Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.4 LAccepted-AOC | L1 | Accepted-AOC Being lowest and reasonable | |
| 2 | L2₹13.1 L+₹56,315 (4.47%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹16.6 L+₹4.0 L (31.6%)Rejected-Finance GROUND FLOOR TRACTOR MARKET KAITHAL ROAD ASSANDH KARNAL HARYANA 132039 | KARNAL | HARYANA | 132039 | L3 | Rejected-Finance Being L3 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
3 Sept 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
HQ CWE AF AMBALA
HQ CWE AF Ambala
CA NO CWE/AF AMB/HAL-24/2020-21 REPAIR /MAINTENANCE OF HT INFRASTRUCTURE IN DOMESTIC AND TECHNICAL AREA AT AF STATION BARNALA UNDER GE AF HALWARA
2020_MES_364852_1
CA NO CWE/AF AMB/HAL-24/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
183 days
GE AF HALWARA
All contractors enlisted with MES in Class E and above and Category bii and for unenlisted refer tender documents
8 documents required · 8 mandatory
₹500
Yes
GE AF HALWARA
₹40,000
Yes
22 Sept 2020
28 Jul 2020
5 Sept 2020
28 Jul 2020
3 Sept 2020
21 Aug 2020
28 Jul 2020 - 7 Aug 2020
60 days
Amount
Supplying, laying, jointing, testing and commissioning of HT XLPE cable, 11000 volts (earthed), insulated, screened, sound compacted aluminium conductor, screening with extruded semi conducting layers, insulation screening with copper tape covers laid up with PVC (ST-2), extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 Part II with amendment, size 150 Sqmm, 3 core , laid in trenches /pipes /ducts /along poles/ walls/ equipment etc including taking down of old cable as exist at site from trenches complete all as specified and directed. NOTES : (i) Cable shall be of manufacturing date not earlier than Mar 2020. All the cable shall be embossed with year of manufacturing, meterage at every metre, in addition to its own standard markings as per IS i.e. Size, voltage etc. Cable shall also be tested in the presence of Rep of Accepting officer at factory premises prior to despatch and also after laying in the trench before returning filling in the trench.(ii) Excavation & earth work, sand cushioning, protection pipes, end termination joints & protection covers shall be made and paid separately. Excavation & earth work shall be paid once if cable is being laid on same location. (iii) No straight through joint shall be permitted in less than single drum length. (iv) The contractor shall produce original purchase vouchers duly machine numbered alongwith excise duty gate pass of factory for verification and record.
Excavation in trenches not exc 1.5mtr wide and not exc 1.5mtr in depth for laying of cable etc not exc 10 sqm on plan and getting out, in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading leveling watering and well ramming in layers not exc 25 cm thick each complete all as specified and as directed.
Removal of surplus soil to a distance not exc 500 mtrs & depositing where directed at a level not exc 1.5 mtrs above the starting point complete all as specified and as directed.
Material and labour for Sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after the cable (punned down to 18 cms depth after laying and stretching of cable ) complete all as specified and as directed.
Supply and laying un-reinforced precast concrete cable cover , Class HVP type-1 with peak, size 300mmx180mmx40mm for protection of cable complete all as specified and as directed.
Disconnecting of HT and DC connections from existing bus bar and disconneting trolly including servicing of complete parts of RMU 3 way, cleaning with carbon tetra chloride, lubrication of mechanical parts, adjustment and calibration of complete relays etc including checking parts, repairs to control wiring with single core copper conductor of existing size as required at site for RMU 3 way, of any type, any make for satisfactory running including replacement of defective spare parts/items and applying one coat of 11 KV insulation paint on bus bar, spouts and other connected parts/items, re-assembling the same, re-connecting all HT & AC/ DC connections to make it functional including tesing on existing load complete all as specified and as directed.
Disconnecting of HT and DC connections from existing bus bar and disconneting trolly including servicing of complete parts of RMU 4 way, cleaning with carbon tetra chloride, lubrication of mechanical parts, adjustment and calibration of complete relays etc including checking parts, repairs to control wiring with single core copper conductor of existing size as required at site for RMU 3 way, of any type, any make for satisfactory running including replacement of defective spare parts/items and applying one coat of 11 KV insulation paint on bus bar, spouts and other connected parts/items, re-assembling the same, re-connecting all HT & AC/ DC connections to make it functional including tesing on existing load complete all as specified and as directed.
Disconnecting of HT and DC connections from existing bus bar and disconneting trolly including servicing of complete parts of RMU 5 way, cleaning with carbon tetra chloride, lubrication of mechanical parts, adjustment and calibration of complete relays etc including checking parts, repairs to control wiring with single core copper conductor of existing size as required at site for RMU 3 way, of any type, any make for satisfactory running including replacement of defective spare parts/items and applying one coat of 11 KV insulation paint on bus bar, spouts and other connected parts/items, re-assembling the same, re-connecting all HT & AC/ DC connections to make it functional including tesing on existing load complete all as specified and as directed. Notes for srl No 07 to 09: 1. Spare parts shall be measured and paid for separately under respective items as supply only in replacement . 2. parts replaced shall be identical to those specified by original manufacture. 3. Parts of minor nature such as nuts, bolts, screws & washers required at site are deemed to be included in the cost quoted.
Supply and fixing in replacement self powered protection relay of RMU complete all as specified and directed Make : SEG, type WIC 1 or equivalent of make as specified.
Supply and fixing in replacement resin cast ring core protection Current Transformer of ratio 14.4/0.075A, Class 10P80, VA 0.1 or suitable for relay type W1C1, 50 C/S of RMU complete all as specified and as directed
Supply and fixing in replacement resin cast ring core metering current transformer of ratio 80/1A, Class 1.0, VA-2.5, 50C/S of RMU complete all as specified and as directed
Supply and fixing in replacement digital multifunction meter for 11 KV RMU complete all as specified and as directed. Make : Rishab Model Rish master 3430 or equivalent of make as specified.
Supply and fixing in replacement shunt tripping coil as existing of RMU complete all as specified and as directed
M&L in replacement for jointing and testing cable jointing kit for 11 KV grade cable indoor termination heat shrinkable joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 120 sqmm complete all as specified and as directed.
M&L in replacement for jointing and testing cable jointing kit for 11 KV grade cable indoor termination heat shrinkable joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 240 sqmm complete all as specified and as directed.
Supply and fixing galvanised iron strip 32x6 mm with porcelin saddles and fixing screws for roof conductors and down conductors above ground after taking down/out strip as existing at site complete all as specified and as directed. Note :- Strip should be brazed/welded at each joint.
Supply and fixing HT copper busbar of size suitable for capacity 600 Amp including taking down of existing bus bars complete all as specified and as directed.
Dismantling old unserviceable gang operated air breaker switch from two pole / four pole structure, and Supply and fixing of gang operated air breaker switch ,triple pole, mechanically operated , mounted on insulators and steel frame with operating mechanism worked from ground level using heavy duty GI pipe, for current rating 400 amps,out door type conforming to IS specifications, HT 11 KV , triple pole with fixed contacts of phosphorous , bronze and a set of drop out HT fuse assembly , fuse carrier fitting , 9 insulator type mounted on MS channel operating rod with pad lock arrangements complete all as specified and as directed.
Supply and fixing in replacement lightning arresters gapless metal oxide type consisting of Zinc Oxide varistors, FRP core and silicon housing with all fitting transmission class discharge capacity 65 kilo amps 11000 volts complete all as specified and as directed.
Supply only of tinned copper drop out fuse wire, solid conductor of size 8-26 SWG, complete all as specified and directed .
Supply only of self adhesive electrical insulation tape of size 1.8cm x 7 mtr x 0.125mm of colour as approved complete all as specified and as directed. .
Opening of all electrical connections HT/LT from the bushings/terminal box of the unserviceable distribution transformer , indoor/outdoor type from existing position/location or 4 pole structure, of any make & specifications,of capacity upto 250 KVA & transporting the transformer to authorised dealer workshop for repairs with opening of top cover including conservator, dehyderating breather and allied items, inspecting the same to assess the repairs required, making the joint inventories of unserviceable items/parts to carryout the repair works, cleaning , greasing and overhauling complete including taking out & replacement of unserviceable /worm out parts with new parts, taking out core/winding coils out from tank and replacement of burnt coils as per existing, fixing parts by draining out of transformer oil to make the transformer serviceable, refilling the transformer oil after cleaning of tank and repairing/dehyderation of oil to get the di-electric strength of oil upto 45 KV(rms), re-assembling after repairing and transporting the repaired transformer back to the work site and placing in original position, connecting all eletrical/meachnical connections, commissioning of transformer on load after testing complete all as specified & as directed. Notes:- (i) The LT/HT coils if rewinded and transformer oil if required for topping, shall be measured and paid separetely.(ii) A Board of Officers shall be appointed by the Accepting Officer for the transformers required repair works and all inventory shall be prepared in presence of contractor/accrediated reps.
Supplying,filling and pouring transformer oil, ISI marked, in sealed containers for Voltage stablizers and transformer, conforming to IS-335 with di-lectric strength not less than 50 KV and testing for strength including recording results complete all as specified and as directed. Notes:- (i) Empty sealed container shall become Govt property & shall be taken on charge through RV. (ii) Transformer oil shall be of make as specified. (iii) Purchase vouchers alongwith manufacturer's test certificate shall be produced at the time of payment.
M&L for taking out burnt copper from coils of transformer ,of any capacity,cleaning all the limbs, rewinding with supper enamelled copper wire of same weight, gauge etc of HT/LT winding with suitable gauge by calculatging mumber of turns as per voltage of transformer, varnishing and drying by vaccum impregnating, replacing insulating material, nuts,bolt etc including testing as per latest IS, compete all as specified and as directed.
Material and labour for earthing complete with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to GI earth lead strip 32x6 mm upto 7.5 mtrs long by means of bolts, nuts, check nuts and washers of galvanized iron and connection to earthing test point & earth dolly including watering pipe GI 20 mm bore, light grade including protection pipe GI medium grade 40mm bore , wire mesh, funnel,lugs, salt, charcoal dust, excavation and refilling pit chamber with PCC 1:2:4 type B1 using 20 mm graded mechnically crushed stone aggregates , RCC 1:2:4 type B-1 using 20 mm graded mechnically crushed stone aggregates pit cover slab 50 mm thick reinforced with 8 mm dia TMT bars @ 15 cm c/c both ways including necessary form work all as shown in electrical plate No 3 of SSR part-I (2009), including testing on completion including taking down of existing earthing as exists on site complete all as specified and as directed. Notes :-- (i) Any increase in length of earth strip and protection pipe of earth strip beyond 7.5 mtr length shall be measured and paid separetely.(ii) On testing if the earth resistance is not obtained, earthing will be generated at NO extra cost ,till the desired earth resistance is obtained.(iii) The chamber shall be constructed atleast 0.5 mtr away from the earth electrode.
Deduction of Total of Sch of credit amount Rs 117490.00
R D Bansal
swarn singh and co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .