Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.5 LAccepted-AOC | L1 | Accepted-AOC LOWEST RATE QUOTED | |
| 2 | L2₹18.0 L+₹53,520.39 (3.06%)Rejected-Finance | L2 | Rejected-Finance higher quoted amount | |
| 3 | L3₹18.3 L+₹78,481.26 (4.48%)Rejected-Finance | L3 | Rejected-Finance higher quoted amount | |
| 4 | L4₹18.5 L+₹1.0 L (5.75%)Rejected-Finance KEOTA NO 2 SAHAGANJ HOOGHLY | HOOGHLY | HOOGHLY | WEST BENGAL | L4 | Rejected-Finance highest quoted amount |
Tender Value
Refer Docs
EMD Value
₹30,000
Closing Date
25 Jan 2022, 12:00 pmClosed
Executive_Engineer_PWD_Hooghly_Electrical_Division
Purta Bhavan sarat sarani hooghly
Electrical Installation work incl. arrangement of Servo Voltage Stabilizer and Air-conditioning system in required places incl. strengthening of electrical power network for proposed 24 beded Hybrid Critical Care unit at Chandannagar SD Hospital, Hoo
2022_WBPWD_359643_1
WBPWD/EE/HED /NIeT-18/2021-22
Open Tender
Electrical Work/ Equipment
Item Rate
25 days
HOOGHLY
Please refer Tender documents.
3 documents required · 3 mandatory
₹30,000
HOOGHLY ELECTRICAL DIVISION
21 Dec 2022
6 Jan 2022
27 Jan 2022
6 Jan 2022
25 Jan 2022
6 Jan 2022
13 Jan 2022
Amount
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed]
Avg. run- 9 Mtr [ 5(d) / E-15 ]
Distn. wiring in 3 X 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 5A 3 pin plug point as per GS with following average run.
On Board [ 4 (a)(i) / E- 10 ]
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works
20 mm size [ 7(a)/ E- 16 ]
25 mm size [ 7(b)/ E- 16 ]
Cutting Channel of required size on masonry wall by Electric operated cutting machine incl. supplying & fixing of heavy gauge Polythene pipe of following diameter as per GS.
19 mm dia 3 mm thick [ 6 (a)/ E- 3 ]
25 mm dia 3 mm thick [ 7 (a)/ E- 3 ]
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire(Brand approved by E.I.C) of the following sizes in the 19mm/25mm prelaid polythene pipe/PVC rigid conduit as per GS.
3 x (1.5 sqmm) [1(b) / E- 9 ]
2x(2.5 sqmm)+1x(1.5 sqmm) [ 1(s) / E-9 ]
2x(4 sqmm)+1x (2.5 sqmm) [ 1(v) / E- 9 ]
2x (6 sqmm) + 1x (4 sqmm) [ 1 (y) / E- 9 ]
4x(10 sqmm)+2x (6 sqmm) [ 1(d1) / E- 9 ]
4x(25 sqmm) + 2x (10 sqmm)
S & F solderless Copper socket by crimping of Copper wires.
a)1.5 sq mm
b) 2.5 sq mm [9(i) / F-5]
c) 4 sq mm [9(ii) / F-5]
d) 6 sq mm [9(iii) / F-5]
e) 10 sq mm [9(iv) / F-5]
f) 25 sq mm
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes (in mm) flushed in wall & 3 mm thick bakellite cover as per GS.
175 x 100 x 65 [11(c)/E-4 ,13(c) /E-5]
240 x 200 x 65 [11(e)/E-4 ,13(e)/E-5]
S & F CRC sheet metal(16 SWG) JB- cum- Switch board of the following sizes complete with three no. suitable size copper bar with holes (for Ph, N & E) fixed on bakellite/Hard rubber insulator over the MS welded chairs incl. bakelite/Perspex/coloured perspex(wall matching colour) top cover 3mm thick flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works.
200mm x 150mm x 65mm [10(c)/E-4]
175mm x 100mm x 65mm [10(b)/E-4]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall as per GS.
6Way Make - Legrand, Enclosure-607716/Schneider, Enclosure-A9HTND06/Crabtree, Enclosure- (DCDKTHODCW06) or equivalent cat of Siemens/L&T as approved E.I.C as approved by E.I.C [ 14 / D- 10 ]
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall as per GS.
2+12 Way [Siemens Enclosure(8GB32102RC14)/ Schneider Enclosure-(A9HSND12) or equivalent model of Legrand / Crabtree] as per direction of EIC. [ 13 / D- 9 & D-10 ]
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as perGS [Make-Legrand/ Schneider/Siemens/ Crabtree/ L&T as per direction of EIC. ]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [Make-Legrand/ Schneider/Siemens/Crabtree/L&T as approved by E.I.C.]
Supplying and fixing 415V, 200A TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc as per GS. [Make- L&T/ Havells/HPL as approved by E.I.C]. [3(a)/D-2]
Supplying and fixing 415V, 125A TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc as per GS. [Make- L&T/ Havells/HPL as approved by E.I.C]. [3(a)/D-2]
Supplying and fixing 415V TPN SFU with sheet steel enclosure of following rating on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (Make- L&T /Siemens/Havells as approved by E.I.C.)
160A TPN SFU [4(a)/D-3]
Supply of 4/3.5 Core XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make- Nicco/Gloster/KEI/Havells as approved by E.I.C]
3.5 Core 120 Sq. mm
3.5 Core 95 Sq. mm
Laying of 3/3½ core cable of following sizes on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting as GS.
Above 90 to 150 Sq. mm [ 2(e)/ F- 1 ]
Laying of cable after cutting floor/pavement/wall as per GS for the following Sizes.
Above 95 sqmm at an average depth of 100 mm in floor/pavement/wall etc. [ 5(iii)/ F- 3 ]
Laying of cable in underground trench as per GS for the following numbers of Cables.
Above 35 and upto 185 Sq. mm [1(b)/ F- 2 ]
Laying only Cable above 50 sqmm but not exceeding 400 sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½ and 4 core. [3(b)/ F-1]
Supplying & fixing medium gauge GI Pipe (ISI-Medium) Protection with necessary fittings as per GS.
80mm dia [11(f)/F-6]
Supplying and fixing compression type gland and finishing those for following XLPE/PVC armoured cable (2/4/3.5) Core as per GS.
3.5 Core 120 Sq. mm [7(d)/F4 & 8(b- xix) /F5]
3.5 Core 95 Sq. mm [7(d)/F4 & 8(b- xix) /F5]
Supply & Fixing 240 V, 2 nos. 6A, & 2 nos. 20A plug socket with separate 2 nos. 6 A & 2 nos. 20A Piano key type switch,indicator & 20A switch type SP MCB (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S &F 240x200x65mm MS (16SWG) switch board andbakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. [28 / E- 7]
Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch, indicator & 20A switch type SP MCB (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. [26/ E- 7]
S & F 240V 6A Piano key type switch (Brand approved by EIC) on existing sheet metal switch board having bakelite/ perspex top cover by screws after making housing for switch by cutting bakelite/ perspex cover and making necessary connections as required. [14(a)/E-5]
S & F 240V, 6A Plug socket (Brand approved by EIC) without switch and plug top on existing sheet metal switch board with bakelite/ perspex top cover by screws after making housing for plug by cutting bakelite/ perspex top cover and making necessary connections with PVC wire and earth continuity wire etc. [15(a)/E-5]
S & F 240V 16/20A Piano key type switch (Brand approved by EIC) on existing sheet metal switch board having bakelite/ perspex top cover by screws after making housing for switch by cutting bakelite/ perspex cover and making necessary connections as required. [14b)/E-5]
S & F 240V, 20A Plug socket (Brand approved by EIC) without switch and plug top on existing sheet metal switch board with bakelite/ perspex top cover by screws after making housing for plug by cutting bakelite/ perspex top cover and making necessary connections with PVC wire and earth continuity wire etc. [15(b)/E-5]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc.[ 5(a) / E-17]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections. [5(b) / E-17]
Supply & Fixing 240 V, 25A Modular starter (Brand approved by EIC) on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [20/E-19]
S&F of 250V timer DB (equivalent to 12 way SPNDB in size) with double door sheet steel enclosure, neutral bar, din rail, with lP43 protection comprises with 20/25A DPMCB(C-curve 10ka) and 1 no 24 hr analog time switch and 1 no 18/25A power contactor complete with internal wiring with suitable size of copper wire including 1 no toggle switch and LED indicator and earthing attachment as per direction of EIC.
Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment
Supply & fixing of 240V, 50Hz Analog Time Switch (Make- L&T GIC, Cat No. J648B1 or equivalent make/model of Havells/Hager) in existing 4 way SS enclosure for controlling of exhaust fan as per direction of EIC.
Supply and delivery of single/twin Industrial LED Batten luminaries incl. Supply of 1 no./2nos. 18W LED Tube
Twin fittings [Philips make Cat No. TMC-501 P1xT-LED 22W P3242 or equivalent make CG / Bajaj / Wipro] incl. 2 nos. 18W Master LED Tube
Single fittings [Philips make Cat No. TMC-501 P1xT-LED 22W P3241 or equivalent make CG / Bajaj / Wipro] incl. 1 no. 18W Master LED Tube
Fixing only single/twin fluorescent/LED light fitting in the ceiling fixed with “L” type MS clamp for RC ceiling / MS pipe as per GS direction of EIC [ 17/C-2 ]
S & F of 12W surface mounted LED light fittings (warm-white or cool day light as per application) incl. necessary connections as per direction of EIC. (Make-CG, cat no.- LCDSPLN-R-12-WW/LCDSPLN-R-12-CDL or equivalent model/cat of Phillips / Bajaj / Wipro/Havells as approved by E.I.C )
Supply & Fixing angular batten holder (Anchor) on 75mm dia PVCround block / round bakelite on wall/ceiling as per GS [ 22/D-13 ]
Supply and fixing 14 W LED bulb (Make- Bajaj/CG/Philips/Wipro) on existing batten holder
Supply & fixing 450mm sweep wall bracket fan(high speed) with metal body & blades(Make- Orient-Wall-II Tornado or equivalent cat/model of CG/EPC/Cinni) with necessary wooden board on wall with nuts, bolts, washer etc.
Supply & fixing heavy duty Exhaust fan (Make- EPC or equivalent make as approved by EIC) of followinng sizes after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust)
12"( 300mm ) Speed 920 RPM
Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall as per GS.
Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board as per GS [ 20( a )/D-13 ]
Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl. earthing attachment and painting as required – (As per Drawing no. 470 of PWD Specification Book – May 1991)
4 bars of rating- 415 V, 200 A with dimension of Al bars [85mm long] :- (4 x 50x5 mm) ; Dimension of Sheet Metal Box:- 500x150mm. [19(a)/D-12]
4 bars of rating- 415 V, 125 A with dimension of Cu bars [85mm long] :- (4 x 15x3 mm) ; Dimension of Sheet Metal Box:- 500x150mm. [19(b)/D-13]
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. Long With TATA-Medium GI pipe as per GS [ 2(a)/G-1]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) Cl hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. [3(a)/G-2]
Excavation of soil for installation of Earth Electrode and filling & ramming for Morrum Soil. [1(b)/G-1]
Connecting the equipments to earth busbar including S & F Solid GI (Hot Dip) wire of size as below as per GS.
No.- 4 SWG [5(a)(i)/G-2]
Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. [5(d)/G-3]
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall as per GS. [4(a)/G-2]
Dismantling of the existing defective and unuseable electrical installation materials.
SITC of 3-Phase 60 kVA Air-cooled Servo Voltage Stabilizer with Input Voltage Range-290V-480V & Nominal Output Voltage-400V, equipped with protection of Over-load/Short-circuit, single-phasing, surge etc. as per direction of E.I.C. (with 2 years warranty) [Factory testing is essential before despatch]. [Make- Numeric or equivalent make as approved by E.I.C]
Supply of 3 Star rated 1.5 Tr. capacity split Air-conditioner machine fitted with Rotary compressors suitable for Refrigerant-R32/R410A. (Make- Hitachi, Model- ZUNOH 3100f or equivalent make as approved by EIC).
Supply of 3 Star rated 1.0 Tr. capacity split Air-conditioner machine fitted with Rotary compressors suitable for Refrigerant-R32/R410A. (Make- Hitachi, Model- ZUNOH 3100f or equivalent make as approved by EIC).
Installation, testing & commissioning of the above-said 1.5/ 1.0 ton capacity split AC incl. supply & fixing required Angle Iron Structure on wall & mending works as per direction of E.I.C.
Supply & Laying Extra Add-on items- 5/8"(for suction) & 1/4"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation, 3 core x 2.5 sq.mm. copper cable incl. fixing arrangement and wrapping insulation of aerotape complete in all respect for 1.5/ 1.0 TR AC Machine and Supply & laying PVC Drain Pipe 25mm dia by shaddling on wall incl. PVC "T", elbow, bend etc as per direction of E.I.C.
Add GST @12% Rs.
Add LWC @1% except item no.-16 ,35, 54 & 55 Rs.
B.S.M ELECTRICAL
R.D.ELECTRICAL ENGINEERING CO
R.K. ENTERPRISE
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .