Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical | Accepted-Technical all documents submitted as per tender criteria |
| 2 | Accepted-Technical | Accepted-Technical all documents submitted as per tender criteria |
| 3 | Rejected-Technical | Rejected-Technical Short fall documents not submitted |
Tender Value
₹10.0 L
EMD Value
₹20,000
Closing Date
8 Jan 2026, 3:00 pmClosed
Superintending Engineer
Estate office NIT Warangal.
Annual Maintenance Contract of 11 0.433 kV Electrical substations 6Nos at NIT Warangal
2025_NITW_890385_1
38/NITW/EO/ELEC/2025-26 Date18.12.2025
Open Tender
Electrical Works
Works
365 days
NIT WARANGAL
Please refer to the tender document
7 documents required · 7 mandatory
₹1,180
To DIRECTOR NITW
₹20,000
11 Feb 2026
18 Dec 2025
9 Jan 2026
18 Dec 2025
8 Jan 2026
18 Dec 2025
18 Dec 2025 - 1 Jan 2026
Carryout routine maintenance, servicing and testing of 630A to 3000A HT VCB by cleaning fixed contacts, moving contacts and arcchutes including servicing and putting the VCB in perfect working condition after detting all relay and ON, OFF mechanism, including testing of breaker timing and IR etc. done with only manufacturing companies / Authorised dealers of respective switch gears on Quarterly basis and Attending the all breakdowns and keep it in healthy condition.
Carryout routine maintenance, servicing and testing of 630A to 1000A HT VCB by cleaning fixed contacts, moving contacts and arcchutes including servicing and putting the VCB in perfect working condition after detting all relay and ON, OFF mechanism, including testing of breaker timing and IR etc. done with only manufacturing companies / Authorised dealers of respective switch gears on Quarterly basis and Attending the all breakdowns and keep it in healthy condition.
Carryout routine maintenance and servicing of 11kV HT panel board having 1 or 2 incomers and 4 to 6 Nos of Outgoing VCBs/LBSs, cleaning with power blower and servicing the contacts, tightning the connection of incoming and outgoing cables, control cables, terminal blocks and checking the CT, PT and testing the numerical relays by primary/secondary injection and putting them in smooth working condition on Quarterly basis and Attending the all breakdowns and keep it in healthy condition.
Carryout routine maintenance and servicing of LT.Cubical panel board having approximately 15 to 22 Nos of switches/MCCB/Changeover cleaning with power blower and servicing the contacts, tightning the connection of incoming and outgoing cables, and checking the operating machanism for smooth functioning of switches and putting them in smooth working condition on Quarterly basis and Attending the all breakdowns and keep it in healthy condition.
Carryout routine maintenance of Oil type transformer in operation covering insulation resistance oil, break down strength. Reconditioning / replacement of silicagel, cleaning of transformer and topping upto oil level if required including checking the tightness of Power and control cables etc. on Quartely basis (extra cost will be paid for oil) and Attending the all breakdowns and keep it in healthy condition.
Carryout routine maintenance of Dry type transformers on Quarterly basis. Transformer in operation covering insulation resistance, check and tighten screws, connections, voltage change bridges and coil support blocks and clean any dust surfaces using a vacuum cleaner or by blowing with dry air and check the thermal protection device that includes the sensors etc on Quarterly basis and Attending the all breakdowns and keep it in healthy condition.
Carryout routine maintenance on Quarterly of 11kV 3P isolator with HG fuse set and LAs servicing including cleaning and lubrication of contacts,checking alignment,tightness of nut bolts etc, clean the porcelain insulators and inspection for cracks and chip off and contact resistance checking for all substation and complete 11kv overhead line in NITW and Attending the all breakdowns and keep it in healthy condition. a)4 pole structure
Carryout routine maintenance on Quarterly of 11kV 3P isolator with HG fuse set and LAs servicing including cleaning and lubrication of contacts,checking alignment,tightness of nut bolts etc, clean the porcelain insulators and inspection for cracks and chip off and contact resistance checking for all substation and complete 11kv overhead line in NITW and Attending the all breakdowns and keep it in healthy condition. a)2 pole structure
Carryout routine maintenance on Quarterly of 11kV 3P isolator with HG fuse set and LAs servicing including cleaning and lubrication of contacts,checking alignment,tightness of nut bolts etc, clean the porcelain insulators and inspection for cracks and chip off and contact resistance checking for all substation and complete 11kv overhead line in NITW and Attending the all breakdowns and keep it in healthy condition. a)1 pole structure
Supply of Transformer oil (tested as per IS 335-1972)
Filteration of transformer oil as per IS specification filter to dielectric strength above 40KV at site with test report including all consumables and machines required for the job etc.
Replacing old and unserviceable gaskets of top cover plate of transformer having following capacity.upto 315KVA
Replacing old and unserviceable gaskets of top cover plate of transformer having following capacity.upto 500/1000KVA
Supply and erectin of transformer breather with silica gel (500gms size)
Supply and refilling of silica gel in transformer breather
Supply and erection of LED indication lamps on the existing panel board.
Providing and erecting heat shrinkable indoor termination kit for 11 KV HT XLPE insulated armoured cable 240-300 Sqmm 3 core with necessary materials etc., complete.
Providing and erecting heat shrinkable outdoor termination kit for 11 KV HT XLPE insulated armoured cable 240-300 Sqmm 3 core with necessary materials etc., complete.
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.55 MB
Tendernotice_2.pdf
PDF • 0.12 MB
tenderdoc.pdf
Tender Documents • 1.54 MB
BOQ_935878.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .