EEE-II/SSZ
OFFICE OF THE Ex. ENGINEER (ELECT)-II 2 nd Floor Technical Laboratory Near NH-24 Ghazipur Delhi
TPD aerobic drum compost plant along with Sieving Trommel, shredding
2023_MCD_158573_1
EEE-II/SSZ/2023-24/6.2
Open Tender
Electrical Works
Item Rate
120 days
work
Please refer to tender documents
4 documents required · 4 mandatory
₹590
₹4,803
10 Jul 2023
23 Jun 2023
3 Jul 2023
23 Jun 2023
30 Jun 2023
23 Jun 2023
Amount
1.8.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
121.1:Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
1.12:Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
1.14.2:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.4:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire
1.23.1:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.5/6 amps switch
1.23.4:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.3 pin 5/6 amp socket outlet
1.30:Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required.
1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
1.50.1:Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep
2.4.1:Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 way (4 + 12), Double door
2.10.1:Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.17:Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32amps 415 volts "C" curve TP MCB complete with connections, testing and commissioning etc. as required.
2.20:Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 amps "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
9.1.20:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm)
5.1:Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required.
5.12:Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
5.16:Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
2.2.1:Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100 Amp, 16 KA, TPMCCB
2.2.3:Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.150 Amp, 16KA,TPMCCB
2.1.5:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.160 Amp TP&N
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
7.5.1:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
7.6.1:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm
7.7.1:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
14.16.1.a:Supplying and laying of following size DWC HOPE pipe lSI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 em below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal)
122.1.3:Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*10 sqmm
OD2870/2023-2024:Supply of exhaust fan heavy duty complete with shutters blades etc as required 18"(450mm ) sweep 1400 rpm etc as required
122.1.12:Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3C*35 sqmm
122.1.29:Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*16 sqmm
122.2.27:SITC of 30W LED Flood Light luminaire fitted with lens, made of pressure die cast aluminium housing & toughened glass cover complete with the following specification as reqd with IP 66 protection (a) Total system wattage =30 watt +/- 5% (b) Luminaire Efficacy>=100 Lm/w (c) Power Factor>=0.95 (d) Protection Class- IP-66
122.2.28:SITC of 60W LED Flood Light luminiare fitted with lens, made of pressure die cast aluminium housing & toughened glass cover complete with the following specification as reqd with IP 66 protection (a) Total system wattage =60 watt +/- 5% (b) Luminaire Efficacy>=100 Lm/w (c) Power Factor>=0.95 (d) Protection Class- IP-66
OD2869/2023-2024:SITC of metal clad, powder coated, compartmentalized cubical panel board as per CPWD electrical specifications including insulated aluminum bus bars, supports, interconnection, erection of switchgears with depth 30 cm to 60 cm and making provisions for termination of incoming/ outgoing cables/ bus ducting and making foundation etc as required. (Suitable for 400 Amp TP & N)
122.2.39:S/I/T/C of LED Tube type luminaire 20 Watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficient LEDs with the following:(a) Total system wattage 20 watt +/- 5%(b )Luminous efficacy lumens/watt >=95 (c)Power Factor >=0.95
M/s New Gupta Electric Works
M/S. A.K. Electricals
Bidder Name
M/s New Gupta Electric Works
G D Electricals
M/S. A.K. Electricals
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .