Lt Col Sanjay Siwach, GE
GE 970 EWS C/o 56 APO PIN-913970
PROVN O 15 X STANDALONEL AIR HEATING SYSTEM AND 15 X BAZOOKA AIR HEATING SYSTEM FOR BLDG NO P-134 P-135 P-136 P-210 P-213 P-214 P-215 P-239 P-342 P-455 AND P-456 AT JAK LI REGT CENTRE, SRINAGAR UNDER GE 970 EWS
2026_MES_756719_1
GE 970 EWS-95(T)/2025-26
Open Tender
Civil Works
Item Rate
180 days
JAK LI RC SRINAGAR
As per tender documents
8 documents required · 8 mandatory
₹500
GE 970 EWS
₹67,300
Yes
14 Apr 2026
18 Mar 2026
8 Apr 2026
18 Mar 2026
6 Apr 2026
1 Apr 2026
18 Mar 2026 - 6 Apr 2026
Supply and install, testing and commissioning of standalone ai heating system for space heating of hot air capacity of 35000 Kcal/Hr suitable for indoor operation with heat exchanger disel or kerosene and fuel filter, burner, blower fan, automatic digital temeparture controller, control panel with visual controls, safety interlocks, over load relay, timers, suitable capacity of fuel tank with following features:- (a) Bottom Flow ( Hot Air release from bottom side of machine) (b) Control panels are double insulated (c) Burning chamber is made of flame resistant mild steel (d) Fully automatic operation (e) electronic control board is not effected high temperature (f) The monoblock body is insulated by the fiberglass and the exterior protection is secured against corrosin by powder painted sheet metal (g) Heat converting pipes are made of finest quality mild steel (h) Environmental friendly (j) Self diagnosis (k) Auto restart (k) Lock (l) Instant Heat (m) Exterme temperature controlling capabilities at minus at 50˚C with its improved heating capacity it heat easily at sub zero temperature. (n) Stablizer free operation (o) Heat output - 35000 Kcal/Hr (p) Hot Air Tempertaure :40˚C (q) Temperature rise :90˚C max (r) Thermal efficiency :80-90% (s) Electric Supply :220Volt, 50 Hz (t) Temperature control : Automatic (u) Fuel type : Diesel / kerosen (v) Burner : Riello/Ben-ton.
Supply and install, testing and commissioning of Bazooka Air heating system for space heating of hot air capacity of 20 KW suitable for semi open sheads operation with heat exchanger disel or kerosene and fuel filter, Automeatic Ignition, automatic digital temeparture controller, control panel with visual controls, safety interlocks, over load relay, timers, 20 Ltrs fuel tank attached with heating system with following features:- (a) Air Flow 900 Cum/hrs ( Hot Air release from front side of machine) (b) Control panel (c) Burning chamber is made of flame resistant mild steel (d) Fully automatic operation (e) electronic control board is not effected high temperature (f) The exterior protection is secured against corrosin by powder painted sheet metal (g) Environmental friendly (h) Self diagnosis (j) Auto restart (k) Lock (l) Instant Heat (m) Stablizer free operation (n) Heat output - 17200 Kcal/Hr (o) Hot Air Tempertaure :40˚C (p) Temperature rise :35˚C max (q) Thermal efficiency :80-90% (r) Electric Supply :220Volt, 50 Hz (s) Temperature control : Automatic (t) Fuel type : Diesel / kerosen.
M & L for one point wiring with PVC insulated un-sheathed cable with stranded copper conductor FR-LSH conforming to IS : 694 of size 2.5 Sq mm single core, including one No. 2.5 Sq mm single core PVC insulated un-sheathed copper cable FR-LS as continuous earth wire drawn in and including PVC casing caping white colour with all accessories of same grade,surface on wall/ceiling including terminated in to Modular switch board / Cast iron/pressed steel terminal box 60mm deep of required size made out of 2mm thick MS sheet duly painted both sides with 3 mm thick plastic laminated sheet top cover fixed with brass screw & cup washers for mounting switch socket combination 5 and 15 Amp flush type on the independent board complete all as specified and as directed
S & F Switch Socket combination multipurpose 5/16 Amps 5in 1 flush type complete all as specified and as directed.
S & F DB with sheet metal enclosure 240 volts, 4 way with 200 Amp rated bus bar single pole & neutral double door type for MCBs including mounting work as required in position, complete all as specified and as directed.
Supply and fixing MCB SPN 40 amps 240 volts C curve, 50 HZ AC 10 KA complete all as specified and as directed.
Supply and fixing MCB SP 06 to 32 amps 240 volts C curve, 50 HZ AC 10 KA complete all as specified and as directed.
M & L for Earthing complete with galvanised steel earth plate, electrode, 600x600x6.0 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) connected to GI wire 4 mm dia by mens of nuts, bolts, & washers of GI as shown in electrical plate No. 5 of SSR Part-I Connected to earthing ten point all as specified and including necessary earth pit PCC 1:3:6 chanber be 50mm thick PCC 1:2:4 chamber cover with 6mm dia mild steel reinforcement of 10 cm c/c spacing both ways in lieu of CI cover , watering arrangement shall be made with GI pipe medium grade of 20mm dia including funnel and protection to earth lead shall be provided with GI pipe light grade 15mm dia upto 7.5 from the earth plate electrode & refilling of soil etc including necessary excavation & earth work in any strata and PCC chamber all as specified and directed by Engr-in-Charge including demolish existing earth pit taking out old materials complete all as specified and as directed.
M&L for Sub Main wiring using FRLS Insulated unsheathed, multistrand copper conductor FRLS PVC cable 2 runs of size 6 sqmm for phase and neutral and 4 Sq mm for earthing. drawn through rigid PVC casing caping fixed on wall/ground/Ceiling etc., and complete all as directed by Engr-in-Charge. Note: Phase should be Red / Yellow / Blue, neutral should be black and earthing wire should be green in colour. Two runs of cable for phase / neutral and one run of cable for earth incl conduit/Casing Caping will be measured and paid as one unit length complete all as specified and as directed.
S & F in repairs MS cross arms channel, bracing, support, clamps etc fabricated structured steel, sections, including nuts, bolts, washers etc and cutting to required length beat to any shape drilling holes, fixed on poles or jointed by means of elect welding complete incl painting with 2 coats of aluminum paint over a coat of red oxide primer after preparation of surfaces incl taking down / dismantling the old items complete all as directed.
stage.html
html • 0.04 MB
technical_847639.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
BOQ_847639.xls
BOQ • 0.26 MB
Tender95T_merged.pdf
Tender Documents • 2.80 MB
AMDT95T.pdf
PDF • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .