| Sl No | Description | Qty | Unit | GLOBE DETECTIVE AGENCY PVT. LTD., Electronics Division L2 | Kalpataru Industries L1 |
|---|---|---|---|---|---|
| 1.00SH I : DSITC of Fire Suppression System and Fire Alarm System | |||||
| 1.01Design, Supply, Installation, Testing & Commissioning of Fire Suppression System for following areas using Gas (clean agent) as per NFPA 2001 complete with the following: Supply of Cylinder UL listed/FM/VDS/LPCB/CCOE(PESO) Approved, complete with valve assembly and arrangement, supervisory switch connection for monitoring cylinder pressure, a pressure gauge with a safety burst disc, electronic control head / Solenoid, pressure operated control, head, flexible hose, strap, NRV, safety cap, Gas discharge Warning sign etc. complete as required. Gas - Quantity would be as per the design volume and as per the necessary codal specifications UL Certifications. Clean agent shall be of FK-5-1-12 Gas flooding System. All the necessary inteconnections by supplying and Laying of MS Pipes as per design with Nozzles, Supply, Installation, Testing and Commissioning of Gas Release Panel complete with timer, battery back up, Gas Release / Gas Abort Switch, Integration with Fire Alarm panel, all connections, accessories required for commissioning of the system etc. complete as required (Make : As per AAI List of Preferred makes) Note: The System will be provided in specified areas only as below. | |||||
| 1.02The contractor will design the system as per NFPA 2001. The contractor will get the design approved by AAI before execution. Statutory Approvals will be taken from concerned authorities. The piping design and pressure calaculations using manufacturer design software for a given dimension of room duly approved by manufacturer/distributors shall be submitted prior to starting of the work. Complete system design using certified design software, shall be duly vetted by the manufacturer (OEM) and submitted to the Engineer-in-Charge for approval before the commencement of work. | |||||
| 1.03Equipment Room: LxB = 3750 mm x 5000 mm ; Height till false ceiling = 3175 mm ; False ceiling height = 300 mm; Independent fire suppression system with individual gas release panel shall be provided. | |||||
| 1.04Battery Room : LxB = 2175 mm x 3250 mm ; Height = 3475 mm ; No False Height Independent fire suppression system with individual gas release panel shall be provided. | |||||
| 1.05Electrical room : 2675 mm x 3250 mm; Height = 3475 mm ; No false height. Independent fire suppression system with individual gas release panel shall be provided for each rooms. | |||||
| 1.06 | Total (1.01 to 1.05) | 1 | Job | 17,52,578 ₹17.5 L | 7,49,856 ₹7.5 L |
| 1.20 | Supply, Installation, Testing & Commissioning of UL/LPCB/ EN listed (latest version) Modular Microprocessor based expandable Intelligent Addressable Type Fire Alarm Control Panel of Minimum two loops, with minimum 160 character graphics / LCD display with touch screen or other keypad and minimum 1000 events history log in the non volatile memory (EPROM), Graphical Display, sufficient numbers of programmable relay controls, Modules, 230 volts, 50 Hz AC power supply, automatic battery charger, 12/24 volts sealed maintenance free lead acid batteries etc. complete as required. The panel shall be capable of activating Gas Releasing Control Module on activation of MCP for operating the Gas based Fire Suppression System.
(Make : As per AAI List of Preferred makes) | 3 | Each | 1,59,840 ₹4.8 L | 1,05,398 ₹3.2 L |
| 1.30 | Supply, Installation, Testing & Commissioning of UL / EN listed (latest version) intelligent addressable multi criteria detector {Smoke + heat } with inbuilt fault isolator / isolator base and with visible LED, fully coated circuit board, superior RF / Transient protection suitable for 2 wires loop connection, complete with plug into common separate base & housing complete with connections etc. as required and to be installed below / above false ceiling roof and concealed space and as per enclosed specifications, etc. complete as required. (Cost of plug in common base shall deemed to be included in cost of detectors)
(Make : As per AAI List of Preferred makes) | 16 | Each | 4,664 ₹74,624 | 2,900 ₹46,400 |
| 1.40 | Supply, installation, Testing and Commissioning of UL / EN listed (Latest Version) Response Indicators for getting fire indications of detectors i/c mounting boxes installed above false ceiling area interconnecting to loop cable etc. complete as required. | 8 | Each | 709 ₹5,672 | 1,644 ₹13,152 |
Tender Value
₹28.6 L
EMD Value
₹85,865
Closing Date
21 Nov 2025, 6:00 pmClosed
Manager EE
O/o ManagerEE
Construction of NDB Building at Puducherry Airport SH Provision of Fire Suppression System and its Associated Works including AICMC for 05 Years after 02 Years DLP
2025_AAI_253723_1
AAI/PDY/ENGG(E)/FSS/2025
Open Tender
Electrical Works
150 days
PUDUCHERRY AIRPORT
Please refer Tender documents.
17 documents required · 17 mandatory
₹1,180
₹85,865
23 Jan 2026
31 Oct 2025
24 Nov 2025
31 Oct 2025
21 Nov 2025
31 Oct 2025
31 Oct 2025 - 7 Nov 2025
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.50 MB
tenderdoc.pdf
Tender Documents • 8.58 MB
BOQ_292225.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid