Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.4 LAccepted-AOC | ₹39.4 L Quoted ₹40.8 L | L1 | Accepted-AOC Lowest bid found in order |
| 2 | L2₹42.2 L+₹1.3 L (3.24%)Rejected-AOC | ₹42.2 L+₹1.3 L (3.24%) | L2 | Rejected-AOC Other than lowest bid |
| 3 | L3₹42.8 L+₹2.0 L (4.78%)Rejected-AOC | ₹42.8 L+₹2.0 L (4.78%) | L3 | Rejected-AOC Other than lowest bid |
| 4 | L4₹45.7 L+₹4.9 L (11.9%)Rejected-AOC | ₹45.7 L+₹4.9 L (11.9%) | L4 | Rejected-AOC Other than lowest bid |
| 5 | L5₹46.1 L+₹5.2 L (12.8%)Rejected-AOC | ₹46.1 L+₹5.2 L (12.8%) | L5 | Rejected-AOC Other than lowest bid |
Tender Value
Refer Docs
EMD Value
₹88,600
Closing Date
30 Sept 2024, 6:00 pmClosed
GE 874 EWS
GE 874 EWS C/O 56 APO
SPL REPAIR OF LT TRANSMISSION LINE AT KANZALWAN AND PROVN OF DG SETS AT RR MARATHA LI UNDER GE 874 EWS
2024_MES_668485_1
GE 874/EWS-58/2024-25
Open Tender
Civil Works
Works
120 days
Kupwara
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE 874 EWS C/O 56 APO
₹88,600
30 Nov 2024
31 Aug 2024
2 Oct 2024
31 Aug 2024
30 Sept 2024
17 Sept 2024
Amount
Dismantling of old unserviceable ACSR conductors from existing PCC/RCC/Steel poles complete all as specified and directed.
Dismantling of old unserviceable insulators any type & any size from pole (PCC/RCC/Steel) complete all as specified and directed.
Dismantling of Cross arms of MS channel or angle section etc complete all as specified and directed.
Dismantling stay assembly complete with stay wire complete all as specified and directed.
Dismantling GI earth wire/ old unserviceable guarding complete all as specified and directed.
Dismantling street light fitting of any size and type complete all as specified and directed.
Dismantling cable protection pipe of size 25/40/50/80 mm dia complete all as specified and directed.
Taking out old unserviceable service mains complete all as specified and directed.
Taking out old unserviceable/ broken street light bracket complete all as specified and directed.
Taking out old unserviceable PCC/steel pole complete all as specified and directed.
Supply and Laying, jointing and testing XLPE insulated armoured heavy duty electric cable with aluminium conductor ,1100 volts grade, cross section area 10 Sqmm 2 core complete laid in trenches, ducts or fix to pipe, on walls, poles complete all as specified and directed.
Supply and Laying, jointing and testing XLPE insulated armoured heavy duty electric cable with aluminium conductor ,1100 volts grade, cross section area 16 Sqmm 2 core complete laid in trenches, ducts or fix to pipe, on walls, poles complete all as specified and directed.
Supply and Laying, jointing and testing XLPE insulated armoured heavy duty electric cable with aluminium conductor ,1100 volts grade, cross section area 25 Sqmm 3.5 core complete laid in trenches, ducts or fix to pipe, on walls, poles complete all as specified and directed.
Supply and Laying, jointing and testing XLPE insulated armoured heavy duty electric cable with aluminium conductor ,1100 volts grade, cross section area 50 Sqmm 3.5 core complete laid in trenches, ducts or fix to pipe, on walls, poles complete all as specified and directed. Note for srl item No 11 to 14:- (a) Earth work shall be measured and paid separately.
Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m depth for foundation, laying of cables/pipes/poles etc., and getting out in soft/loose soil complete all as specified and directed.
All as per item No 15 above but exc 1.50 and n.exc 3.0m deep complete all as specified and directed
Returning filling in including spreading levelling watering and well ramming in layers not exceeding of 25 cm thick in soft/loose soil complete all as specified and directed
Removal of surplus soil as obtained from excavation to a distance not exc. 50 Mtr and depositing where directed at a level not exc. 1.5 Mtr above the starting point complete all as specified and directed.
Supply and laying dry river sand for cable cushioning in trenches to required width at bottom and top of cable including spreading levelling watering and consolidation complete all as specified and directed by Engineer-in-charge. Note:-Punned thickness only shall be measured and paid.
Supply and laying old size brick covering with width equal to length of brick as the mechanical protection to cable with well burnt sub class 'B' laid in trenches flat complete all as specified and directed by Engineer-in-charge.
Supply and fixing steel tubes, light grade, galvanised 40 mm dia with all fittings laid in trenches complete all as specified and directed.
Supply and fixing steel tubes, light grade, galvanised 50 mm dia with all fittings laid in trenches complete all as specified and directed.
Supply and fixing street light Engineering plastic one piece moulding control box with locking arrangement made out of HDPE and FI clamp 25 x 3mm complete of dimensions in CM +/-10%(34x28x13) including MCB SP 6 Amp 240 Volts complete with 02 Nos aluminium busbar or terminal two Nos (2P-R/Y/B and N) of rating 63 amps for single phase and neutral on porcelain based insulators complete all as specified and directed.
Supply, erecting and fixing the true vertical position, steel tubular swaged pole(410 SP-31),09 mtr long, complete with cast iron base plate, pole cap/final taper plug ,bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole ,including two coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with one coat of red oxide primer and two coats of aluminium paint complete all as specified and directed.(Numbering of the poles shall be done with synthetic enamelled painted letter of shape & size as directed. Note:-(a) Cost of numbering of pole shall be deemed to included in unit rate.(b) Excavation, Earth work and PCC foundation will be measured and paid for separately.
S & F GI bracket made out of GI pipe light grade of size 50/40/32 mm 1.2 m long cut to length bend to the required shape and 02 Nos mounting flat iron clamps size 40mm x 6mm, 04 Nos hexagonal bolts 10mm dia 100mm long with nuts and washers complete all as specified and directed.
Supply and fixing LED street light luminaries 70/72 Watt having shall be made of single piece Aluminium Die cast with powder coated in RAL-7032 shade with heat distribution fins on housing with UV stabilized toughened glass cover and should have secondary lens on each LED for better light distribution .The system luminaire efficacy should be > 110 LM/W with high power LED,.LED driver shall be potted and BIS certified with efficiency > 85 % frequency 50 HZ, Operating voltage range 120V-270V,current not more than 0.320 Amp, PF 0.95, THD (I) < 10 %, supported with 5 KV internal and 10 KV external SPD, Humidity 10% to 90 % RH, working temperature - 20⁰ C to 50⁰ C lige expectancy of LED should be 50000 burning hours with minimum 70 % initial lumen maintained, CRI >70
M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded stone aggregate) in foundation of PCC poles/struts as specified including necessary form work complete all as specified & directed.
M&L for plain cement concrete 1:3:6 type C-2 (using 40mm graded stone aggregate) in foundation of stay assembly etc including necessary form work complete all as specified & directed.
M&L for plain cement concrete 1:2:4 type B-1 (using 20mm graded stone aggregate) for coping around poles, including necessary form work finishing even and smooth without using extra cement complete all as specified & directed.
Supply and fixing 1100 volts grade heavy duty cable with PVC insulated solid/stranded copper conductor served with an inner sheathing of PVC tape and overall PVC sheathed of size 1.5 sqmm 3 core suitable for LED security light for pole box to street light fitting with connector and thimble, nut & bolt and washer etc., complete all as specified and directed.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), LT Panel/Bus Bar, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium busbar of Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & back side opening type, with aprons for cable entry, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) lock with 2 keys, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size including the provision of space to accommodate the under mentioned items. The scope of work includes the following:-
(a) Aluminium bus bar cap 200 Amp-04 Nos
(b) MCCB four with breaking capacity 25 or 35 KA,40 Amp - 01 No
(e) RYB neon indicating lamp set of three- 01
Notes: (i) Rates are deemed to be inclusive of PCC platform of suitable size and 45cm height and 4 Nos legs of 40mmx40mmx6mm and 60 cm in height for fixing the panel (ii) Danger Notice board in Hindi and English of size 20cmx 15cm shall be fixed on the panel (iii) Contractor provided powder coated finish paint on panel and test certificate.
M & L for Earthing complete with and including galvanised steel earth plate electrode 60×60cm×6mm thick surrounded by mixture of charcoal and salt in alternate layers, buried directly in ground vertically in a pit of depth not less than 2.25 metres deep below ground level with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron or steel earth lead wire 4.0mm dia (No 8 SWG) by means of bolts, nuts, check nuts and washers of galvanised iron or steel earth wire protected by galvanised steel pipe 15 mm bore (light grade) and connected to main switch or main control board or junction box all as shown in electrical plate No. 3 of SSR 2009 (Pt-I) & including necessary excavation and earth work complete all as specified and directed. Note :- The rate also include charcoal and salt in alternate layers, 20mm bore GI Pipe (light grade) for watering, protection pipe funnel, wire mesh, PCC 1:2:4 type B1 chamber in cement concrete 50mm thick precast RCC cover duly reinforced with XPM (weight not less than 3kg/sqm) and CI frame etc and including provision of test point, connecting to test point and testing on completion etc complete.
M & L for Earthing complete with galvanised steel earth plate electrode of size 60×60cm×6mm thick surrounded by mixture of charcoal and salt in alternate layers, buried directly in ground vertically in a pit of depth not less than 2.25 metres deep below ground level with top edge of the plate not less than 1.5 metres below normal ground level, connected to equipment by using GI strips of size 32 x 6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No.5 of MES schedule and connected to earthing test point all as specified and directed including earth pit of size 30cm x 30cm x 45 cm made of PCC 1:3:6 and PCC 1:2:4 cover, funnel, GI Tubing etc & testing on completion. Note :- The unit rate includes the cost of excavation & earth work in any type of soil, charcoal and salt in alternate layers, 20mm bore GI Pipe (med grade) for watering 40mm GI protection pipe (light grade) funnel, wire mesh, lugs, PCC 1:2:4 type B1 chamber in cement concrete 50mm thick precast RCC M-25 (design mix) cover duly reinforced with XPM (weight not less than 3kg/sqm) and CI frame etc and including provision of test point, connecting to test point and testing on completion etc complete all as specified. The unit rate also include earthing lead and protection pipe upto 7.5mtr from top of earth plate.
Supply and fixing of on load changeover switch 415 volt in sheet metal enclosure 4 pole of capacity 100,160& 250 Amp (as required) complete all as specified and directed.
M&L for Painting to LT poles, 9 mtr with cross arms, bracing and clamps with one coat of synthetic enamel paint over one coat of red oxide primer including scrapping the old paint carefully to make smoothen complete and painting strips of red and black from foot of pole upto 5 feet each strip of 30 cm height all as specified and directed.
Supply, fabricate , fixing structural mild steel RS joist , channel angle iron, flat iron and brackets etc for fabrication of cross arms, bracing supports clamps including D clamps, eye hook and back plate etc fabricated from structural steel section including nuts , bolts, washers, welding (cold and hot ) drilling holes for bolts, bend to any shape or size as indicated and directed , inclusive of one primer coat and two coats of aluminium paint after preparation of surfaces complete all as specified and directed.
M&L in replacement of Shackle type, porcelain, vitreous, white, brown or green insulators for working pressure 1100 volts grade, 90 mm dia 75 mm height including galvanized mild steel straps of 31 x 3 mm size, 12 mm dia insulator bolts, washers and nuts complete all as specified and directed.
M&L in replacement of Pin type porcelain vitreous white brown or green insulator including one galvanized mild steel spindle, two galvanized iron, washers and one galvanized iron nut, 100 mm height, 65 mm dia for 1100-volt grade all as specified.
M&L in replacement of ACSR conductor of any size and any type including stretching, fixing and binding to insulator on OH LT line service feeders all as specified including aluminium binding wire or aluminium tapes complete all as specified. This item includes all consumables (such as binding wire and replacement insulators and cross arms, etc., for replacement of damaged ones found after/ during replacement process).
Re stretching of LT /HT ACSR conductor and GI wire of any size and on any type of poles carrying upto six conductors in a span including disconnecting from insulator and rewinding to insulator after stretching with and including aluminium wire including re-fixing/re-adjusting line spans, line separators, cross arms on poles complete all as specified and directed.
M & L for stay assembly of stay rod of diameter 20 mm complete with accessories as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately) complete all as specified and as directed.
M & L for hot dip galvanized stay strands of grade I, 7 Nos wires construction, wire diameter 4 mm, nominal strand diameter 12 mm, heavy zinc coating complete all as specified and as directed.
S & F galvanised mild steel wire 3.15 mm or 4 mm dia in overhead lines complete all as specified and as directed.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), LT Panel/Bus Bar, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium busbar of Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) lock with 2 keys, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size including the provision of space to accommodate the under mentioned items. The scope of work includes the following: -
(a) Aluminium bus bar cap 200 Amp-04 Nos
(b) MCCB four pole with breaking capacity 25 or 35 KA,63 Amp - 01 No
(e) RYB neon indicating lamp set of three- 01
Notes: (i) Rates are deemed to be inclusive of PCC platform of suitable size and 45cm height and 4 Nos legs of 40mmx40mmx6mm and 60 cm in height for fixing the panel (iii) Danger Notice board in Hindi and English of size 20cmx 15cm shall be fixed on the panel (vi) Contractor provided powder coated finish paint on panel and test certificate.
Supply and installation of 7.5 KVA 1 Phase Silent DG Set comprising of (CPCB IV+ NORMS COMPLIANCE developing 10.74 BHP @ 1500 RPM 7.5 KVA Alternator rated at 1 phase, 230 Volts , 50 Hz: 0.8 p.f @ 1500 RPM both mounted , and aligned on a common MS base frame complete with MS Fuel Tank, Manual Control Panel Residential Exhaust Silencer ,AVM pads fitted on base frame ,1 No. 12 Volts DC Battery, Battery Leads, 1st Fill of Lube Oil all housed in Sound proof Acoustic Enclosure.
Supply and installation of 5.5 KVA Ultra Silent Recoil plus Self petrol generator complete all as specified and as directed.
Note :- The rate of Generator quoted by contractor shall be as per following specification with one year service /replace warranty
Type : Ultra Silent & Compact
Engine Type :GCAGD
Starting System :Recoil/ Electric Starter
Fuel : Petrol
Rated Output Power :5.5 kva
Max output :7.0
Displacement :389 cm³
Continuous Running Hours :6.5 hrs.
ignition system :Full Transistor Ignition
Noise Level :85.2 DB
Voltage :230V
Note Specification should be of following
Fuel System :Electronically Controlled Fuel Injection system
Oil Alert System :Yes
Fuel Tank 19.2 Liters
Oil capacity: 1.1liter
Fuel consumption : 1200ml/ hr
Frequency :50 HZ
Rated Current :23.9 A
Dimensions :1261x700x722 mm
Weight : 123.2 Kg
RATHER BROTHERS (BID ID -3108536)
M/S MOHD MAQBOOL RATHER (BID ID -3104739)
M/s Lal Enterprises (BID ID -3122142)
patriotic builders (BID ID -3108636)
M/S AB AHAD RATHER (BID ID -3099169)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .