Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.8 LAccepted-AOC 24 C GOABAGAN LANE KOLKATA 700006 WEST BENGAL | KOLKATA | KOLKATA | WEST BENGAL | 700006 | ₹28.8 L | L1 | Accepted-AOC AOC_Issued |
| 2 | L2₹31.9 LRejected-Finance | ₹31.9 L | L2 | Rejected-Finance that the bid is not L1 |
| 3 | L3₹33.1 LRejected-Finance | ₹33.1 L | L3 | Rejected-Finance that the bid is not L1 |
| 4 | Rejected-Technical | - | - | Rejected-Technical Due to absense of updated contractor license |
| Sl No | Description | Qty | Unit | ALPHA ELECTRICALS L1 | ASCO L2 | BANERJEE CONCERN L3 |
|---|---|---|---|---|---|---|
| 1.00SUB-HEAD --DISTRIBUTION WIRING Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (KEI/MESCAB/GLOSTER) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. | ||||||
| 2.00 | 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish. [only switch board concealed]
2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC
Average run 8 mtr | 471 | Pt. | 985 ₹4.6 L | 925 ₹4.4 L | 1,171 ₹5.5 L |
| 3.00 | Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (KEI/MESCAB/GLOSTER) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box andmending good the damages to original finish
i) On Board | 59 | Nos. | 60 ₹3,540 | 73 ₹4,307 | 92 ₹5,428 |
| 3.10 | Average run 6 mtr for separate 5 A | 40 | Nos. | 675 ₹27,000 | 762 ₹30,480 | 898 ₹35,920 |
| 4.00 | Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board | 24 | Nos. | 198 ₹4,752 | 192 ₹4,608 | 238 ₹5,712 |
| 5.00 | Supplying & Fixing sheet metal inspection box (16 SWG) of
the following sizes flushed in wall by housing the same after
cutting brick wall incl. making earthing attachment, painting
and mending good damages to building works
i) 200 mm x 150 mm x 65 mm | 12 | Nos. | 280 ₹3,360 | 239 ₹2,868 | 292 ₹3,504 |
| 5.10 | ii) 150 mm x 100 mm x 65 mm | 30 | Nos. | 210 ₹6,300 | 165 ₹4,950 | 197 ₹5,910 |
| 6.00 | Distribution wiring in 1.1 KV single core stranded 'FR'
PVC insulated & unsheathed copper wire (KEI/MESCAB/GLOSTER) incl S & F 20/32 mm size PVC rigid conduit 'FR' (Precision-LMS/AKG make) incl. necy. fittings as required
i) 3 x 22/0.3 (1.5 sqmm) (Separate plug+ Compound light) | 950 | Mtrs. | 108 ₹1.0 L | 127 ₹1.2 L | 140 ₹1.3 L |
| 6.10 | ii) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC for power point | 700 | Mtrs. | 125 ₹87,500 | 133 ₹93,100 | 164 ₹1.1 L |
| 6.20 | iii) 2x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC ( only for TPN to common SPNDB for common area) | 100 | Mtrs. | 205 ₹20,500 | 227 ₹22,700 | 266 ₹26,600 |
Tender Value
Refer Docs
EMD Value
₹71,800
Closing Date
28 Dec 2023, 1:00 pmClosed
EEI,KNHED, PW Dte
KIT Building Annex, 4thFloor,P-16, India Exch. Place Extn., Kolkata -700073
Electrical Rewiring, Renovation work i.c.w. Civil Renovation Work of New Menials Quarter at ID and BG Hospital, Kolkata
2023_WBPWD_620013_1
WBPWD/EE/KNHED/NIQ-122/23-24
Open Tender
ELECTRICAL WORKS ORG
30 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹71,800
28 Apr 2026
11 Dec 2023
2 Jan 2024
15 Dec 2023
28 Dec 2023
15 Dec 2023
Amount
SUB-HEAD --DISTRIBUTION WIRING Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (KEI/MESCAB/GLOSTER) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl.
175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish. [only switch board concealed] 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC Average run 8 mtr
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (KEI/MESCAB/GLOSTER) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box andmending good the damages to original finish i) On Board
Average run 6 mtr for separate 5 A
Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works i) 200 mm x 150 mm x 65 mm
ii) 150 mm x 100 mm x 65 mm
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (KEI/MESCAB/GLOSTER) incl S & F 20/32 mm size PVC rigid conduit 'FR' (Precision-LMS/AKG make) incl. necy. fittings as required i) 3 x 22/0.3 (1.5 sqmm) (Separate plug+ Compound light)
ii) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC for power point
iii) 2x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC ( only for TPN to common SPNDB for common area)
iv) 4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC(VTPN To HTPN for common area)
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. i) 1.5 sq.mm
ii) 2.5 sq mm
iii) 4 sqmm
iv) 6 sqmm
v) 10 sq.mm
SUB-HEAD --PLUGS & SOCKETS etc. Supply & Fixing 240 V, 2 nos. 6A plug socket with separate 2 nos. 6 A Piano key type switch, indicator & 16A kit-kat flush type fuse (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 200 x150 x 65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required
Supplying & Fixing Industrial Plug & Socket board with 240 V, 20A, SPN & Earth Plug socket & 20A top incl. S&F 20 A SP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and ncecessary conection.( For INVERTER Connection of each Quarter)
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex coverand making necessary connections as required
SUB-HEAD --MCBDB/PBDB/MAIN SWITCHES etc. Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment ( Make: Havells/L&T/SIEMENS/Legrand) 4 way Enclosure ( For distribution of Common area Power)
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment( Make: Havells/L& T/SIEMENS/Legrand) 4 way Enclosure ( For distribution of Common area Power)
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment..( Make: Havells/L& T/SIEMENS/Legrand) 2+8 way Enclosure ( For Common area Power & Each Quarter)
Supplying and fixing 2 way MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection 125 A ( Make: Havells/L& T/SIEMENS/Legrand)
Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts boltsetc incl. provision for earthing attachment i) 6 way ( vertical)
ii) 8 way(Horizontal)
iii) 6 way ( Horzontal)
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection(L&T/legrand) i) 32A DP MCB (At Ground Floor -Incomming For Quarter DB & Electrical Room & SPNDB)
ii) 63 A TP MCB ( VTPN Outgoing)
iii) 63A FP Isolator (TPN at common Area)
iv) 6-32 A SP
S & Fixing 1/2 inch thick Hylum Sheet of Size 3 mtr x 3 mtr-
SUB-HEAD SUPPLY OF LUMINARIES etc. Supply & fixing of Single LED tube light fittings 100lm/watt. (Make :- Crompton -IGP161LT8-16.1 x T 8/ Equivalent product of Philips/Wipro ). incl S&D LTT8-20 4 ft LED tube lamp with Alluminium heat sink (Make:- Philips/ Crompton/ Wipro) ( for Quarter)
Supply & fixing of Single LED tube light fittings 100lm/watt. (Make :- Crompton -IGP161LT8-16.1 x T 8/ Equivalent product of Philips/Wipro ). incl S&D LTT8-20 4 ft LED tube lamp with Alluminium heat sink (Make:- Philips/ Crompton/ Wipro)Fixing the fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports incl. S&F EI conduit, ball socket/socket type ceiling plate and connecting the length of PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm) flexible copper wire of 1.10 mt. length.(For Common area)
Supply & fixing of 9W LED Lamp (Make: Philips/crompton/wipro)
Supply & Fixing angular batten holder (Anchor) on 75mm dia PVC round block / round bakelite on wall/ceiling
Supply & fixing of 220V,1200mm Sweep ceiling fans complete with safety wire and all accessories having the following specification. 1200mm, 240V, AC (Crompton HS/Orient /Usha )
Supply & fixing of Exhaust fans complete with all accessories having the following specification. 9"( 225mm ) Speed 920 RPM( Toilet & Kitchen ) (EPC/Crompton)
Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991)
Supply & Fixing 240V, Modular step type fan regulator (Step type) (Anchor/Legrand) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) 23 cm Exhaust fan (9")For Al
SUB-HEAD CABLE/WIRE etc. Cutting channel of 31 mm x 31 mm size on masonry wall incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire fish wire incl. mending good damages to building works. a) 13 mm dia 3 mm thick polythene pipe without earth continuity wire.
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.With 25x25x3mm angle iron support 200x50x1.25mm (18SWG)
Supplying 1.1 KV grade 2 core 10 sqmm armoured Alminium XLPE cable (Make: MESCAB/KEI/Polycab/Havells/Gloster)
Supplying 1.1 KV grade 2 core 6 sqmm armoured Alminium XLPE cable (Make: MESCAB/KEI/Polycab/Havells/Gloster)
Supplying 1.1 KV grade 4 core 35 sqmm armoured Alminium XLPE cable (Make: MESCAB/KEI/Polycab/Havells/Gloster)
Laying only Cable upto 50 sqmm through existing GI Pipe for single, 2 core 10 Sqmm cable with 2 x 10 swg GI wire
Laying of 2 core 10 sq.mm cable as below, on existing Cable Tray and binding with suitable size GI wire.
Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting(2 core 6 sq.mm + 2 core 10 sq.mm)
Laying of one cable of 4 core 35 sq.mm through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand
S&F of compression type gland complete with brass gland, rubber rings for dust & moisture proof entry of PVC armoured cables as below as per G.S. i) 2 Core 10 sq.mm
ii) 4 Core 35 sq.mm
Finishing the ends of following cables by crimping method including S/F dowells solderless sockets, tapes and jointing materials etc. as per G.S. i) 4 Core 10 mm²
ii) 4 Core 35 mm²
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required 100 mm dia(ISI-M)
Supply of Cable Supplying of one number 1.1 KV Grade XLPE insulated and PVC sheathed aluminium conductor cable ( Armoured ) (Make:Polycab/Havells/Gloster) 4 Core 240 mm² ( Feeder near G Block to feeder No 4)
Laying of cable Laying of one No. cable above 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed.
S&F of compression type gland complete with brass gland, rubber rings for dust & moisture proof entry of PVC armoured cables as below as per G.S. 4 Core 240 mm²
Finishing the ends of following cables by crimping method including S/F dowells solderless sockets, tapes and jointing materials etc. as per G.S. 4 Core 240 mm²
SUB-HEAD Compound Light + MISCELLANEOUS etc. S & Installation of 3" dia 2 Mtr Long heavy gauge GI Pipe having MS sole plate welded with drilled hole at botton of the pole to be istalled on roof of building incl. providing CC (6:3:1) muffing 450x450x600 mm in size or equivalent size of cylindrical muffing above ground level around the pole base complete with 3 mm thick neatly finished cement plaster all round after dismantling the unserviceable muffing if any S & F 50 mm dia 2 mtr long detachable type GI single arm bracket suitable for the pole head. The arm bracet shall be properly welded with 15 mm thick stifner plate of pole sleeve for strengthening inl properly fixing arrangement with the pole by bolt,nut washer as per direction of EIC
Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint.The loop box will be fixed 1 mtr height from the ground level with the help of 2 nos 1 long 25 mm dia gi pipe for loop in loop out of the cable
SITC of road lighting luminaire ( IP 66 ) with peanut lens and high power LED and to ensure uniform distribution, higher spacing between poles and maintenance free system and s suitable for use with 230Volt 50Hz AC supply etc as required with inbluilt SPD ( Make - Crompton Model No. CRP414 LED180 57-SL-GL-NSG/equivalent product of philips/Wipro in all respect )
Supply & fixing of Timer control panel on wall comprising of :- i) 415V AC 20 A power contactor - 3 nos ( 1 NO), ii)Analog type Timer 24 hours capacity, 230V, AC supply-1 no. iii ) 415V, 32A TPN MCB, C type-1 no. iv) 230V AC toggle switch, single pole Double throw, 6A, 230V. v) 415V, 32A, 4 way terminal-3 nos. vi) with necy interconnection with 1.5 sqmm cu flexible wire ( Finolex / Havells )including ferrule marking & socketing within the 12 way SPNDB NCB enclosure box. Make - Cabtree / ABB / Seimens
Shifting the existing pannel incoming C/O-63A, Outgoing-63A-3nos,100A-1no with different type main switch ,cables disconnection and temporary power supply .(Principal Ante roon to Outdoor wall)
Withdrawing different size cable on wall (4C 70 sqmm, 4Cx35sqmm, 4Cx 25sqmm,) from ante room to outdoor wall for connection to panel.
Relaying different size cables on wall (4C 70 sqmm, 4Cx35sqmm, 4Cx 25sqmm,) for connection to panel at new place.
Rewiring of existing panel and changing internal wiring replace with copper as per requirmend and servicing.
Foundation(3ft*2ft approx) & installation of panel with necessary connection of cables with proper arragement.
Supply and fIxing of 100 A C/O inplace of existing C/O 63A ON LOAD C/O with metal enclosure make-L&T.
Supplying and Laying concealed on wall of 1.1 KV grade armoured Alminium XLPE cable on wall as per G.S. (Make: Gloster/Havells/Nicco) i) 4 Core 70 sqmm
ii) 4 core 35 sqmm
iii) 4 Core 25sqmm
Supply and fixing compression type gland complete with brass gland brass ring and rubber ring for dust and moisture proof entry of XLPE/PVC armoured cable.(for new and existing cable) i) 70 sqmm
ii) 35 sqmm
iii) 25 sqmm
Finishing the end of following XLPE/PVC armoured cables bycrimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials(for new and existing cable) i) 70 sqmm 4core
ii) 35 sqmm 4core
iii) 25 sqmm 4core
Distn. Wiring in 1.1 Kv gr. Single core stranded ‘FR’ PVC insulated & unsheathed cu. wire (Havells / KEI / Finolex) in 20/32/40 mm size PVC rigid conduit ‘FR (precession) incl. necy. Fitting as reqd. a) 4 x25 sqmm + 1x 16 sqmm for ECC
Finishing end of copper wire and PVC/Al cable of the fol;owing sizes by crimping method as per GS 25 sqmm
Straigh through Jointing of cable by compoundjointing kit including S&F ferrul, tapes and jointing materials (Brand approved by EIC) i) 4 core 70 sqmm
ii) 4 core 50 sqmm
Fixing only old existnig 100A main switch in wall with fastner and bolts.
SUB-HEAD EARTHING etc. Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages Solid GI wire No. 4 SWG
Cost of Dismantaling the old wiring, pipes, switch board, damaged parts during Civil renovation & take back from site.(Considering Less Cost of only Scrap Material).Electrical equipments of good condition should be submit in sectional store)
(Rate should be quotated including all taxes and duties and GST)
BANERJEE CONCERN
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.43 MB
2911.pdf
Tender Documents • 1.46 MB
BOQ_1321297.xls
BOQ • 0.29 MB
suspension.pdf
Additional Documents • 2.91 MB
Download all tender documents and submit your bid