Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.1 LAccepted-AOC 5 31 EWS PREETAM NAGAR ALLAHABAD 211011 | ALLAHABAD | ALLAHABAD | UTTAR PRADESH | 211011 | ₹18.1 L Quoted ₹19.0 L | L1 | Accepted-AOC AoC being lowest |
| 2 | L2₹20.4 LRejected-Finance 47A C3 OLD DAMU NAGAR PULIAKULAM COIMBATORE 641 045 | COIMBATORE | COIMBATORE | TAMIL NADU | 641045 | ₹20.4 L | L2 | Rejected-Finance Other than lowest bidder |
| 3 | L3₹23.7 LRejected-Finance 28 A 4A DHARAMVIL MARG SULEM SARAI PRAYAGRAJ PIN 211011 UP | PRAYAGRAJ | PRAYAGRAJ | UTTAR PRADESH | 211011 | ₹23.7 L | L3 | Rejected-Finance Other than lowest bidder |
| 4 | Rejected-Technical MEGHDOOT HOTTEL MALL ROAD RANIKHET UTTARAKHAND | - | - | Rejected-Technical Not in appropriate category i.e. c(i). |
| Sl No | Description | Qty | Unit | M/S vibhuti enterprises L1 | Krishna Enterprises L2 | M/S Amar Enterprises L3 |
|---|---|---|---|---|---|---|
| 1.00 | Overhauling & servicing of window /Split/tower/cassete type Air Conditioners up to 4.0 Ton capacity of any make and carry out of following tasks at different location of different establishment including taking down the AC (if required) from existing location, refixing / commissioning and testing the same after overhauling complete including the following :-
(a) Inspection taking down, opening (dismantling), washing the condensor and cooling coil complete with water by fixing indoor pvc jacket as required and cleaning with air blower and testing complete. (b) Checking / examine operation of condensor, blower motor, cooling coil and checking the air circulation to ensure complete movement of working part trouble free. (c) Inspection of leakage in system and removal obstruction if any. (d) Inspecting all electrical connection and remove if any defects (e) Top up Refrigerent gas if required.
Note: Replacement of new parts/worn out parts in lieu of unserviceable/burn out part shall be measured and paid separately as supply only items of sch A. | 180 | Each Job | 75 ₹13,500 | 500 ₹90,000 | 350 ₹63,000 |
| 2.00Supply only the following spare parts for up to 5.5 ton capacity of Tower/cassate/window/ Split type AC any make & any model. | ||||||
| 2.01 | (i) Air Filter Make and model-as per existing. | 2 | Set of two | 70 ₹140 | 10 ₹20 | 150 ₹300 |
| 2.02 | (ii) Starting relay Make-Totaline/Epcos/CLASSIC/Whirlpool. | 10 | Each | 100 ₹1,000 | 55 ₹550 | 200 ₹2,000 |
| 2.03 | (iii) Starting capacitor 120-150 mfd Make- Totaline / Epcos / DVM/Whirlpool. | 10 | Each | 50 ₹500 | 125 ₹1,250 | 200 ₹2,000 |
| 2.04 | (iv) Starting capacitor 100-120 mfd. Make- Totaline / Epcos //DVM/Whirlpool. | 12 | Each | 50 ₹600 | 123 ₹1,476 | 200 ₹2,400 |
| 2.05 | (v) Running capacitor 40-60 mfd. Make- Totaline/ Epcos/ DVM/Whirlpool. | 50 | Each | 50 ₹2,500 | 103 ₹5,150 | 180 ₹9,000 |
| 2.06 | (vi) Running capacitor 30-36 mfd. Make- Totaline / Epcos /DVM/Whirlpool. | 20 | Each | 50 ₹1,000 | 150 ₹3,000 | 200 ₹4,000 |
| 2.07 | (vii) Running capacitor 4-6 mfd. Make- Totaline/ Epcos/Whirlpool. | 20 | Each | 50 ₹1,000 | 50 ₹1,000 | 70 ₹1,400 |
| 2.08 | (viii) Thermostate switch Make as per existing. | 2 | Each | 50 ₹100 | 50 ₹100 | 200 ₹400 |
Tender Value
₹35.8 L
EMD Value
₹71,600
Closing Date
7 Jan 2026, 6:00 pmClosed
GE (AF) Bamrauli
GE (AF) Bamrauli
REPAIR MAINT OF AC ANY TYPE WATER COOLER DESERT COOLER REFRIGERATOR DEEP FREEZER INTERNAL ELECTRIFICATION ELECTRICAL FITTINGS AND FIXTURES AND MISC EM WORKS AT AF STN BAMRAULI UNDER GE AF BAMRAULI
2025_MES_744037_1
9018/E8
Open Tender
Civil Works - Others
180 days
GE (AF) Bamrauli
Please refer tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Bamrauli
₹71,600
Yes
25 Apr 2026
11 Dec 2025
9 Jan 2026
11 Dec 2025
7 Jan 2026
26 Dec 2025
Overhauling & servicing of window /Split/tower/cassete type Air Conditioners up to 4.0 Ton capacity of any make and carry out of following tasks at different location of different establishment including taking down the AC (if required) from existing location, refixing / commissioning and testing the same after overhauling complete including the following :- (a) Inspection taking down, opening (dismantling), washing the condensor and cooling coil complete with water by fixing indoor pvc jacket as required and cleaning with air blower and testing complete. (b) Checking / examine operation of condensor, blower motor, cooling coil and checking the air circulation to ensure complete movement of working part trouble free. (c) Inspection of leakage in system and removal obstruction if any. (d) Inspecting all electrical connection and remove if any defects (e) Top up Refrigerent gas if required. Note: Replacement of new parts/worn out parts in lieu of unserviceable/burn out part shall be measured and paid separately as supply only items of sch A.
Supply only the following spare parts for up to 5.5 ton capacity of Tower/cassate/window/ Split type AC any make & any model.
(i) Air Filter Make and model-as per existing.
(ii) Starting relay Make-Totaline/Epcos/CLASSIC/Whirlpool.
(iii) Starting capacitor 120-150 mfd Make- Totaline / Epcos / DVM/Whirlpool.
(iv) Starting capacitor 100-120 mfd. Make- Totaline / Epcos //DVM/Whirlpool.
(v) Running capacitor 40-60 mfd. Make- Totaline/ Epcos/ DVM/Whirlpool.
(vi) Running capacitor 30-36 mfd. Make- Totaline / Epcos /DVM/Whirlpool.
(vii) Running capacitor 4-6 mfd. Make- Totaline/ Epcos/Whirlpool.
(viii) Thermostate switch Make as per existing.
(ix) Propeller fan suitable for window/split type AC Make- As per existing.
(x) Cooling Coil Make- as per existing.
(xi) Condensor coil Make- as per existing.
(xiii) Outer cover duly painted for Window/split AC.
S & F of 9 W LED Bulbs warm white, high energy efficiency LED luminaries to be fitted on existing holders 240 V,50 Hz, complete all as specified and directed.
M & L in replacement for only twin core PVC insulated unarmoured cable 4 Sqmm Flat 1100 Volts with Aluminium multi stranded conductor, complete all as specified and directed by Engr-in-Charge.
M & L in replacement for only twin core PVC insulated unarmoured cable 6 Sqmm Flat 1100 Volts with Aluminium multi stranded conductor, complete all as specified and directed by Engr-in-Charge.
(xii) MCB SP 20-32 Amps ‘C’ Series ,10KA, 240 volts SP Make : Havells/HPL/Legrand.
(xvi) Front grill for split/window AC Make as per existing.
(xix) Wiring kit with thimbles.
(xx) Power Contactors 240 volts AC 50HZ 16-25 Amps range.
(xxi) Power contactor 415V AC, 50 Hz 20-32 Amps range.
(xxii) Isolator 4 pole 63 Amps 415 Volt.
(xxiii) Overload protector suitable for compressor as per existing.
(xxiv) Blower for indoor unit/window AC as per existing.
S & F of Sheet metal enclosure in/on wall with socket plug top and MCB single pole neutral enclsoure with 2 pin + earth plug and socket complete with one single pole MCB of 32 amps 230 volts of repturing capacity of 10 KA and making good the disturbed surface with existing colour matching, complete all as specified and directed. Make- Legrand / Havells / schnider.
Removing the burnt/defective sealed compressor unit any type of any make from Air Conditioner window type up to 2.0 ton capacity by cutting of suction and discharge lines unscrewing the foundation nuts & bolts etc, supply and fixing of new sealed compressor unit of suitable make as existing by connecting suction and discharge lines with filling of refrigerant gas (in quoted rate), welding/brazing work and tightening foundation nuts & bolts including etc., complete all as specified and directed. Note:- (a) Capillary, drier, copper tubing etc are inclusive in unit rate. (b) New compressors will be purchased from authorised dealer only.
All as per Sr item No. 4.00 above but for air conditioner split type 1.5 ton capacity.
All as per Sr item No. 4.00 above but for air conditioner split type 2.0 ton capacity.
All as per Sr item No. 4.00 above but for air conditioner split type 3.0 /4.0 ton capacity.
M&L for replacement of damaged copper tubing of dia 5/8 inch including insulation with heavy duty foam and brazing work in Split Air conditioners for discharge and suction of gas betweem indoor and outdoor unit complete of sizes as per requirement and specified.
M&L for replacement of damaged copper tubing of dia 3/8 inch including insulation with heavy duty foam and brazing work in Split Air conditioners for discharge and suction of gas betweem indoor and outdoor unit complete of sizes as per requirement and specified.
M&L for replacement of damaged copper tubing of dia 1/2 inch including insulation with heavy duty foam and brazing work in Split Air conditioners for discharge and suction of gas betweem indoor and outdoor unit complete of sizes as per requirement and specified.
M&L for replacement of damaged copper tubing of dia 1/4 inch including insulation with heavy duty foam and brazing work in Split Air conditioners for discharge and suction of gas betweem indoor and outdoor unit complete of sizes as per requirement and specified.
M&L for replacement of damaged insulation with heavy duty foam for copper tubing of split air conditioners, complete all as specified and directed.
S&F in replacement of PVC drain pipes of size 15 mm from indoor unit to exist point as per design including accessories clmps fastners, complete all as specified and as directed by Engineer-in-charge.
Supply and fixing of medium class insulated Hard PVC Drain Water pipe of 20 mm dia with all fittings ie elbow, tee, bend etc., complete all as specified and directed.
Repair to Air conditioner Window/Split type upto 2.0 ton to capacity by testing the leakage in system by filling of Nitrogen gas upto suitable pressure and repairing of leakage with brazing work, cleaning and flushing out the complete system, replacing of drier/filter if required, making the complete system leak proof, vacuuming the system and charging Refrigernt gas (M410a/R134a/R-22) as existing and testing etc, complete all as specified & directed. Note :(a) Drier/filter, capillary and copper tubing are inclusive in unit rate.(b) Contractor should be responsible if leakage of refrigerent gas after repair on completing job and done same job without extra payment.
Repair to Air conditioner Split type 3.0 ton to 4.0 ton capacity by testing the leakage in system by filling of Nitrogen gas upto suitable pressure and repairing of leakage with brazing work, cleaning and flushing out the complete system, replacing of drier/filter if required, making the complete system leak proof, vacuuming the system and charging Refrigernt gas (M410a/R32/R-22) as existing and testing etc, complete all as specified & directed. Note :(a) Drier/filter, capillary and copper tubing are inclusive in unit rate.
Supply and replacement blower Motor 1/5 or 1/6 HP 230V AC, 50 Hz suitable for Air conditioner window type upto 2.0 ton capacity as per existing model, complete all as specified and directed.
Supply and replacement blower Motor 0.2/0.25 HP for Air conditioner split type of capacity 1.5 ton/2.0 ton/3.0 ton/4.0 ton as per existing model complete as directed and specified.
Repair and fixing blower Motor of split type /window type Air Conditioners of any make and any capacity for making air conditioner serviciable, complete all as directed and specified.
Supply and replacement Condensor Motor (outdoor motor) for split type Air conditioner as per existing model and any capacity, complete as directed and specified.
Repair and fixing Condensor Motor (outdoor motor) for split type Air conditioner as per existing model of any make and any capacity for making air conditioner serviciable, complete all as directed and specified.
Repair and fixing Printed Circuit Board of split type /window type Air Conditioners of any make and any capacity for making air conditioner serviciable, complete all as directed and specified.
Supply and replacement Printed Circuit Board as per existing model to repair to split type/window type Air Conditioners of any make and type of any capacity any, complete all as specified and directed. Make- Voltas/Carrier/toshiba.
(a) Supply and replacement Inverter Type Printed Circuit Board(for indoor and outdoor unit complete) of any make and type of air conditioner split inverter type of any make and type (variable speed compressor) as per existing model and capacity up to 2.0 ton, complete all as specified and directed. Make: Carrier (X power gold)/Electrolux/LG/HITACHI.
Per Point
Repair and fixing Inverter Type Printed Circuit Board of split type Air Conditioners (with variable speed compressor) of any make and any capacity for making air conditioner serviciable, complete all as directed and specified.
Supply and replacement for wireless remote control unit for split/window type airconditioner as per existing model, complete all as specified and directed. Make Carrier (Duracool)/Carrier (X power gold)/LG/VOLTAS.
M&L for Shifting and refixing of split type AC (Indoor and Outdoor units) of any make and any type after servicing and charging of gas (M410a/R134a/R-22/r32) by testing the leakage in system by filling of Nitrogen gas upto 300 PSIG and repairing of leaking spot/joints with gas welding work, cleaning and flushing out the complete system with gas, supply and replacing of drier/filter, making the complete system leak proof, vacuuming the system as existing and testing etc, complete all as specified & directed. Note :(a) Dismantling and refixing of split AC are including in quoted rate. (b)Drier capillary,copper tubing,refrigernt gas,Insulation and LDPE pipe are inclusive in quoted rate.(c) making hole and filling the hole on wall with PCC (1:2:4) type BO (Using 12.5mm graded stone aggregade, 15mm thick rendereing in cement mortar (1:3) good the disturbed surface with existing colour matching are inclusive in quoted rate.
M&L for Shifting and refixing of window AC of any make and any type after servicing and charging of gas (M410a/R134a/R-22/R32) by testing the leakage in system by filling of Nitrogen gas upto 300 PSIG and repairing of leaking spot/joints with gas welding work, cleaning and flushing out the complete system with gas, supply and replacing of drier/filter, making the complete system leak proof, vacuuming the system as existing and testing etc, complete all as specified & directed. Note :(a) Dismantling and refixing of window AC are including in quoted rate. (b)Drier capillary,copper tubing,refrigernt gas and LDPE pipe are inclusive in quoted rate.(c) Making hole on wall and good the disturbed surface with existing colour matching are inclusive in quoted rate.
M&L for attending day to day complaints and rectifying faults like decarbonizing connections in the AC Box, , any burning due to over loading in AC and restoring connection of AC with wire or thimbles,attending and rectifying faults related to AC like drain water leakage ,filter cleanig,remote setting etc and related to VRF based Air conditioner upto24/28 Ton capacity incl Sunday & Holidays, complete all as directed by Engineer-in-Charge. Note : (i) All T&P required shall be provided by contractor including ladders of any size as per requirement at site. (iii) Minor items like machine screw, plastic clamps, insulation tape, nails, flexible pipe, thimbles, lugs for contactor, etc shall deemed to be included in the unit rate. (iv) The major items replaced during repairs shall be measured and paid under respective items of Sch 'A'.
DESERT COOLER
Taking down/out desert cooler of any make and capacity from various locations and M & L for complete cleaning washing and descaling scraping down and removing existing paint, preparation of surface and painting the entire/complete body of desert cooler, inside and outside, by sprayer with two coats of approved synthetic enamel paint and writing SM/ MES no. with black synthetic enamel paint by complete all as specified & directed EIC.
M&L for desert cooler’s cabinet, locally fabricated with three side panels (front, top and tank) and vertical members made out plain galvanised iron sheet with double diversion grills and grill box suitable for 18” sweep fan and making holes for connections with and including fixing arrangements such as 4 way PVC distributor, PVC pipe 3 to 4 Mtrs for spraying water, wood wool pads, electrical wiring for fan & pump controlled separately with 5 Amps piano type switch etc, complete all as specified and directed.
(xiii) Three pin metalic socket outlet suitable for sheet metal enclosure Make : Havells/HPL/Legrand.
S&F in replacement of ready made wood wool pad with Meshes of size as required at site of 15 mm thickness, made out of chicken wire mesh filled with fine quality wood wool and stitched with GI wire for desert cooler of any make & size complete all as specified and directed.
S&F in replacment of Desert cooler fan motor operating on SP 230 Volts, 50 HZ AC, 150 W,1400 rpm,copper winding with fan blade and mounting Kit complete after and including taking out existing fan motor all as directed. Make : Khaitan or crompton or Equivalent
S&F of PVC sheathed and PVC insulated 3 core cable, 1.5 Sqmm copper conductor of Make: Plaza/ Gloster / Havells / Kalinga complete all as specified and directed.
S & F of angle stop valve of PTMT any colour high pressure screwed for iron pipe and fixed, as specified and directed by Engr-in-Charge.
M & L for repair or rewinding with super enameled copper winding wire of exhaust fan motor of desert cooler any type any make including all minor parts like bush, bearing etc, all as specified and directed by Engr-in-Charge.
S & F of ball valves (Float Valve) high pressure PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe, as specified and directed by Engr-in-Charge.
S & F of Clamp for kit fan motor as per site requirement with nut, bolt & washers, complete all as specified and directed.
S & F of Piano type switch 5 Amps of Make: Anchor / Cona / Kay.
S & F of PVC water distributor, (Set of four way and two way).
S & F of plug top 5amp 3 pin type Make:- Anchor/Standerd/Kay.
Note :- Credit shown in credit schedule of tender document shall be considered by the tenderer while quoting the rates of various items. The same shall be recovered from various payment to contractor before handing over old material.
M & L for painting of ceiling fans , in situ with synthetic enamel paint by spraying including filling cavities with filler, one or more coat to achieve even and smooth surface after cleaning all dust etc.and endorsement of fan no. with black synthetic enamel pain
Per RM
Supply and fix in repair PVC gang box ISI marked three module for mounting one 15 amp socket & switch, complete all as specified and as directed. Make plaza/Anchor as approved.
t, complete all as specified and directed.
S & F of PVC connections 15mm size with PTMT nuts of length 300 mm (PTMT fitting shall be of approved makes), complete all as specified and directed.
Supply and fixing in repair plywood grade BWR type BB of thickness 4.0 mm fixed with screws to timber frame work, complete all as specified and directed.
WATER COOLER
Dismantling of electric connection and water connection of water cooler opening the condensor fan motor blade, electrical accessories and spare parts of system carefully servicing of serviceable parts replacement of U/S parts oiling of fan motor etc reassembling all spare parts incl rewiring of internal connection of water cooler, testing and commissioning, complete all as specified and directed. Note : New spares replaced against Worn out or unserviceable spare parts shall be measured and paid separately as supply only under respective item of this sch.
Removing burnt/defective sealed compressor unit of any make from water cooler cap 40 Ltrs/hr by cutting of suction and discharge li
(xiv) Three pin metallic plug top suitable for sheet metal enclsoure Make : Havells/HPL/Legrand.
(xv) PVC flexible insulated cable multi-strand copper conductor 3/4 core of size 2.5 sq mm Make- Kalinga / Plaza / Gloster/Polycab.
nes and unscrewing the foundation nuts & bolts etc, supply and fixing new sealed compressor unit by tightening the foundation nuts and bolts and connecting suction and dischrage line with gas welding work including supply and filling of refrigerent gas R-22 or as per existing at site in suitable quantity as per manufacturers instruction, complete all as specified and directed.
M&L for replacement of Rubber hose pipe of 20 mm bore with clips for outlet tray of water cooler approximately 1.5 Mtr long, complete all as specified and directed.
M&L for replacement of PVC sheet rubber bedding and lock of top cover of water cooler by screwing/welding MS sheet of top cover, complete all as specified and directed.
M&L for making the system leak proof and charging of gas R-22 / R-134a or existing at site as required in water cooler of any capacity including replacement of drier and capillary tube and testing on load, complete all as specified and directed.
M&L for scraping old painted surface of water cooler any capacity and painting with two coats of synthetic enameled paint including writing SM/MES No with black paint with minimum 25 mm size of letters, complete all as specified and directed.
M&L for replacement of condenser fan motor of SP, 230V, cap 1/35 HP with fan blade, complete all as specified and directed.
M&L for replacement of condenser fan motor of SP, 230V, cap 1/8 HP with fan blade, complete all as specified and directed.
Supply and replacement of 15mm bore Push cock/lift cock brass chromium plated, complete all as specified and directed.
Supply and replacement of flexible PVC pipe 40mm/50mm/60mm as per requirement for the drainage of waste water of water coolers, complete all as specified and directed by Engnr-in charge.
Detection and rectification of leakage of storage tank of water cooler by brazing soldering/welding as required at site or at work shop testing for leak proof complete all as directed. Note : (a) Nipple adaptor if required deemed to be included in unit rate. (b) Push cock, float valve etc if required will be measured and paid separately. (c) Changing of rubber/plastic packing is incl in unit rate.
Taking out the drain tray with PVC pipe of water cooler, electroplating (chromium plating) of drain tray after repair by denting/painting and including replacement of new PVC pipe of suitable size and length and refixing back all as directed.
Dismantling of electric connection and water connection of water purifier (RO), electrical accessories and spare parts of system carefully servicing of serviceable parts and replacement of U/S parts reassembling all spare parts incl rewiring of internal connection, testing and commissioning, complete all as specified and directed. Note : Minor parts like conection pvc pipe,overflow ,waterflow switch etc are included in quoted rate.
Supply only the following items for water cooler :-
(a) Starting capacitor 60/80 mfd
(b) Running capacitor 10 mfd
(c) Thermostat
(d) Relay
Supply and fixing in replacement of Recess mounted complact vertical round shaped down light LED 2 watt suitable for low ceiling height, complete all as specified and directed.
(e) Over load protector
(g) Strainer/filter drum type/pen type
(h) Door gasket
REFRIGERATORS
Repair maint of refrigerator of any capacity, cleaning of indoor panel, servicing of serviceable parts, replacement of worn out parts, testing for smooth functioning of refrigerator, complete all as specified and directed. Note : Replaced worn out part shall be measured and paid separately as supply only.
M&L for detection of leakage in refregeration of capacity 260L/310L and repairing thoroughly to ensure the complete system leak proof and charging of refrigerant gas as per existing on site with appropriate quality incl necessary brazing, welding, testing and commissioning, complete all as directed by Engr-in-Charge. Note : Replacement of Capillary, drier and copper tubing/filter strainer are inclusive in unit rate.
Dismantling of unserviceable sealed compressor unit from refrigerator and replacing with new compressor as existing capacity and charging of refrigerant gas of appropriate qty and testing for smooth functioning, complete all as specified and directed. Note : (a) New compressor will be purchased from authorised dealer only. (b) Capillary, drier and additional copper tubing are included in unit rate. (c) Old compressor either cut open or sealed to be replaced with new one.
Supply only the following item for refrigerators as per sample :-
(a) Thermostat switch as per sample
(b) Relay box type as per sample
(c) Door gasket as per sample
(d) Cooling coil as per sample
(e) Condensing coil as per sample
(f) Freezer door any make
(g) door switch
(h) Bulb Holder
(j) Door Handle
(k) Lamp
(l) Door Lock
(n) bottle holder shelves any size
(o) Vegetable tray with cover
(p) Main shelves
(q) water filter for samsung Refrigertor
(h) Printed circuit board for invertor type Refrigertor of capacity upto 320 Ltrs for existing model
DEEP FREEZER
M&L for Repair maint of deep freezer of any capacity, cleaning of indoor panel, servicing of serviceable parts, replacement of worn out parts, testing for smooth functioning of deep freezer, complete all as specified and directed. Note : Replaced worn out part shall be measured and paid separately as supply only.
M&L for making the system leak proof and charging of gas as required in Deep Freezer of any make of capacity up to 400Ltr including replacement of drier and capillary tubing and testing on load, complete all as specified and directed.
Supply and replacing Cable 3 core flexible heavy duty copper cable of size 2.5 sqmm for AC , Water Cooler ,Stabilizer etc, complete all as specified and directed.
Removing burnt/defective sealed compressor unit of any make from DEEP FREEZER of any capacity by cutting of suction and discharge lines and unscrewing the foundation nuts & bolts etc, supply and fixing new sealed compressor unit by tightening the foundation nuts and bolts and connecting suction and dischrage line with gas welding work including supply and filling of refrigerent gas R-22 in suitable quantity as per manufacturers instruction, complete all as specified and directed.
M&L for replacement of PVC sheet rubber bedding and lock of top cover of deep freezer of any type and by screwing/welding MS sheet of top cover, complete all as specified and directed.
M&L for replacement of condenser fan motor of SP, 230V, cap 1/50 HP with fan blade for refrigerator or deep freezer, complete all as specified and directed.
Supply only the following item for Deep Freezer as per sample :-
(a) Thermostatic switch for any capacity.
(b) Relay /capictor any type for any capacity as per sample.
(c) Door gasket as per sample.
(d) Cooling coil as per sample.
(e) Condensing coil as per sample.
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc.
M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through new PVC concealed conduit mediem grade, ISI marked and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty, fabricated branded modular metal flush box duly make embossed, concealed in walls with suitable modular inner and outer plate for housing switches , socket outlet and fan regulators etc, complete all as specified and as directed for the followings:-
(a) One light, fan, bell point controlled by one switch.
(b) One 3 pin switch socket outlet point 5 Amps on independent board.
S&F of water lifting pump submersible type upto 1.5 Meter head,40 Watt Suitable for 220-240V, AC 50 Hz 1 Phase and including taking out existing defective pump from Desert Coolers, complete all as specified & as directed. Make : Khaitan or equivalent in list of Makes as approved.
(c) One 3 pin switch socket outlet point 5 Amps on same board with other switch.
M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through new PVC concealed conduit mediem grade, ISI marked and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty, fabricated branded modular metal flush box duly make embossed, concealed in walls with suitable modular inner and outer plate for housing switches , socket outlet and fan regulators etc, complete all as specified and as directed for the followings:-
(a) One light, fan, bell point controlled by one switch.
(b) One 3 pin switch socket outlet point 5 Amps on independent board.
All as per item No 50.00 above but water cooler of capacity 60 Ltrs/hr
M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through new PVC casing caping mediem grade, ISI marked and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth co
ntinuty, fabricated branded modular metal flush box duly make embossed, concealed in walls with suitable modular inner and outer plate for housing switches , socket outlet and fan regulators etc, complete all as specified and as directed for the followings:-
Supply and fix in repair Switch piano 6 amps, single pole, one way, 230 volts
Supply and fix in repair Switch piano 16 amps, single pole, one way 230 volts
Supply and fix in repair Socket outlet 6 Amp 2pin & 3 pin, flush type
Supply and fix in repair Socket out let, 16 amp and 6 amp, flush type
Supply and fix in repair Electronic fan regulator 5 step 230 volts,switch type
Supply and fix in repair Electronic fan regulator 5 step 230 volts, socket size
Supply and fix in replacement Switch socket combination 2 IN 1 3 PIN 6/16 Amp 220 Volt flush type.
Supply and fix in repair Lamp holder, insulated body, with back plate 230 Volt suitable for batten fittings.
Supply and fix in repair Capacitor 230 volt, 1 Mfd all as specified and directed by Engr-in-Charge.
Supply and fix in repair Switch modular type, 230 volts, single pole, one way, 10 Amp, one module.
Supply and fix in repair Switch modular type, 230 volts, single pole, one way, 16 Amp one module.
Supply and fix in repair Socket out let 5 pin, 10 Amp, 230 volts modular type.
Set of 3
Supply and fix in repair Socket out let 5 pin, 10 amp & 20 amp, 230 volts modular type.
S & F in repair Modular Fan step regulator, 120W - 2 module, complete all as specified and directed.
Supply & fix in replacement PVC box comprising of switch socket combination multi - purpose 5 pin, 6/16 Amp box type, complete all as specified and as directed.
Supply & fix in replacement PVC box comprising of switch socket combination multi - purpose 3 pin, 6 Amp box type, complete all as specified and as directed.
Supply and fix in replacement calling bell ding dong type 220 volt 50 Htz, complete all as specified and as directed.
Supply and fix in repair LED batten luminaire surface mounted, 4 feet system wattage of 20 Watts, > 2200 systems lumen outputwith lifetime of 50000 burning including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed, complete all as specified and as directed.
Supply and fix in repair LED batten luminaire surface mounted, 2 feet system wattage of 10 Watts, > 1000 systems lumen outputwith lifetime of 50000 burning including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed, complete all as specified and as directed.
Supply and fix in repair 2x2 LED fitting recess mounting flate panel 36 watt, down light 240 volt 50 Htz 150 luumen/watt comprising driver locking arrangement prewired completely.
All as per item No 50.00 above but water cooler of capacity 150 Ltrs/hr. Note (For item No 50 to 52) :- (i) Cost of transportation from store to factory and back shall be deemed to be included in the quoted rates. (ii) GI fitting damaged while taking out/fixing back water coolers shall be replaced by the contractor at his own cost. (iii) All new compressor shall be purchased from authorised dealer only. (iv) Capillary, drier, filter strainer are inclusive in unit rate.
Supply and fix adore LED lamp 3 star rating 5 watt lumen out put 500 Lm, complete all as specified and as directed by Engr-in-Charge.
Supply and fix LED Tube rod fittings 4 feet long single side connection, complete all as specified and directed.
S & F of GI Tubing 'Medium grade' of 15 mm size as per existing with screwed socket joints, togather with all tube fitting to connect desert coolar with water pipe line, complete all as specified and directed by Eng-in-Charge. NOTE: Cost of bands, Tees, reducing tees ,ends ,elbow, connectors,caps etc and other minor parts not specifically mentioned shall also be replaced where required for proper functioning shall be demanded to be included in the quoted rate. No extra payment shall be made to the contractor on this account.
(b) Supply and replacement Inverter Type Printed Circuit Board(for indoor and outdoor unit complete) VRF based air conditioner split inverter type as per existing model and capacity 24/28HP/Ton ton, complete all as specified and directed. Make:Carrier
S & F of ceiling rose surface backlite 65x50mm 3 terminals, complete all as specified and directed.
S & F of bed side lamp LED 3 Watt, all as specified and directed by Engr in Charge. Make Philipis Model No 48042/30/3 and eqvt particular specification.
Supply and fixing decorative wall light 2x 20 Watt TOR Compete all as specified and directed by Engr-in-Charge. Make Philips model No 3430/11C/86 and eqvt Specification particulars make Havells/Bajaj
Supply and fixing in replacement of Recess mounted complact vertical round shaped down light LED 15 watt suitable for low ceiling height, complete all as specified and as directed.
S & F in replacement surface mounted, suare LED down light fitting12 watts with die cast aluminium housing and system wattage of 12W, including connecting up with PVC sheathed 3 core 1.5 Sqmm copper conductor flexible wire fixed complete all as specified and directed.
S&F in replacement PVC cable copper conductor multi strandrad flexible 23/76 twin core and making connections from ceiling rose to fan, complete all as specified and as directed.
Supply and fix in replacement 1.5 Sqmm FR PVC insulated stranded copper conductor cable 1100 volts grade, complete all as specified and as directed.
Supply and fix in replacement 2.5 Sqmm FR PVC insulated stranded copper conductor cable 1100 volts grade, complete all as specified and as directed.
Supply and fix in replacement 4.0 Sqmm FR PVC insulated stranded copper conductor cable 1100 volts grade, complete all as specified and as directed.
All as per item No 79.02 here in before but with copper conductor cable for one 3 pin socket outlet, 15 amp independent, with cable 2.5 Sqmm size.
Supply and fix in replacement 6.0 Sqmm FR PVC insulated stranded copper conductor cable 1100 volts grade, complete all as specified and as directed.
Supply and fix in repair PVC gang box ISI marked three module for mounting one 5 amp socket & switch, complete all as specified and as directed.
Supply and fix in repair PVC gang box ISI marked six module for mounting two 5 amp socket & two switch, complete all as specified and as directed.
Supply and fix in repair PVC gang box ISI marked 9 module for mounting three 5 amp socket & three switch, complete all as specified and as directed.
Supply and fix in replacement white cover plate with frame three module for modular switches and sockets, complete all as specified and directed.
Supply and fix in replacement white cover plate with frame six module for modular switches and sockets, complete all as specified and directed.
Supply and fix in replacement white cover plate with frame twelve module for modular switches and sockets, complete all as specified and directed.
Supply and fix metal flush box three module 1.6 mm for mounting modular switches and sockets, complete all as specified and directed.
Supply and fix metal flush box six module 1.6 mm for mounting modular switches and sockets, complete all as specified and directed.
Supply and fix metal flush box twelve module 1.6 mm for mounting modular switches and sockets, complete all as specified and directed.
Supply and fix bulkhead fitting enviornmental friendly, ultra modern, energy saving, surface mounted, decorative oval bulkhead edgelit LED luminaire comprising of highbrightness LEDs of 10 watt, complete all as specified and as directed.
Sub main wiring with 2 run of single core PVC insulated and PVC Unsheathed, multistranded copper condutor of nominal area 6 sqmm FRLS, 1100 Volts grade cable drawn into and including rigid non metalic PVC Conduit of including all fittings and one run of PVC insulated and PVC unsheathed, multistranded copper conductor of nominal area 6 sqmm FRLS 1100 volts grade cable continuous earth wire of green colour code, complete all as specified and as directed. Note:- (a) Two runs of 6.0 sqmm cable and one run of 6 Sqmm cable as earth lead with conduit shall be measured as one unit length for payment. (b) Quoted rate shall deem to be included cost of cutting chasses in wall for concealling conduit and making good to match with existing finish.
Sub main wiring with 2 run of single core PVC insulated and PVC Unsheathed, multistranded copper condutor of nominal area 4 sqmm FRLS, 1100 Volts grade cable drawn into and including rigid non metalic PVC Conduit of including all fittings and one run of PVC insulated and PVC unsheathed, multistranded copper conductor of nominal area 4 sqmm FRLS 1100 volts grade cable continuous earth wire of green colour code, complete all as specified and as directed. Note:- (a) Two runs of 4.0 sqmm cable and one run of 4 Sqmm cable as earth lead with conduit shall be measured as one unit length for payment. (b) Quoted rate shall deem to be included cost of cutting chasses in wall for concealling conduit and making good to match with existing finish.
Supply anf fix of Factory made sheet metal enclosure distribution boards, (protection class IP-65) double door, vertiical type suitable for mounting isolator fixing MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, SP and N, 12 ways, 240 volts, Make Legrand/Hager/siemense,complete all as specified and as directed. Note : MCBs shall be measured and paid for separately under respective item of this schedule.
Supply anf fix of Factory made
sheet metal enclosure distribution boards, (protection class IP-65) double door, vertiical type suitable for mounting isolator fixing MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, SP and N, 8 ways, 240 volts, complete all as specified and as directed.
M&L for opening up the winding of ceiling fan 1200 mm any make and type and rewinding with super enamelled copper winding wire with suitable gauge winding ,wraping insulating material, insertion and varnishing well including drying, complete all as specified and as directed. Testing of the ceiling fan after refixing in position to the entire satisfaction of Engr-in-Charge.
M&L for opening up the winding of ceiling fan any 1400 mm any make and type and rewinding with super enamelled copper winding wire with suitable gauge winding ,wraping insulating material, insertion and varnishing well including drying, complete all as specified and as directed. Testing of the ceiling fan after refixing in position to the entire satisfaction of Engr-in-Charge.
Supply only ball bearing No. 6201.
Supply only ball bearing No. 6202.
S&F in replacement capacitor of 2.5 MFD.
S&F in replacement capacitor 3.15 MFD.
All as per item 81.02 here in before but with copper conductor cable for one 3 pin socket outlet, 15 amp independent, with cable 2.5 Sqmm size.
Supply & fising rubber reel suitable for ceiling fan of any capacity, complete all as specified and as directed.
S&F Ceiling fan blade suitable for 1200mm sweep of any make with suitable size as per site requirement, complete all as specified and directed. (As per sample)
Supply & Fixing worn out shaft, beyond economical repair of existing ceiling fan any make, type or size as per original one ceiling/exhaust fan, complete all as specified and as directed.
Supply and fixing of MCCB, four pole, 415 Volt ,100 Amp rating, 10 KA ultimate breaking capacity fixed in DBs catered herein before, complete all as specified and directed.
Supply and fixing of MCB, tripple pole and neutral, 415 volts, 32 to 63 Amps rating, 10KA, "C" series fixed in DBs catered herein before, complete all as specified and directed.
Supply and fix in replacement MCB, SP, 6 to 32 Amp rating, 230 volt, 10 KA, 'C' series fixed in DBs catered herein before, complete all as specified and directed.
Supply and fix in replacement MCB, SP, 230 volts, 35 to 63 Amp rating, 10 KA, C series fixed in DBs catered herein before, complete all as specified and directed.
Supply and fix MCB, single pole and neutral, 230 volts, 40 to 63 Amp rating, 'C' series fixed in DBs catered here-in-before, complete all as specified and directed.
Supply and fix in connecting and testing LED street light 30 watt 6000k new generation energy saving and enviornmental friendly long life versatile pressure die cast aluminium housing IP-66 roadway luminaries with high power LED as light source and electronic driver complete with connection and accessories for fixing with with including grade 40mm dia GI pipe as bracket in appropriate length complete including taking down old light fitting, complete all as specified and directed.
S&F in repair Fresh air fan motor of capacity 1/6 HP 230 volts, 50 Hz, AC supply suitable for 250/200 mm size Fresh air fan as per sample, complete all as specified and directed.
Supply and fixing in replacement of Recess mounted complact vertical round shaped down light LED 5 watt suitable for low ceiling height, complete all as specified and directed.
S & F of show case led lamp light 3 Watt, complete all as specified and directed.
(f) Wiring Kit
Supply and fix wall mounted decorative fancy type bedroom light LED type with frosted glass mounted on metalic frame with holder including 12 watt LED bulb Philips cat part No-45617 or equivelent in list of make as approved.
M & L for tape roll, complete all as specified and directed by Engr-in-Charge.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.49 MB
Tender.pdf
Tender Documents • 1.36 MB
BOQ_833121.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid