Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical Rejected due to not full fill the technical eligibility criteria |
| 4 | Rejected-Technical CW 545 SANJAY GANDHI TRANSPORT NAGAR NEW DELHI 110042 | NORTH | DELHI | 110042 | Rejected-Technical Rejected due to not full fill the technical eligibility criteria |
| 5 | Rejected-Technical | Rejected-Technical Rejected due to not full fill the technical eligibility criteria |
Tender Value
Refer Docs
EMD Value
₹23,500
Closing Date
9 Aug 2024, 12:00 pmClosed
Executive Engineer (EM) M-1
Chitra Vihar BP Station Laxmi Nagar Delhi-110092
Improvement of water supply system by replacement of Pump set No-01 and other allied works at Old Seemapuri BPS.
2024_DJB_260563_7
NIT No-12 EE (EM) M-I/ (24-25)
Open Tender
Electrical Works
Works
30 days
Chitra Vihar BP Station Laxmi Nagar Delhi-110092
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
A/c.50448339804
₹23,500
30 Aug 2024
3 Aug 2024
9 Aug 2024
3 Aug 2024
9 Aug 2024
3 Aug 2024
Dismantling of old sluice valves, NRV’s, Bends, MS pipe and 60 HP pump set by removing electric connection and remove the common base frame by cutting old nut bolt with the help of gas cutter and manual labour and demolish the RCC foundation by pneumatic hammer also removing the old cable and old starter.
S/o horizontal split casing pump with Bronze impeller & Neck Ring and Casing (CI), Shaft & Sleeve SS-410, coupled with TEFC IE2 rating motor mounted on suitable MS Base Frame with coupling & coupling guard. (1) Pump Duties-Discharge-270 cum/hr, Head-40 mtrs, size-150mm x125 mm Make : Kirloskar/Mather & Platt/DJB Approved make (2) 2) Motor-60 HP/45 KW, RPM-1450, make-KEC/CG/ABB/DJB Approved make
Supply of MS Pipe of size 150 mm of length 3 mtr both side flanged as per site requirement. Make:- Tata/Jindal/DJB Approved Make
Supply of MS Bend both side flanged of size 150mm of thickness 8mm as per site requirement
Supply of foot valve of size 150mm as per site requirement. Make: - Kirloskar/IVC/DJB Approved Make
Supply of CI sluice valve of size 150 mm dia, PN 1.0 make: - Kirloskar/IVC/DJB Approved Make
Supply of CI NRV of size 150 mm dia, PN 1.0 make-Kirloskar/IVC/DJB Approved Make
Supply of MS Reducer of Size 150mmX125mm of thickness 8mm as per site requirement
Supply of MS flange of size 150 mm dia as per site requirement
Supply of MS flange of size 125 mm dia as per site requirement
Supply of Nut Bolts and washer of good quality as per site requirement
Supply of rubber insertion sheet 75% synthetic Make: Jyoti/National
Making of RCC foundation of size 1.50 Mtr x 0.50 Mtr x 0.10 mtr by 1:1.5:3 concrete including providing fixing of 12 Nos. foundation bolt of size 25mm x 600mm i/c leveling & plastering.
Installation/fixing of above sluice valves, NRV’s, Bends, MS pipes and pump with proper alignment and also making of all electrical connections i/c thimbling & tapping & fitting of flanges with the help of welding, gas cutter & tri pod etc as required on full load i/c cartage and testing on full load etc.
Shakti Trading Co.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .