Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.5 LAdmitted-Finance | ₹7.5 L | L1 | Admitted-Finance |
| 2 | L2₹8.2 LAdmitted-Finance | ₹8.2 L | L2 | Admitted-Finance |
| 3 | L3₹8.9 LAdmitted-Finance | ₹8.9 L | L3 | Admitted-Finance |
| 4 | L4₹9.2 LAdmitted-Finance | ₹9.2 L | L4 | Admitted-Finance |
| 5 | L5₹9.9 LAdmitted-Finance SEC 3 GANGYAL GARDEN JAMMU | ₹9.9 L | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Electromechanics Engineers And Contractors L3 | Akhil Enterprises L5 | GRD ENGINEERS L2 | AUTO TECH INDIA L1 | M/S MAHESH KOTWAL CONTRACTOR L4 |
|---|---|---|---|---|---|---|---|---|
| 1.00Wiring for sub main wiring with following sizes of PVC/ insulated copper conductor wires in the surface/ recessed PVC / MS conduit along with PVC insulated copper conductor earth wire as required complete with connections, testing and commissioning etc. as per specifications and drawings. | ||||||||
| 1.10 | 4x6 sq. mm with 2 x 6.0sq. mm earth wire | 80 | meter | 587 ₹46,960 | 150 ₹12,000 | 587 ₹46,960 | 400 ₹32,000 | 700 ₹56,000 |
| 1.20 | 4x10 sq. mm with 2 x 6.0sq. mm earth wire | 80 | meter | 787 ₹62,960 | 149 ₹11,920 | 787 ₹62,960 | 700 ₹56,000 | 1,400 ₹1.1 L |
| 1.30 | 4x16 sq. mm with 2 x 6.0sq. mm earth wire | 60 | meter | 100 ₹6,000 | 450 ₹27,000 | 100 ₹6,000 | 1,300 ₹78,000 | 1,700 ₹1.0 L |
| 2.00Supply, installation, designing testing at works, installation and commissioning of outdoor type cubical panel box suitable for 3 phase 4 wire 415 volts 50 Hz supply system CRCA sheet steel enclousre panel with febricated with 14/16 SWG CRCA sheet steel and duly powder coated with simns grey and chemical treattment for with front and rear openable provided with suitable gaskit to make dust/vermin proof for ip 54 as per IS 13947 degree of protection, fault rating 50 KA/1 sec including angle iron base frame of size 50x50x6 mm for mounting the panel board at the hieght of 600 mm from FFL etc ( L&T, Legarnd and schineder) including dismentaling of existing LT panel etc as Directed by eng-in- charge. | ||||||||
| 2.10Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100% | ||||||||
| 2.20Note : | ||||||||
| 2.30All metering current transformers shall be Class 1, 15 VA. | ||||||||
| 2.40MDB-1 (Indoor Type) | ||||||||
| 2.50Incomer | ||||||||
Tender Value
₹10.0 L
EMD Value
₹19,980
Closing Date
14 May 2026, 4:00 pmClosed
Estates Officer, SKUAST-Jammu
Estates Division, SKUAST-J, Chatha
Providing electric repair work by way of replacing damaged panel, Copper wire, PVC power cable and other allied work at FVSc and AH R S Pura
2026_SKUST_309529_6
AU/Estates/2026-27/05 dated 07-05-2026
Open Tender
Electrical Works
90 days
Main Campus, Chatha
Please refer tender documents
4 documents required · 4 mandatory
₹500
Assistant Comptroller (Estates), SKUAST-Jammu
₹19,980
18 May 2026
8 May 2026
15 May 2026
8 May 2026
14 May 2026
8 May 2026
Wiring for sub main wiring with following sizes of PVC/ insulated copper conductor wires in the surface/ recessed PVC / MS conduit along with PVC insulated copper conductor earth wire as required complete with connections, testing and commissioning etc. as per specifications and drawings.
4x6 sq. mm with 2 x 6.0sq. mm earth wire
4x10 sq. mm with 2 x 6.0sq. mm earth wire
4x16 sq. mm with 2 x 6.0sq. mm earth wire
Supply, installation, designing testing at works, installation and commissioning of outdoor type cubical panel box suitable for 3 phase 4 wire 415 volts 50 Hz supply system CRCA sheet steel enclousre panel with febricated with 14/16 SWG CRCA sheet steel and duly powder coated with simns grey and chemical treattment for with front and rear openable provided with suitable gaskit to make dust/vermin proof for ip 54 as per IS 13947 degree of protection, fault rating 50 KA/1 sec including angle iron base frame of size 50x50x6 mm for mounting the panel board at the hieght of 600 mm from FFL etc ( L&T, Legarnd and schineder) including dismentaling of existing LT panel etc as Directed by eng-in- charge.
Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100%
All metering current transformers shall be Class 1, 15 VA.
MDB-1 (Indoor Type)
Incomer
160 A 4P 36K MCCB – 1No.
R,Y,B phase indicating lights with control fuses - 1 set
Bus Bar
250 A 415V, 50Hz, 3ph, 4 wire Aluminium Bus bar
Outgoing
TPN 63 amp 8 no
TPN 40 amp 8 no
SPN 40 amp 6 no
SPN 63 amp 6 no
Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100%
All metering current transformers shall be Class 1, 15 VA.
MDB-1 (Indoor Type)
Incomer
250 A 4P 36K MCCB – 1No.
R,Y,B phase indicating lights with control fuses - 1 set
Bus Bar
400 A 415V, 50Hz, 3ph, 4 wire Aluminium Bus bar
Outgoing
TPN 63 amp 8 no
TPN 40 amp 8 no
SPN 40 amp 6 no
SPN 63 amp 6 no
Moulded case circuit Breakers shall be thermal magnetic trip type. Fault level for all MCCB and bus bar shall be 50 KA. ICU shall be equal to ICS=100%
All metering current transformers shall be Class 1, 15 VA.
MDB-1 (Indoor Type)
Incomer
125 A 4P 36K MCCB – 1No.
R,Y,B phase indicating lights with control fuses - 1 set
Bus Bar
250 A 415V, 50Hz, 3ph, 4 wire Aluminium Bus bar
Outgoing
TPN 63 amp 6 no
TPN 40 amp 6 no
SPN 40 amp 4no
SPN 63 amp 4no
Supply and laying of PVC Power cable 1.1 KV Grade armoured aluminium XLPE cables including earth work, cost of end termination, thimbles and saddles etc. as required.
3.5 C X 120 SQ MM
3.5 C X 240 SQ MM
Earthing withGI earth plate 600mm x 600 mm x 6mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (with charcoal or coke and salt) complete as required for earthing and lightning protection
Providing and fixing 25 mm x 6 mm GI strip from earth electrode as required(10 Meter) each approx
Repairing of 150 KVA oil cooled servo voltage stablizer 3 phase by way of replacing of Dimmer/veriable (3nos) and complete rewinding of copper coil (3nos) including cost of old material and replacing of synchronizing motor 10KG(3nos) motor network,bacalite plate,microsoft switch(3nos),wiring for auto control micro procerror card(3nos), bearing variable socket (3nos), volt meter 96 mm 300 volt(3nos),front plate, push button(6nos) togal switch (6nos) and indicator 12 nos complete job
Repairing of 5 HP motor( mono block pump set ) by way of complete rewinding etc as requried
Providing and fixing of following rating and breaking capacity and Pole MCCB with thermal magnetic trip type and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel making connections, etc. as requried ( L&T, Legarnd and schineder)
250 ampre MCCB 4 pole 36 ka thermal magnetic trip type with spreader link
200 ampre MCCB 4 pole 36 ka thermal magnetic trip type with spreader link
400 ampre MCCB 4 pole 36 ka thermal magnetic trip type with spreader link
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.28 MB
Termsandconditions.pdf
Tender Documents • 0.22 MB
BOQ_1002192.xls
BOQ • 4.39 MB
Download all tender documents and submit your bid