Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.7 LAccepted-AOC | L1 | Accepted-AOC Being First Lowest | |
| 2 | L2₹38.0 L+₹5.3 L (16.2%)Rejected-Finance | L2 | Rejected-Finance Other Than First Lowest | |
| 3 | L3₹39.6 L+₹6.9 L (21.2%)Rejected-Finance | L3 | Rejected-Finance Other Than First Lowest |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
15 Feb 2020, 6:00 pmClosed
GE Lalgarh Jattan
GE Lalgarh Jattan
REPAIR/ REPLACEMENT OF LT OH LINES, LT UG CABLES, LT POLES, LT PANELS, FEEDER PILLAR BOX, APFC PANELS, SWITCH GEARS AND CONNECTED WORKS AT LGJ MIL STN
2020_MES_317513_1
8930-35/19-20
Open Tender
Civil Works
Item Rate
180 days
GE Lalgarh Jattan
Class D Cat (b) (i)
8 documents required · 8 mandatory
₹500
GE Lalgarh Jattan
₹80,000
Yes
GE Lalgarh Jattan
31 Mar 2020
22 Jan 2020
18 Feb 2020
22 Jan 2020
15 Feb 2020
6 Feb 2020
24 Jan 2020
Amount
Taking down old street light fitting of any wattage/size disconnecting all electrical connection complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement Integral LED street light luminaire white light comprising of epoxy powder coated housing, enclosed with glass cover in frame 45 W suitable for 40/50 mm OD entry for direct mounting on pipe bracket with all electrical accessories wired up to the terminal block suitable for mounted on bracket / poles / walls complete all as specified and directed by Engineer-in-Charge. Make : Bajaj Cat Part No BRTFG 45W V2 or equivalent in Hevels/CG.
Supply & fixing flood light fitting powder coated pressure die cast aluminium housing with mirror optic reflector toughened glass cover with high power LED 120 Watt 240 Volt 50 Hz and unique peanut lens with optics for uniform distribution with SMPS complete with drivers and LED, connectors prewired complete all as per Bajaj Cat Part No BARFEG 120W LED or equivalent in Havells/Crompton including taking down old unserviceable flood lights of any specification complete all as specified and directed by Engineer-in-Charge.
M&L for feeder piller box out door type both side openable double door and dust/vermin proof made out of 3 mm thick plain MS sheet 0.90x0.45x0.90m supported on angle iron of size 40x40x6mm including necessary PCC for grouting and powder coating paint internally and externally. The panel shall comprise of :- (a) 4 Nos aluminium bus bar of 300 Amp rating. (b) MCCB 3 Pole 415 Volt 200 Amp, rupturing capacity 35 KA. (c) 01 No MCCB 3 Pole 415 Volt 100 Amp 25KA. (d) 06 Nos MCB SP-5 32 Amp. (e) Earth terminal (f) Danger notice plate as per IS. Make : As per approved list
Laying only, jointing and testing in trenches, on poles, walls XLPE insulated armoured heavy duty electric cable with alluminium counductor 1100 Volt grade all as specified and directed of cross sectional 300 Sqmm x 3.5 core including taking down old u/s one complete all as specified and directed by Engineer-in-Charge. Note for item no. 5 to 8 : Cable shall be issued under Sch 'B' free for fixing only.
,----ditto--- All as per serial item No 5 above, but 185 Sqmm x 3.5 Core, complete all as specified and directed by Engineer-in-Charge.
,----ditto--- All as per serial item No 5 above, but 120 Sqmm x 3.5 Core, complete all as specified and directed by Engineer-in-Charge.
,----ditto--- All as per serial item No 5 above, but 95 Sqmm x 3.5 Core, complete all as specified and directed by Engineer-in-Charge.
Supply and laying, jointing and testing in trenches on poles walls XLPE insulated armoured heavy duty electric cable with alluminium counductor 1100 Volt grade of cross sectional 50 Sqmm x 3.5 Core including taking down old u/s one complete all as specified and directed by Engineer-in-Charge. Make : Havells/ Gloster /CCI.
,----ditto--- All as per serial item No 9 above, but 35 Sqmm x 3.5 Core, complete all as specified and directed by Engineer-in-Charge. Make : Havells/ Gloster /CCI.
,----ditto--- All as per serial item No 9 above, but 16 Sqmm x 2 Core, complete all as specified and directed by Engineer-in-Charge. Make : Havells/ Gloster /CCI.
,----ditto--- All as per serial item No 9 above, but 16 Sqmm x 4 Core, complete all as specified and directed by Engineer-in-Charge. Make : Havells/ Gloster /CCI.
,----ditto--- All as per serial item No 9 above, but 10 Sqmm x 2 Core, complete all as specified and directed by Engineer-in-Charge. Make : Havells/ Gloster /CCI.
Supply and fix cable joining kit for 1.1 KV grade cable for straight through joint complete with jointing material heat Shrink type and accessories suitable for 3.5 / 4 Core XLPE, armoured, Aluminium conductor cable of size 16 to 50 Sqmm, Indoor/Outdoor type complete all as specified and directed by Engineer-in-Charge. Make : Densons/M Seal / 3M
,----ditto--- All as per serial item No 14 above, but cable of size 70 to 95 sqmm Core, complete all as specified and directed by Engineer-in-Charge. Make : Densons/M Seal / 3M
,----ditto--- All as per serial item No 14 above, but cable of size 120 to 150 sqmm Core, complete all as specified and directed by Engineer-in-Charge. Make : Densons/M Seal / 3M
,----ditto--- All as per serial item No 14 above, but cable of size 185 to 300 sqmm Core, complete all as specified and directed by Engineer-in-Charge. Make : Densons/M Seal / 3M
Supply and laying best quality locally availble Sub class 'B' bricks (old size) for cable protection cover, laid flat and lay in trenches over TGE cable complete all as specified and as directed by Engineer-in-Charge.
Excavation in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables or fixing poles and stays and struts etc. not exceeding 10 Sqm on plan and not exceeding 1.5 metre in depth and getting out in soft/loose soil including trimming the sides and forming bottom surfaces to required levels complete all as specified and as directed by Engineer-in-charge.
Removing the excavated material (soil) upto a distance n.exc 50 mtr & depositing where directed a level n.exc 1.5 mtr above the starting point complete all as specified and as directed by Engineer-in-Charge.
Returning & filling in including sprading levelling, watering & well ramming in layers n.exc.1.5 mtr above starting point in soil complete all as specified and as directed by Engineer-in-Charge.
M&L for natural dry sand cushioning for cable protection complete complete all as specified and as directed by Engineer-in-Charge.
Earthing complete with galvanized steel earth plate electrode 600x600x 6mm buried directly in ground vertically to a depth not less then 2.25 mtr below normal ground level with top edge of the plate not less then 1.50 mtr below normal ground level connected to galvanized earth strip of size 32x6 mm thick by means of bolts, nuts, check nuts and washers complete up to and including test point, earthing pit, charcoal common salt, Earthing strip of 32x6 mm dia up to 7.5 mtr, 20 mm dia medium grade GI watering pipe, GI protection pipe 40 mm dia up to 7.5 mtr long, PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate, PCC pit cover including earth work complete all as shown in Electrical Plate No-5 of SSR-1991 (Part-I)
M & L for GI pipe, light grade laid in trenches / fixed to pole / wall for cable protection of following size 40 mm complete all as specified and as directed by Engineer-in-Charge.
M & L for GI pipe, light grade laid in trenches / fixed to pole / wall for cable protection of following size 50 mm complete all as specified and as directed by Engineer-in-Charge.
M & L for GI pipe light grade laid in trenches / fixed to pole / wall for cable protection of following size 80 mm complete all as specified and as directed by Engineer-in-Charge.
Dismantling of ACSR or AAC conductors, service feeder or distribution span complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacment sillicagel breather of transformer complete all as specified and as directed by Engineer-in-Charge.
M&L for GI strip of size 32x6 mm as earth continuity conductor or main earthing lead fixed to wall battens or recess or chases or buried in ground or drawn in conduit/pipe or fixed to pole or any other indicated situation for loop earthing etc complete all as specified and as directed by Engineer-in-Charge.
Taking out of existing stone sett for laying of LT cable underneath and making good the disturbed surface by relaying the stone sett complete all as specified and as directed by Engineer-in-Charge.
M&L for PCC (1:4:8) type D2 (using 40mm graded stone aggregate) as in foundation for electric pole etc complete all as specified and as directed by Engineer-in-Charge.
M & L for PCC (1:3:6) type C2 (using 40mm graded stone aggregate) in coping for electric poles or for stay assy etc complete all as specified and as directed by Engineer-in-Charge.
M&L for pre-stressed cement concrete pole, 9 mtr long cross section 102mm x 152mm at top and 102mm x 289mm at bottom, class 10 complying with requirements of IS-1678-1998 incliuding painting of poles with two coats of synthetic enamel paint over a coat of primer in alternate strip of 30 cm each in black and white colour upto 1.5 mtr height from top of PCC pedestal/copping of poles and numbering of poles with synthetic enamel paint white in 80mm high letters over 150mm x 230mm black base made from synthetic enamel paint and dismantling of old u/s pole and removing from site complete all as specified and as directed by Engineer-in-Charge. Note : Earth work and PCC work shall be measured and paid seperately.
Dismantling and demolition of existing LT poles 9 mtr long complete all as specified and as directed by Engineer-in-Charge.
M&L for LED post top 40 watt made in cast aluminium spigot housing with decorative clear opal acrylic diffuser and IP 65 protection complete including fixing arrangement complete all as specified and as directed by Engineer-in-Charge. Make : Bajaj Cat Pt No BGCT W4 LED WW or equivallent in Crompton/HPL/Havells.
S&F in replacement analogue time switch 3 mode complete all as specified and as directed by Engineer-in-Charge. Make : L&T Cat Pt No J6118B304 or equivallent make of Indo Asian/ HPL.
S&F in replacement contactor 40 Amp with standard coil voltage ML-415 Volt, 50 Hz complete all as specified and as directed by Engineer-in-Charge. Make :L & T or equivalent BCH, Havells, Crompton
S&F ACSR conductor of size as specified on LT/HT overhead line including all jumper connection and binding on insulator all as specified and directed by Engineer-in-Charge.
S&F Galvanised steel wire 4 mm dia for cradle hexagonal/ rectangular or running straight including taking down complete all as specified and directed by Engineer-in-Charge.
S&F pin type, porcelain, vitreous, brown insulator including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut, 65 mm dia and 100 mm height for 1100 volts grade incl taking down complete all as specified and directed by Engineer-in-Charge.
S&F Shackle type, Porcelain, vitreous, white, brown green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts, 90 mm dia and 75 mm height having GI straps 31x3 mm and for 12 mm dia bolt for 1100 Volts grade incl taking down complete all as specified and directed by Engineer-in-Charge.
M&L for taking down old LT panel of any type/size including dismentling all accessories and depositing to MES Store Yard complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing route indicator made out of precast RCC 1:2:4 type B1 using 20mm graded aggregate reinforced with 6 mm dia MS bars of semicircular shape 15 cm dia 10 cm thick duly engraved MES LT cable having RCC pillar of size 10 x 10 x 60 cm embedded 30 cm below ground level and 30 cm above ground level and painted with two coats of cherry colour of synthetic enamel paint above ground level including necessary excavation and earth work complete all as specified and directed by Engineer-in-Charge.
Supply and fixing junction box of size 200 x 160 x 98 mm outdoor type, IP-65, made out of polycorbanate with glass fiber reinforced suitable for 3 phase, 415 Volts, pole mounting consisting of aluminium bus bar strip 15 cm x 3mm, 4 Nos fixed on porcelain insulator and provision of incoming/outgoing cables with grommets, including in built 2 Amp MCB, SP, 10 KA complete all as specified and as directed by Engineer-in-charge.
Material and labour for boring under roads for crossing of UG cables complete all as specified and as directed by Engineer-in-charge.
Supply only for fixing under serial item No. 49 to 53 of BOQ in replacement MCCB of Capacity 250 Amp, 4 pole, 415 Volt, short circuit breaking capacity not less than 25 KA, therma;l magnetic trip, setting 80-100% lcs confirming to IEC-947, IS-13947, including thimbles, nuts, bolts, washers etc including making incoming, outgoing connections complete all as specified and as directed by Engineer-in-charge. Make : Legrand/L&T/Havells.
,----ditto--- All as per serial item No 46 above, but MCCB of capacity 200Amp, complete all as specified and directed by Engineer-in-Charge.
,----ditto--- All as per serial item No 46 above, but MCCB of capacity 100 Amp, complete all as specified and directed by Engineer-in-Charge.
M & L for repair, maintenance, out/indoor L T panel/feeder pillar box of size not exc 2.5mx1.8mx0.90m, 415Volts 3 phase with neutral, cubical type comprising of bus bar, incoming out going MCCB / switch gears, control measuring instruments, wiring, inter connection cables, bus, alley etc needs the following :- (a) Damage. broken, rusted MS sheet metal body with gas/arc welding in patches or complete doors body in or out side all as per site. (b) Repair, replacement of door hinges mild steel of 150 mm size and 4 Nos both side front and rear including locking system, providing hasp and staple 150 mm 2 Nos on both panels make it rigid, sliding bolt 300 mm 4 Nos, MS knobs, MS handles 150 mm 4 Nos, robust smooth openable all as directed. (c) Replacement or repair worn out MCCB/switch gears 3 or 4 pole as existing spn. (d) Replacement or repair of measuring or control instruments eg, ammeter, voltmeter, PF or frequency meter all as directed. (e) Replcement of phase indicating lamps (f) Repair of wiring with 1.5 Sqmm single core wire copper conductor. (g) Providing cable glands and aluminium cable lugs for incoming and out going cables.(h) Servicing and maint of bus bar and chamber. (j) preperation of old painted surface for painting. (k) M&L for spray painting with super enamel acylic paint of superior grade as approved and existing colour code complete all surfaces. (l) Writing letters or numbers of panel details and in or out going feeders with paint or self adhesive steakers all as specified and directed by Engineer-in-Charge/GE. (m) Danger notice plate as per IS. Note : (1) Following parts and accesories shall be measured and paid separately :- (a) MCCB's or other switch gears. (b) Volt meter, ammeter, PF meter indicating lamps. (c) M S Sheet of any specification. (2) Cost for all other parts and accesories deemed to be inclusive in quoted rates no extra shall be paid.
Repair, maintenance, material and labour for out/indooe L T panel/feeder pillar box of size not exc 2mx1.5mx0.75m, 415 volts 3 Phase with neutral cubical type comprising of bus bar, incoming out going MCCB / switch gears, control measuring instruments, wiring, inter connection cables, bus, alley etc needs following :- (a) Damage, broken, rusted MS sheet metal body with gas / arc welding in patches or complete doors body in or out side all as per site. (b) Repair, replacement of door hinges mild steel of 150 mm size and 4 Nos both side front and rear including locking system, providing hasp and staple 150 mm 2 Nos on both panels make it rigid, sliding bolt 300 mm 2 Nos, MS knobs, MS handles 150 mm 4 Nos , robust smooth openable all as directed. (c) Replacement or repair worn out MCCB / switch gears 3 or 4 pole as existing spn.(d) Replacement or repair of measuring or control instruments eg, ammeter, voltmeter, PF or frequency meter all as directed. (e) Replcement of phase indicating lamps.(f) Repair of wiring with 1.5 Sqm single core wire copper conductor.(g) Providing cable glands and aluminium cable lugs for incoming and out going cables.(h) Servicing and maint of bus bar and chamber. (j) Preperation of old painted surface for painting. (k) M&L for spray painting with super enamel acylic paint of superior grade as approved and existing colour code complete out side and inside surfaces.(l) Writing letters or numbers of panel details and in or out going feeders with paint or self adhesive steakers all as specified and directed by Engineer-in-Charge/GE.(m) Danger notice plate as per IS. Note : (1) following parts and accesories shall be measured and paid separately :- (a) MCCB's or other switch gears. (b) Volt meter,ammeter,PF meter indicating lamps. (c) MS Sheet of any specification. st for all other parts and accesories deemed to be inclusive in quoted rates no extra shall be paid.
Repair, maintenance, material and labour for out/indooe L T panel/feeder pillar box of size not exc 2mx1.5mx0.75m, 415 Volts 3 Phase with neutral cubical type comprising of bus bar, incoming out going MCCB/ switch gears, control measuring instruments, wiring, inter connection cables, bus, alley etc needs following :- (a) Damage, broken, rusted MS sheet metal body with gas / arc welding in patches or complete doors body in or out side all as per site. (b) Repair, replacement of door hinges mild steel of 100mm size and 4 numbers both side front and rear including locking system, providing hasp and staple 100 mm 2 Nos on both panels make it rigid, sliding bolt 250 mm 4 Nos, MS knobs, MS handles 100 mm 4 Nos robust smooth openable all as directed.(c) Replacement or repair worn out MCCB/switch gears 3 or 4 Pole as existing spn.(d) Replacement or repair of measuring or control instruments e,g, ammeter, voltmeter, PF or frequency meter all as directed.(e) Replcement of phase indicating lamps. (f) Repair of wiring with 1.5 sq mm single core wire copper conductor.(g) Providing cable glands and aluminium cable lugs for incoming and out going cables.(h) Servicing and maint of bus bar and chamber. (j) Preperation of old painted surface for painting. (k) M&L for spray painting with super enamel acylic paint of superior grade as approved and existing colour code complete out side and inside surfaces.(l) Writing letters or numbers of panel details and in or out going feeders with paint or self adhesive steakers complete all as specified and directed by Engineer-in-Incharge/GE. (m) Danger notice plate as per IS. Note : (1) Following parts and accesories shall be measured and paid separately :- (a) MCCB's or other switch gears.(b) Volt meter, ammeter, PF meter indicating lamps. (c) MS Sheet of any specification. (2) cost for all other parts and accesories demed to be inclusive in quoted rates no extra shall be paid.
,---Ditto--- all as per serial item no. 51 above, but of size 1.20 m x 0.90 m x 0.45 m complete all as specified and directed by Engineer-in-Charge.
,---Ditto--- all as per serial item no. 51 above, but of size 1.00 m x 0.75 m x 0.45 m complete all as specified and directed by Engineer-in-Charge.
Supply, fixing, connecting & testing in repairs under BOQ item No. 49 to 53, Power factor controller intellegent relay sigle CT sensing 8 steps, power requirement 3 VA and VA burden rating 15 VA, 230 VAC to automatically switch on the required amount of capacitors complete all as specified and directed by Engineer-in-Charge. Make : EPCOS, Schneider, L&T, Havells.
Supply only for fixing under item No. 49 to 53 of BOQ in repairs MCCB 3 Phase 415 Volts, 3 Pole, rating 63/100 Amps, 15/18 KA, Ics=100%Icu, adjustable overload setting and thermal release 80 to 100 %, complete duly fixed with fasteners and spreaders, copper / aluminium lugs / terminals with minor modification in existing LT panels any type and size complete all as specified and directed by Engineer-in-Charge. Make : Legrand, Schneider, L&T, Havells.
,--ditto--- All as per serial item no. 55 above, but rating 125 Amps, 25/30 KA, thermal release 100-125% complete all as specified and directed by Engineer-in-Charge. Make : Legrand, Schneider, L&T, Havells.
,--ditto--- All as per serial item no. 55 above, but rating 160 Amps, 25 KA, thermal release 125-160% complete all as specified and directed by Engineer-in-Charge. Make : Legrand, Schneider, L&T, Havells.
,--ditto--- All as per serial item no. 55 above, but rating 200 Amps, 36KA, thermal release 160-200% complete all as specified and directed by Engineer-in-Charge. Make : Legrand, Schneider, L&T, Havells.
,--ditto--- All as per serial item no. 55 above, but rating 250 Amps, 25 KA, thermal release 200-250% complete all as specified and directed by Engineer-in-Charge. Make : Legrand, Schneider, L&T, Havells.
,--ditto--- All as per serial item no. 55 above, but rating 320 Amps, 36 KA, electronic release 250-320%. complete all as specified and directed by Engineer-in-Charge.
,--ditto--- All as per serial item no. 55 above, but rating 400 Amps, 50 KA, electronic release 320-400%complete all as specified and directed by Engineer-in-Charge. Make : Legrand, Schneider, L&T, Havells.
,--ditto--- All as per serial item no. 55 above, but rating 630 Amps, 50 KA, electronic release range 250-630 ampscomplete all as specified and directed by Engineer-in-Charge. Make : Legrand, Schneider, L&T, Havells.
Supply only Spreader terminals tinned copper any shape 100 to 250 Amps rating complete duly fixed and connected with nut bolt and washers complete all as specified and directed by Engineer-in-Charge. Make : Legrand, L&T, Havells
Supply only Rotary handle for MCCB operation up to 125 Amps complete duly fixed in repairs complete all as specified and directed by Engineer-in-Charge. Note : To be fixed under item No. 49 to 53.
Supply only Rotary handle for MCCB operation, above 125 Amps up to 250 Amps complete duly fixed in repairs complete all as specified and directed by Engineer-in-Charge. Note : To be fixed under item No. 49 to 53.
Stailess steel enclosure for MCCB up to 125 Amps withinbuilt neutra link and cable gland suitable for arm cable up to 70 Sqmm 3.5 Core supply and fixed in repairs complete all as specified and directed by Engineer-in-Charge. Note : To be fixed under item No. 49 to 53. Make : Legrand, HPL, L&T, Havells
Supply only Stainless steel enclosure for MCCB, above 250 Amps upto 250 Amps with inbuilt neutra link and cable gland suitable for arm cable up to 185 Sqmm 3.5 Core supply and fixed in repairs complete all as specified and directed by Engineer-in-Charge. Make : Legrand, HPL, L&T, Havells
Supply only Multi function meter digital VAF plus PF meter accuracy class 1.0, aux supply 80-300 VAC, CT/-5A, flush mounting 96X96 mm size fixed in repaires complete all as specified and directed by Engineer-in-Charge. Make : AE, L &T, EPCOS, MECO, HPL.
Supply and fix in repairs indoor tape insulated ring type low tension current transformer accuracy class 1.0, rated burden 15 VA, CTR 100/5 Amps complete all as specified and directed by Engineer-in-Charge. Make : AE, Schneider, EPCOS, C&S
Supply and fix in repairs indoor tape insulated ring type low tension current transformer accuracy class 1.0, rated burden 15 VA, CTR 200/5 Amps complete all as specified and directed by Engineer-in-Charge. Make : AE, Schneider, EPCOS, C&S
Supply and fix in repairs indoor tape insulated ring type low tension current transformer accuracy class 1.0, rated burden 15 VA, CTR 300/5 Amps complete all as specified and directed by Engineer-in-Charge. Make : AE, Schneider, EPCOS, C&S.
Supply and fix in repairs indoor tape insulated ring type low tension current transformer accuracy class 1.0, rated burden 15 VA, CTR 400/5 Amps complete all as specified and directed by Engineer-in-Charge. Make : AE, Schneider, EPCOS, C&S
Supply and fix in repairs LED indicator lamp 16 mm dia, 240 VAC, in different colours red, yellow, blue, green or amber as required at site complete all as specified and directed by Engineer-in-Charge. Make : AE, L &T, MECO, HPL.
Supply and fix in replacement PVC copper wire mulistrand copper conductor single core required for panel wiring including copper terminals, of size 1.5 Sqmm complete connected and fixed complete all as specified and directed by Engineer-in-Charge. Make : Finolex, Havells, Plaza, Anchor.
Supply and fix in replacement PVC copper wire mulistrand copper conductor single core required for panel wiring including copper terminals, of size 4 Sqmm complete connected and fixed complete all as specified and directed by Engineer-in-Charge. Make : Finolex, Havells, Plaza, Anchor.
Supply and fix in replacement PVC copper wire mulistrand copper conductor single core required for panel wiring including copper terminals, of size 10 Sqmm complete connected and fixed complete all as specified and directed by Engineer-in-Charge. Make : Finolex, Havells, Plaza, Anchor.
Supply and fix in replacement PVC copper wire mulistrand copper conductor single core required for panel wiring including copper terminals, of size 16 Sqmm complete connected and fixed complete all as specified and directed by Engineer-in-Charge. Make : Finolex, Havells, Plaza, Anchor.
Surface dressing in soft soil including cutting and removing vegetation and bushes/shrubs on the surface not exceeding 15 cm in depth complete all as specified and directed by Engineer-in-Charge.
Taking out and removing stone aggregates / rocks upto depth not exceeding 50 cm of any size from the sub station area and depositing the same outside to a distance not exc.50 m from sub station for clearing complete all as specified and directed by Engineer-in-Charge.
M&L for sperading in layers not exc.15 cm thick stone aggregates (using 20 mm graded stone aggeragetes) in sub stations including levelling, hand punning and consolidating etc complete all as specified and directed by Engineer-in-charge
M & L continuous brick edging with width eqal to depth of brick, laid dry on edge in power sub station area with burnt clay bricks of old size complete all as specified and directed by Engineer-in-Charge.
Supply only to be fixed under item No. 49 to 53 of BOQ in repairs Mild Steel, plain, black sheet 1.6 mm thick in wall cladding, steel gates and similar work, cut to size, holes punched, including round headed screws, clout nails or rivets steel framing with plain 40 mm lap joints with riveted or welded for fabrication and making of LT electrical panel shutters , body repair etc complete all as specified and directed by Engineer-in-Charge.
Supply and fix in repairs Power contactor for street light automation application 3 Pole, 415 VAC, Coil Votage 230 VAC of rating 63 Amps, 1 No and 1 NC complete all as specified and directed by Engineer-in-Charge. Make : L&T, Schneider, BCH, EPCOS, Havells.
Overhauling/servicing of ACB 630/800 Amps, 415V of any make by carrying out following :- (a) Taking out ACB from the panel board. (b) Removal of dirt, dust & carbon particles by air blower. (c) Cleaning of all moving & fixed contacts of ACB with dry cloth & CRC solution and greasing of moving contacts & gears. (d) Checking and setting of ACB ON/OFF operation mechanism through TNC & push button. (e) Checking tightness of all control wires. (vi)Assembly of ACB in panel and testing complete.
Surface excavation in soft/loose soil for taking out sand and pabbles for and including removing vegetation and bushes not exceeding 30 cm in depth in sub stations complete all as specified and directed by Engineer-in-Charge.
M&L for sperading stone aggregates/hardcore of guage not exceeding 63mm, deposited, spread and levelled in layers n exc 15 cm thick over sand layer including proper levelling complete all as specified and directed by Engineer-in-Charge.
M & L for rough excavation in soft / loose soil not exceeding 1.5 deep and getting out for taking out LT cables from loop for proper connection and laying near LT panel/ feeder pillar box at sub stn complete all as specified and directed by Engineer-in-Charge.
S & F in repairs MCB tripple pole and neutral 415 Volts AC supply, 4 Pole, 63 Amps , 10 KA rating, C curve characteristics. complete connected acomplete all as specified and directed by Engineer-in-Charge. Make : Legrand, L&T, Schneider, Havells.
S & F in repairs MCB tripple pole and neutral 415 Volts AC supply, 4 Pole, 32 Amps , 10 KA rating, C curve characteristics. complete connected complete all as specified and directed by Engineer-in-Charge. Make : Legrand, L&T, Schneider, Havells.
S & F in repairs MCB triple pole, 415 Volts AC supply, 3 Pole, 63 Amps, 10 KA rating, C curve characteristics complete all as specified and directed by Engineer-in-Charge. Make : Legrand, L&T, Schneider, Havells
S & F in repairs MCB single pole and neutral 230 Volts AC supply, 2 Pole, 32 Amps , 10 KA rating, C curve characteristics complete all as specified and directed by Engineer-in-Charge. Make : Legrand, L&T, Schneider, Havells
S & F in repairs MCB single pole and neutral 230 Volts AC supply, 2 Pole, 16 Amps , 10 KA rating, C curve characteristicscomplete all as specified and directed by Engineer-in-Charge. Make : Legrand, L&T, Schneider, Havells. Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender, from total amount of Schedule 'A'/BOQ
Ganganagar Enterprises
AYUSH BUILDERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .