Dy. General Manager Housing Unit-II Sgr
Dy. General Manager Housing Unit-II Sgr
Providing and fixing of false ceiling for 200 Bedded District Hospital Handwara and Balance work (Electrical and Civil).
2025_HAUDD_299105_1
e-NIT No. 10 of 12/2025-26, Dated -24-12-2025
Open Tender
Civil Works - Others
Percentage
Dy. General Manager Housing Unit-II Sgr
As per NIT
2 documents required · 2 mandatory
₹5,000
Dy. General Manager Housing Unit-II Sgr
₹2.3 L
30 Jan 2026
26 Dec 2025
17 Jan 2026
26 Dec 2025
16 Jan 2026
26 Dec 2025
Providing and fixing mineral fibre false ceiling tiles at all heights ofsize 595X595mm of approved texture, design and pattern. (Armstrong Buildwel, Bioguard & equivalent) The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in charge.With 16 mm thick bevelled tegular mineral fibre Antimicrobial false ceiling tile confirming to ISO 5 (class10
Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7) in true horizontal level over existing grid including dash fasteners ,hanger rods,screws where ever required With 16 mm thick bevelled tegular mineral fibre Antimicrobial false ceiling tile confirming to ISO 5 (class100 ) specifications
steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in grounding/DWC Pipe including excavation, sand cushioning, protective covering and refilling the trench, Making end Termination Brass and Aluminium Lugs etc as required.
3.5 C X 150 Sq.mm
Supply & Fixing of 36W , 2x2 LED reccesse type Luminaire suitable for operating Voltage range of 150V-270V. Luminaire should be suitable for armstrong /grid ceiling mounting with help of 4 Nos clips for suspension. Body made up of CRCA powder coated with Diffused Optics. Luminaire size should not be less than 595x595x60mm and power factor >=0.95, CRI>=80, THD<10%, Max system wattage should be 36 Watt.
Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.38 MB
BOQ_969978.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .