includes opening the complete enclouser, bus bars, HT & LT side boxes, cable etc. checking of all the safety equipment’s, cleaning, servicing & Testing and submission of service reports accordingly after completion of the work as per the requirement.
LOCATION : NEW AIRPORT COLONY, MUMBAI
Servicing and testing of following 11 KV, HT Panels including Overhauling/Servicing of all VCBs, maintainance of complete HT panel including checking all operational mechanisms, functions, positions, tripping actions, calibration of protective relays and checking their proper operation by secondary current injection technique and submitting the test reports accordingly etc.complete as required. For New Airport Colony Incomer Panel:-800A, TP VCB :- 01 Nos Outgoing Panel:-800A, TP VCB :- 04 Nos Make & Model : ABB & VD4
Servicing and testing of following 11 KV, HT Panels including Overhauling/Servicing of all VCBs, maintainance of complete HT panel including checking all operational mechanisms, functions, positions, tripping actions, calibration of protective relays and checking their proper operation by secondary current injection technique and submitting the test reports accordingly etc.complete as required. For Porta Cabin Incomer Panel:- 800A, TP VCB :- 01 Nos Make & Model : ABB & VD4
Overhauling /servicing of following L& T make 415V electrical draw out type ACBs (MODEL -C Power ) integrated in Main LT Panel & AMF panel including checking all operational mechanisms, functions, positions, tripping actions as per OEM guidelines & submitting test reports accordingly etc.complete as required. 1250 Amp, TP (Thermo-magnetic Release Type - DN1)
Overhauling /servicing of following L& T make 415V electrical draw out type ACBs (MODEL -C Power ) integrated in Main LT Panel & AMF panel including checking all operational mechanisms, functions, positions, tripping actions as per OEM guidelines & submitting test reports accordingly etc.complete as required. 1000 Amp, TP (Thermo-magnetic Release Type - DN1)
Overhauling /servicing of following L& T make 415V electrical draw out type ACBs (MODEL -C Power ) integrated in Main LT Panel & AMF panel including checking all operational mechanisms, functions, positions, tripping actions as per OEM guidelines & submitting test reports accordingly etc.complete as required. 800 Amp, TP (Thermo-magnetic Release Type - DN1)
Overhauling /servicing of following L&T make 415V electrical draw out type ACB (MODEL -U-power Omega) integrated in Main PCC Panel, APFC panel & synchronizing panel including checking all operational mechanisms, functions, positions, tripping actions as per OEMs guidelines & submitting test report accordingly etc. complete as required. 1600 Amp, FP, (Matrix releases - MTX 3.5)
Servicing & Testing of following 11/0.433 KV, Dry type cast resin transformers of 1000 KVA, Kirloskar Make by carrying out preventive maintenance activity of transformer as per OEM recommendations to keep the transformer in serviceable condition. Work includes opening the complete enclouser, bus bars, HT & LT side boxes, cable etc. checking of all the safety equipment’s, cleaning, servicing & Testing and submission of service reports accordingly after completion of the work as per the requirement.
Servicing & Testing of 11 KV/ 433 Volts, 1000 KVA of Oil Transformers including checking & tightening of HT/LT cable termination,operation of tap changer, testing of transformer oil i/c acidity test, insulation resistance of transformer. The job includes complete filtration of transformer oil and top-up of oil to maintain the withstand capacity of oil minimum 40KV at least for two minutes, checking of all safety equipment and submission of test reports etc. complete as required.
SH-II: Supply of Spares
Service position microswitch - (C 6) (Make: L&T)
Microswitch for Releases (C1) (Make: L&T)
Test or isolated position microswitch - (C 8) (Make: L&T)
ACB door bazels (Make: L&T)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .