Facilities Management Division, Bangalore
HINDUSTAN AERONAUTICS LIMITED Facilities Management Division, Bangalore
Refurbishing Works including Civil Interiors Electrical and Fire Alarm System for CS Cell at MCSRDC Building HAL Bangalore
6895
TENDER NOTICE/NCP/52/23-24/01
Works
Contract Section Civil-FMD-Bangalore
₹1,180
₹79,500
25 Apr 2024
1 Apr 2024
1 Apr 2024
25 Apr 2024
HINDUSTAN AERONAUTICS LIMITED BANGALORE FACILITIES MANAGEMENT DIVISION
NAME OF THE WORK: Refurbishing Works including Civil Interiors, Electrical and Fire Alarm System for CS Cell at MCSRDC Building, HAL (Bangalore). CONTRACT NO. HAL/FMD/R-179/23-24
Name of the Contractor :
Sl. No. Specification Quantity Unit Rate in Figs [Excluding GST] Rate in Words Amount
Preamble: (1) The subject work has been called on works contract basis and prevailing GST for same is 18%. Any change in GST +/- during the currency of contract shall be on HAL account. The Tenderer shall abide by prevailing GST act. (2) L1 (lowest quote) will be determined based on the total quoted amount including GST. (3) This BOQ specification has to be read in conjunction with detailed technical specification and tender drawings if any.
Part 'A' - Civil Works
DISMANTLING & DEMOLITION
1 Dismantling of existing false ceiling of any type and of any height with required scaffolding, etc., including handing over all dismantled resuable items to the maintenance department stores and unusable materials to scrap yard, etc., all complete as directed by the Engineer-in-Charge. 420 Sq m
Dismantling of existing panelled or glazed wall partitions and wall panelling/work stations of any type including framework, handing over all dismantled resuable items to the maintenance department stores and unusable materials to scrap yard, etc., all complete as directed by the Engineer-in-Charge. 14 Sq m
Dismantling of existing aluminium partitions and doors of any height, including glazing / panelling, handing over all dismantled resuable items to the maintenance department stores and unusable materials to scrap yard, etc., all complete as directed by the Engineer-in-Charge. 504 Sq m
Dismantling of existing wooden/FRP doors of size (1.05m x2.10m) including accessories and handing over all dismantled resuable items to the maintenance dept. stores and unusable materials to scrap yard, etc., all complete as directed by the Engineer-in-Charge. 3 Each
Demolition of existing brick masonry work, taking out from walls built in cement mortar of any description at any height and position with requried scaffolding etc., and shifting reusable materials if any to maintenance stores for reconstruction purpose and disposal of demolished material (Except saleable materials) outside HAL to a distance of 5km, etc., all complete as directed by the Engineer-in-Charge. 2 Cu m
Dismantling of existing Alluminium windows/ventilators including framework, glazing, attached grills, accessories etc. and handing over all dismantled resuable items to the maintenance dept. stores and unusable materials to scrap yard, etc., all complete as directed by the Engineer-in-Charge. 10 Each
Dismantling of existing Tiles of any description or thickness in floors, dadoo and skirting laid, bedded and pointed in any mortar and moving unusable materials to scrap yard with a distance of not exceeding 10km, etc., all complete as directed by the Engineer-in-Charge. 420 Sq m
Taking down/ dismantling existing steel and iron work in windows,ventilators of any type and of any height including doors by cutting rivets/ by welding with required scaffolding, etc., including handing over all usable dismantled steel and iron items as a frame in whole size to the maintenance department stores and un usable material to scrap yard, etc., all complete as directed by the Engineer-in-Charge. 90 Quintal
Providing and fixing gypsum board 12mm thick in ceiling fixed with screw as per manufacturers instructions with G.l. frame work for seamless ceiling comprising of G.l. perimeter channel 0.55mm thick with two unequal flanges of 20 and 30mm and web of 27mm fixed to surrounding wall using nylon sleeves and screws at 450mm centre to centre/intermediate channel 0.90mm thick having two equal flanges of 15mm each and web of 45mm suspended from soffit at approx 900mm centre to centre with Gl cleat and steel expansion fasteners with and including ceiling section (not exc 1.20m length) of 0.55mm thickness having kurled web of 50mm and flange of 26mm each with lips of 10.50mm fixed to the intermediate channel with connecting clips across the intermediate channel at 457mm centre to centre including hangers 6mm dia. G.I. (Upto 1200mm length) adjusting level fixed to roof slabs by means of ceilling cleats made out of G.I. flat 40 x 3mm size, 60mm long and expansion hold fasteners 12.50mm dia. 40mm long, etc., all complete as directed by the Engineer-in-Charge. Note: (i) Plan area shall be measured for payment. (ii) The quoted rate shall be for the entire work and nothing extra shall be paid on this account. 18 Sq m
Providing and fixing seamless calcium silicate ceiling made out of 1800x1200mm size board of 8mm thick siliceous and calcareous materail reinforced with cellulose fibre fixed to the ceiling section with 25mm long self drilling and tapping screws having phillips head with under head cutter at 200mm centre to centre ,including finishing the joint of face board with specifically formulated jointing compound and 48mm wide fibre tape to provide seamless finish fixed over comprising of G.l. perimeter channnel 0.55mm thick with two unequal flanges of 20 and 30mm and web of 27mm fixed to surrounding wall using nylon sleeves and screws at 450mm centre to centre/intermediate channel 0.90mm thick having two equal flanges of 15mm each and web of 45mm suspended from soffit at approx 900mm centre to centre with Gl cleat and steel expansion fasteners with and including ceiling section (not exc 1.20m length) of 0.55mm thickness having kurled web of 50mm and flange of 26mm each with lips of 10.50mm fixed to the intermediate channel with connecting clips across the intermediate channel at 457mm centre to centre including hangers 6 mm dia. G.I. (Upto 1200mm length) adjusting level fixed to roof slabs by means of ceilling cleats made out of G.I. flat 40 x 3mm size, 60mm long and expansion hold fasteners 12.50mm dia. 40mm long, the entire work with one coat primer and two coats of emulsion paint for smooth finish, etc., all complete as directed by the Engineer-in-Charge. Note: The quoted rate shall be for the entire work with any slopes,curves,design cut or projections and nothing extra shall be paid on this account. 118 Sq m
Supplying & fixing of fully perforated 12mm thick micro tegular edged or 10mm thick square edged GRG false ceiling tiles, mineral fibre tile false ceiling at all heights of approved make consisting the following: Tiles of size 595 x 595mm of approved texture, design and patterns having moisture content less than 2%, humidity resistance of 99%, NRCO.50 to 0.75 as per IS 8225:1987, Noncombustible as per BS 476(part 4)-1970 and light reflectance of 85% (minimum) to be laid in true horizontal level suspended on inter locking metal T-Grid of hot dipped galvanized iron section of 0.33mm thick (galvanized @ 120 grams per sqm including both sides) comprising of main-T runners of size 15 x 32mm of length 3000mm,cross-T of size 15 x 32mm of length 1200mm and secondary intermediate cross-T of size 15 X 32mm of length 600mm to form grid module of size 600 X 600mm, suspended from ceiling using galvanized mild steel items (galvanizing @ 80 grams per sqm) i.e 50mm long, 8mm outer diameter M-6 dash fasteners, 6mm dia fully threaded hanger rod upto 1000mm length and L-shape level adjuster of size 85X25X2mm.Galvanized iron perimeter wall angle of size 24 x 24 x 0.40mm of length 3000mm to be fixed on periphery wall /partition with the help of plastic rawl plugs at 450mm center to center and 40mm long dry wall wood screws. The work shall be carried out as per specifications, drawing and as per directions of the Engineer-in-charge 146 Sq m
Supplying & fixing premium double charged vitrified tiles of approved shade (Light colour) & pattern, min. 9 mm thick (Square / rectangular), area of each tile not greater than 0.36 m², in floors and skirting etc., set & jointed in neat cement slurry at 3 kg/m² and pointed in white or coloured cement to match the colour of tile, over a screed of cement mortar (1:4) 20 mm thick including machine cutting, curing, etc., all complete as directed by the Engineer-in-Charge. Note : Quoted rate shall be inclusive of screed, pointing etc. 420 Sq m
Supplying & fixing anti-skid ceramic/vertified tiles of approved colour & pattern, min. 7 mm /9 mm thick (Square / rectangular), area of each tile exceeding 0.06 m² but not exceeding 0.11 m², in floors, set & jointed in neat cement slurry at 3 kg/m² and pointed in white or coloured cement to match the colour of tile, over a screed of cement mortar (1:4) 20 mm thick including machine cutting, curing, etc., all complete as directed by the Engineer-in-Charge. Note : Quoted rate shall be inclusive of screed, pointing etc. 38 Sq m
Supplying & fixing premium Matt Finsihed/as required vitrified tiles etc., of approved shade (Light colour) In dado over a screed of cement mortar (1:3) 15 mm thick & pattern, min. 9 mm thick, area of each tile not exceeding 0.36 m² or maximum size available, set & jointed in neat cement slurry at 3 kg/m² and pointed in white or coloured cement to match the colour of tile, including machine cutting, curing, etc., all complete as directed by the Engineer-in-Charge. Note: Quoted rate shall be inclusive of screed, pointing etc. 108 Sq m
Supplying, mixing, laying plain cement concrete (1:2:4), using 12.5 mm and down graded granite aggregates in drains, channels, trenches, septic tanks etc., including consolidation, necessary formwork, curing, materials, labours, tools and tackels, plants, etc., all complete as per specifications and as directed by the Engineer-in-Charge. 31.049999999999997 Cu m
SANITARY & WATER SUPPLY & PLUMBING
Supplying, fixing or laying, testing and commissioning the following dia CPVC SDR-11 pipes conforming to IS 15778 of approved make jointed together with solvent on walls/ceiling or in floors including all necessary plain and brass threaded CPVC fittings, clamps, pipe cutting & wastages, chasing & cutting holes in masonry and making good, etc., all complete as directed by the Engineer-in-Charge.
a) 16mm dia 25 R m
b) 20mm dia 30 R m
c) 25mm dia 30 R m
d) 32mm dia 15 R m
e) 40mm dia 20 R m
Supplying, fixing, testing and commissioning of white vitreous china wall hung EWC of size around (475 x 350 x 390) mm or nearest available size conforming to IS 2556 (Part 2) and of approved make with sleek PVC cistern of around 10 litres capacity conforming to IS 7231, closet fixed to the wall by suitable bolts, cistern fixed on suitable brackets embedded in cement mortar (1:4) or by plug and screws including seat and cover, suitable trap, jointing with cement mortar or putty wherever required, cutting and making good the floors/walls, connecting to sewer line etc. with all necessary fittings and accessories like 15 mm dia CP brass stop cock, 15 mm dia PVC inlet, flush pipe, coupling and lock nut, clamps, washers, etc., all complete as directed by the Engineer-in-Charge. 6 Each
Supplying and fixing light coloured vitreous china flat back urinal of light/white colour approved make, fixed to the wall by using wooden plugs embedded in cement mortar (1:3) including CP brass flush valve with wall flange, jointing with cement mortar or putty wherever required, cutting and making good the walls and floors, connecting to floor trap etc. with all necessary fittings and accessories like flush pipe, CP spreader, 32 mm dia semi-rigid PVC waste pipe, coupling, clamps, etc., all complete as directed by the Engineer-in-Charge. 2 Each
Supplying, fixing, testing and commissioning health faucet (ABS body) mild steel chromium plated suitable for 15 mm dia pipe and of approved make with 1.25 metre long flexible tube & ABS wall hook including 15 mm dia CP brass angular stop cock, etc., all complete as directed by the Engineer-in-Charge. 6 Each
Supplying, fixing, testing and commissioning sinks with drainage board of min. overall size 915 mm x 460 mm and min. bowl size 410 mm x 330 mm x 160 mm conforming to IS 13893, made of stainless steel 302 or 304 grade , min. 1 mm thick conforming to IS 5522, supported on suitable brackets embedded in cement concrete (1:2:4) blocks including bedding in cement mortar to dwarf wall or including fixing cantilever brackets, connecting union to pipe, connecting to floor trap, painting bracket with two coats of synthetic enamel paint over a coat of approved primer etc. with all necessary fittings and accessories like rubber plug with CP brass chain, 50 mm CP brass waste fitting, GI or PVC waste pipe, nuts, washers, etc., all complete as directed by the Engineer-in-Charge. 1 Each
Supplying, fixing, testing and commissioning vitreous china White/Light colour wash basin semi pedestal type of size around (500 x 400)mm or nearest available size, oval shape and of approved make, including fixing and adjusting wall, connecting to floor trap etc., with all necessary fittings and accessories like 15 mm dia brass CP angular stop cock, 15 mm dia SS pillar cock of approved model & make, 32 mm CP brass waste fitting, 32 mm dia semi-rigid PVC waste pipe, 32 mm CP brass bottle trap with connection pipe and wall flange, 15 mm dia PVC inlet pipe, etc., all complete as directed by the Engineer-in-Charge. 5 Each
Supplying and laying granite 20mm thick (Table rubbed and polished) in washbasin counters, cooking platforms, storage counters, shelves and the like including pointing in white cement (1:2) using marble dust with admixture of pigment to match the shade of granite, chasing & fixing to the wall in CC 1:2:4, half round nosing of edges, etc., all complete as directed by the Engineer-in-Charge. 4 Sq m
Supplying and fixing (600 x 450) mm bevelled edge mirror of selected quality glass, mounted on 6 mm thick commercial plywood and fixed to wooden plugs with chromium plated brass screws and cup washers, etc., all complete as directed by the Engineer-in-Charge. 6 Each
Supplying, fixing, testing and commissioning 15mm dia chromium plated cast copper alloy screw down type fancy bib taps with crutch or butterfly handle conforming to IS 8931, screwed down and fixed with wall flange, etc., all complete as directed by the Engineer-in-Charge. 6 Each
Supplying, fixing, testing and commissioning 15mm dia chromium plated cast copper alloy, with capstan heads, screwed down high pressure, with or without lettered 'Hot' or 'Cold' type fancy Pillar tap with long screwed shanks and fly-nuts, conforming to IS 8931, screwed for iron pipe and fixed with wall flange, etc., all complete as directed by the Engineer-in-Charge. 6 Each
Supplying and fixing CP brass towel rail min. 20mm dia and of length not less than 600mm including flange, screws, etc., all complete as directed by the Engineer-in-Charge. 3 Each
Supplying and fixing wall mounted soap dish PTMT fixed ( minimum weight 105gms ) of approved make with wall flange and concealed brass screw sets, including cutting and making good the walls, etc., all complete as directed by the Engineer-in-Charge. 5 Each
Supplying, fixing, testing and commissioning PVC (SWR grade) floor trap with 75mm dia outlet of approved make, including connection with soil/waste pipe, cement concrete (1:2:4) for embedding the trap, providing SS cockroach free floor grating with cup, cutting and making good the floors, etc., all complete as directed by the Engineer-in-Charge. 16 Each
Supplying, fixing, testing and commissioning PVC pipes of 110mm dia of 6 kg/cm² SWR grade and of approved make with rubber ring joints conforming to IS 5382, jointed together with solvent, on walls, including all necessary fittings & specials, bends, branches, sockets, clamps, pipe cutting and wastages, cutting and making good the walls, etc., all complete as directed by the Engineer-in-Charge. 40 R m
Supply and Fixing of Toilet Paper Holder with flat ressed type stainless steel, etc., all complete as directed by the Engineer-in-Charge. 6 Each
Supplying and Fixing of Urinal Partitions Plates with high density particle board of approved design,shape & colour, finished with high pressure laminate of approximate size 1000mm x 450mm x 25mm including necessary screws, fittings and fixures, etc., all complete as directed by the Engineer-in-Charge. 4 Each
Supplying, laying, testing and commissioning the following dia PVC pipes of 6 kg/cm² SWR grade and of approved make with rubber ring joints conforming to IS 5382, jointed together with solvent, in trenches and floors, including all necessary fittings & specials, bends, branches, sockets, pipe cutting and wastages, cutting and making good the floors, etc., all complete as directed by the Engineer-in-Charge
a) 75mm dia 14 R m
b) 110mm dia 20 R m
Cutting existing water line and jointing with new 40mm dia CPVC line including threading/screwing, alterations/additions if any with necessary specials required to connect the new line, etc., all complete as directed by the Engineer-in-Charge. 1 Each
Supplying, jointing, testing and commissioning, approved make 40mm dia GM body gate valves with screwed ends, etc., all complete as directed by the Engineer-in-Charge. 2 Each
Constructing, testing and commissioning brick masonry inspection chamber of size 455mm x 610mm (Clear inside dimension) and depth 450 mm, with sewer bricks having average compressive strength not less than 75 kg/cm² in cement mortar (1:4), C.I. cover with frame (Medium duty) 455 x 610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (Weight of cover 23 kg and weight of frame 15 kg), R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with CM (1:3), finish smooth with a floating coat of cement on walls and bed concrete, all as per standard design including cost of materials, labour charges, curing, etc., all complete as per specifications and as directed by the Engineer-in-Charge. 2 Each
Cutting into existing manholes/drains for connecting new drains, making good to pipe and rendering, cutting out existing benching for and forming branch channel (1/2 round or 3/4 section) in cement concrete 1:2:4 smooth finished, and reforming benching as required, etc., all complete as directed by the Engineer-in-Charge.
a) 100mm internal dia 2 Each
Blockwork with 200 mm thick precast cement concrete solid blocks conforming to IS 2185 (Part 1) having minimum average compressive strength of 4 N/mm² and density not less than 1800 kg/m³ built in cement mortar 1:6 (1 cement : 6 coarse sand) for walls at all levels including necessary formwork, curing, finishing, making or leaving holes & chases and making good, etc., all complete as directed by the Engineer-in-Charge. 6.6000000000000005 Cu m
Blockwork with 100mm thick precast cement concrete solid blocks conforming to IS 2185 (Part 1) having minimum average compressive strength of 4 N/mm² and density not less than 1800 kg/m³ built in cement mortar 1:4 (1 cement : 4 coarse sand) for walls at all levels including necessary formwork, curing, finishing, making or leaving holes & chases and making good, etc., all complete as directed by the Engineer-in-Charge. 72 Sq m
Supplying, fabricating and fixing second class hard wooden plain, solid, straight chowkats and frames, wrought framed, rebated on the solid, rounded or chamfered, put together with glue, pinned at joints and fixed to wall, etc., all complete as directed by the Engineer-in-Charge. Note: The timber in contact with masonry shall be treated with anti-termite paint. 0.4 Cu m
Supplying, fabricating and fixing in position 40mm thick flush shutter conforming to IS 2202 (Part I), block board solid core type with plywood face panels and type 1 decorative laminate min. 0.90mm thick on both sides, including provision of internal wood lipping, rebates, suitable blocks for taking mortice locks, latches or other fittings, fitting to frames/chowkats, etc., all complete as directed by the Engineer-in-Charge. Note: Fittings / hardware shall be paid separately. 11 Sq m
Supplying and fixing fiber glass reinforced plastic (FRP) door frames of cross section 90mm x 45mm having single rebate of 32mm x 15mm to receive shutter of 30 mm thickness. The laminte shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame, etc., all complete as directed by the Engineer-in-Charge. 30 R m
Supplying and fixing 30mm thick glass fibre reinforced plastic (FRP) panelled door shutter of approved make to door frames, made with fire retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS 14856, etc., all complete as directed by the Engineer-in-Charge. 10 Sq m
Supplying and fixing the following fittings / hardware of approved make and design to door with all required screws, bolts, nuts, washers, etc., all complete as directed by the Engineer-in-Charge.
a Polished brass barrel tower bolts 200 mm long with barrel of extruded sections of brass and rolled or drawn brass bolt conforming to IS 204 (Part 2) 10 Nos
b Brass sliding door bolt (Aldrop) 200 mm long with sand or die-cast brass hasp, staple (Bolt type) and rolled or drawn brass bolts conforming to IS 2681 5 Nos
c Extruded brass butt hinges 125 mm long with brass hinge pin, bright polished conforming to IS 205 15 Nos
d Polished extruded brass handles fabricated type 150 mm long conforming to IS 208 with continuous plate 10 Nos
e Floor door stopper of anodised aluminium alloy body and tongue (Anodic coating not less than grade AC 10 as per IS 1868) with hard drawn steel spring, overall length of cover plate 150 mm conforming to IS 1823 5 Nos
f Mild steel hold fasts conforming to IS 7196 5 Kgs
g Door closer hydraulically regulated, designation No 3, universal type, Aluminium (Die cast) body 10 Nos
h 4 levers Mortice lock with handle, vertical type, size 100mm Brass fancy type handles, polished bright 5 Nos
Supplying, fabricating and fixing powder coated alluminium louvered ventilator (Min. thickness of powder coating 50 microns) made up of aluminium extruded sections conforming to designaton 63400 of IS 1285 and of approved make, with frame of size not less than (63.50 x 38.10 x 1.70)mm, weighing not less than 0.9 kg/m and min. 5mm thick frosted/obscured glass strips fixed on 'U' channels with all necessary fittings and accessories, etc., all complete as directed by the Engineer-in-Charge. Note: The quoted rate shall be for the entire work and nothing extra shall be paid on this account. 6 Sq m
Supplying, fabricating and fixing powder coated aluminium (Min. thickness of powder coating 50 microns) work for doors, windows, ventilators and partitions with extruded built up standard tubular sections / appropriate Z or other sections of approved make conforming to designaton 63400 of IS 1285 and IS 733 including fasteners, EPDM rubber / neoprene gasket, snap beading for glazing / panelling, pivots or hinges, cleat angle, C.P. brass / stainless steel screws, etc., all complete as directed by the Engineer-in-Charge. Note: Beadings / glazing clips shall not be measured for payment. 2698.7225000000003 Kgs
Supplying and fixing particle board 12mm thick, interior grade, prelaminated both sides with decorative lamination including fixing to framework of suiatable size with fasteners, etc., all complete as directed by the Engineer-in-Charge. 280 Sq m
Supplying and fixing sheet glass not less than 4.80mm thick, ordinary quality conforming to IS 2835, exceeding 0.50m² in each pane including necessary materials, putty, sealants to keep the glass in position, etc., all complete as directed by the Engineer-in-Charge. 350 Sq m
Supplying and fixing figured,pin headed type glass not less than 5mm thick in partitions/louvers, ordinary quality conforming to IS 2835, exceeding 0.5 m² in each pane including necessary materials, putty, sealants to keep the glass in position, etc., all complete as directed by the Engineer-in-Charge. 20 Sq m
Supplying, fabricating and fixing powder coated alluminium (Min. thickness of powder coating 50 microns) door shutters made up of aluminium extruded sections conforming to designaton 63400 of IS 1285 and of approved make comprising of the following: a) Top member of size not less than (47.50 x 44.45 x 1.95)mm and bottom member of size not less than (83.50 x 44.45 x 2.00)mm. b) Intermediate member of size not less than (49.91 x 44.45 x 1.50)mm. c) Vertical members of size not less than (47.50 x 44.45 x 2.00)mm. b) Superior quality rubber glazing gasket and aluminium tapered glazing clips measuring around (19 x 17)mm, self interlocking, screwless snap on type for fixing glazing / panelling. c) 2 nos. of 150 mm long aluminium handles. d) PUSH/PULL stickers on appropriate sides. The rate is inclusive of all other necessary fittings like locks, pivots, floor springs, etc., all complete as directed by the Engineer-in-Charge. Note: Glazing / panelling shall be paid separately. 36 Sq m
Supplying, fabricating and fixing in position M.S. rolled sections to form the grider framed work such as grills, gratings, ladders,railings etc., with ends of bars shouldered and/or riveted, welded etc., of approved design using standard sections, including necessary cutting, welding, embedding in concrete, masonry, etc., all complete as directed by the Engineer-in-Charge. Note: The rate is including one coat of primer and two caits of enamel painting for full sections/surafce area 1890 Kgs
Supplying, fabricating and fixing powder coated aluminium glazed three track sliding windows (Min. thickness of powder coating 50 microns) made up of aluminium extruded sections conforming to designaton 63400 of IS 1285 and of approved make comprising of the following: a) Top, bottom and lock side sections of the shutter shall not be less than (39.4 x 17.7 x 1.2)mm and weighing not less than 0.43 kg/m. b) Interlock side section of the shutter shall not be less than (39.4 x 17.7 x 1.2)mm and weighing not less than 0.51 kg/m. c) Top and side sections of the frame shall not be less than (91.8 x 31.75 x 1.5)mm and weighing not less than 0.98 kg/m to accomodate the shutter section. d) Bottom section of the frame shall be with gutter and not less than (91.8 x 45.5 to 37.5 x 1.5)mm and weighing not less than 1.57 kg/m. e) Shutters are to be provided with minimum 5mm thick plain glass conforming to IS 2835 for two shutters and stainless steel fly proof mesh for one shutter fixed with good quality tapered aluminium interlocking screwless snap on type glazing clip not less than 0.90mm thick. The rate is inclusive of all necessary fittings / hardware like touch lock, EPDM gasket, rollers, handle etc., with any additional aluminium members if required to carry out the work as per specification, etc., all complete as directed by the Engineer-in-Charge. Note: The quoted rate shall be for the entire work and nothing extra shall be paid on this account. 64 Sq m
Supplying and fixing 10mm thick toughened glass in alluminium doors, partitions or similar works including fixing with necessary EPDM washers, etc., all complete as directed by the Engineer-in-Charge. 20 Sq m
Taking down the cement or cement lime plaster of any description including raking out joints,hacking for key,scrubbing down with water, etc., all complete as directed by the Engineer-in-Charge. 30 Sq m
Providing, applying and laying cement mortar (1:6) plastering 15mm thick on brick/concrete surfaces, finished even and smooth with trowel for internal walls etc., with necesary materials, labour, scaffolding, curing, tools and tackles, etc., at all heights, all complete as directed by the Engineer-in-Charge. 90 Sq m
Painting old plastered interior surfaces with two coats of low VOC premium plastic emulsion with acrylic base conforming to IS 15489, of approved make, colour, shade, tint & pattern at all levels, over a coat of approved alkali resistant primer including preparing the surface by removing loose dirt and any organic growth, smoothening the surface by using suitable emery paper, filling crevices and finishing even with white cement putty or Plaster of Paris, necessary scaffolding, etc., all complete as directed by the Engineer-in-Charge.
a) Walls 394.04 Sq m
b) For ceilings 79.5 Sq m
Painting steel surfaces of any description with two coats of synthetic enamel paint conforming to IS 2932, of approved colour and manufacture over a coat of approved zinc chromate primer including preparation of surface by wire brushing/sand papering and wiping the surface clean with mineral solvents to remove grease and hard marks etc., applying metal paste for steel surface before painting the first coat etc., all complete as directed by the Engineer-in-Charge. Top coat of desired shade shall be applied after the undercoat has thoroughly dried and rubbed with fine grade of abrasive paper to ensure smooth and even surface, free from brush marks, etc., all complete as directed by the Engineer-in-Charge. 90 Sq m
Painting wooden surfaces of any description with two coats of synthetic enamel paint conforming to IS 2932, of approved colour and manufacture over a coat of approved primer including preparation of surface by rubbing with fine grade of abrasive paper to ensure smooth and even surface, applying knifing paste filler putty before painting the first coat, etc., all complete as directed by the Engineer-in-Charge. 30 Sq m
Supplying and fixing roller blinds consisting of control unit ldler, head of rail, roller tube, bottom rail operating chain, brackets and clamps/nuts/bolts/of approved colour/pattern including necessary supporting hanger holders/screws and removal of existing blinders, etc., all complete as directed by the Engineer-in-Charge. The fabric shall be of approved colour, texture and finish. 90 Sq m
Supplying and fixing Plywood grade BWR, type BB of minimum 12mm thick, including removal of existing plywood whereever necessary, including screws, etc., all complete as directed by the Engineer-in-Charge. 60 Sq m
Supplying and fixing of 0.90mm thick decorative laminates type-I, or surface finish, colour and pattern as approved, etc., all complete as directed by the Engineer-in-Charge. 60 Sq m
Providing and applying Texture paint on newly plastered surfaces with approved make, colour, shade, tint & pattern at all levels, including preparing the surface by removing loose dirt and any organic growth, filling of cracks with white cement putty or Plaster of Paris, necessary scaffolding, etc., all complete as directed by the Engineer-in-Charge. 100 Sq m
Supplying and fixing solar control film minimum 25 micron reflective type to glass panes as per instructions of manufacturer, etc., all complete as directed by the Engineer-in-Charge. 70 Sq m
Supplying and fixing single sided 3M make frosted sticke/ film to be pasted on glass panes as per instructions of manufacturer, etc., all complete as directed by the Engineer-in-Charge. 150 Sq m
Sub Total of Part 'A' - Civil Works (Excluding GST)
Part 'B' - Electrical Works
1 Supply, fixing in flush with the false ceiling including suitable fixing arrangment using Chain links, testing & commissioning of recess mounting type square LED lighting fixture of wattage not exceeding 36watt made out of white powder coated CRCA housing/ aluminium housing, front frame with translucent /polycarbonate cover including control gear. The luminaire should have Lumen efficacy ≥100 lm/watt and lumen output not less than 3600lumens with PF >0.9 and Colour temperature shall be >5700K operating on single phase 230V voltage 50 Hz AC supply with voltage range 140-270V including necessary interconnections and other standard accessories complete in all respects and as directed by Engineer incharge. LED used in the lighting fixtures should be one of the approved make. LM79 certification for luminaires & LM80 certificate for LED shall be produced.The LED Light fixture shall be of Bajaj BZRSQL 36W LED GX WH/Equivalent model in other approved makes luminaries which meets the above technical specification. LED used in the luminaire should be one of approved make as per approved make list of HAL. 53 Nos
2 Supply and fixing on ceiling testing & commissioning of round type Recess mounted LED downlighter with aluminium die-cast body, finish with drop down PC diffuser to deliver low glare illumination with optimized heat sink for efficiant heat dissipation, wattage not less than 18W LED lighting fixture, lumens efficiency ≥ 100lm/w at luminaire level, effficent heat sink, Colour temprature shall be >6500K, operating on single phase 230V voltage 50 Hz AC supply with voltage range 140-270V. 79 certification for luminare & LM80 certificate for LED shall be produced. including control gear, power factor of control gear shall be >0.90. Bajaj make model no:Bajaj BGSLO Sleek Recess RD 18W WH LED/Equivalent model in other approved makes luminaries which meets the above technical specification. LED used in the luminaire should be one of approved make as per approved make list of HAL. 54 Nos
3 Supply, fixing directly to the ceiling/wall using suitable mounting arrangements testing & commissioning of surface mounting Decorative type 10W LED mirror light fitting, including driver, the driver shall have PF >0.9 and Colour temprature shall be >6500K, THD <20% operating on single phase 230V voltage 50 Hz AC supply with voltage range 140-270V including necessary interconnections between driver and lighting fixtures complete in all respect and as directed by EIC. The lighting fixture shall be Bajaj make Model-BCLSB 10W WH/Equivalent make in other approved makes. 4 Nos
4 Supply & fixing on existing 20 MM dia 1500mm length GI suspention pipe 1200mm sweep, Ceiling fans including fixing hardwares complete with blades, down rods and accessories etc, 230V single phase 50Hz AC supply. Minimum air delivery 210cu.m/min with service value 6.00 BEE. Five star rated with brushless direct current motor(BLDC) complete, erected in position with necessary flexible copper leads of required colour and with canopy, down rod 1500mm length, necessary rubber bushings, clamps nuts,bolts etc., complete in all respects and as directed by Engineer-in-charge. 23 Nos
5 Supply, installation, testing & commissioning of 300mm dia 900 rpm heavy duty exhaust fan of any approved make with louvers, connecting cord with 6A, 3 pin plug top and with all necessary accessories, including making wall openings and replastering to smooth finish with matching paint etc., complete in all respects and as directed by Engineer-in-charge. 6 Nos
6 Supply & fixing of TPN MCB DB & MCB
Supply,fixing the DB in flush with wall/ on wall/ on steel columns as per site requirement, testing & commissioning of the following factory built powder coated Double door MCCB/MCB DB of any approved make fabricated out of M.S. sheet steel enclosure & necessary cutouts for operating the MCB knobs & comprising of suitable rating tinned copper busbars & earthing bus with tapped holes including internal wiring with stranded copper PVC wires or suitable size copper strips, necessary M.S. angle supports for fixing, chipping the wall and replastering to smooth finish etc., wherever required as per site condition, complete in all respects, as directed by Engineer-in-charge and comprising the following as detailed below:
a) 4 Way vertical type TPN MCCB DB 1 No
b) 4 Way Horizantal type TPN MCB DB 2 Nos
c) 6 Way Horizantal type TPN MCB DB 3 Nos
d) 100A, 415V gr. 25KA, 4P MCCB DB 1 No
e) 32A, 415V gr. 4P MCB 5 Nos
f) 32A, 415V gr. TP MCB 12 Nos
g) 6-32A, 250V gr. SP MCB 78 Nos
Note: 1. All MCBs shall be suitable for inductive loads. 2. All MCBs shall be rated for 10kA breaking capacity. 3. All MCBs shall have overload and short circuit releases.
Wiring to light / fan points/ exhaust fan points/ 6A socket points from nearest DB in concealed wiring system as per site requirement (Refer Electrical tender drawing enclosed) using suitable size 2mm thick PVC conduit with necessary junction boxes, bends, reducers, collars, end caps etc., and wiring with 3 runs of 2.5sqmm FRLS copper conductor stranded PVC insulated 1100V gr. wire with ISI mark (One as earth conductor) including suitable size modular type MS concealed box as per site requirement with base plate, glossy finish front plate, angle holder with base etc., for housing switches, sockets, fan regulator etc. including supply of modular type switches, socket outlets, fan regulators etc., with necessary interconnections, chipping the wall & replastering to smooth finish by using chicken wire mesh wherever necessary complete in all respects as detailed below:
a) Wiring to single light point controlled by 1 No 6A, 250V gr. flush type modular SP switch complete in all respects. 5 Pts
b) Wiring to two light point controlled by 1 No 6A, 250V gr. flush type modular SP switch complete in all respects. 49 Pts
c) Wiring to fan point controlled by 1 No. 6A, 250V gr. flush type modular SP switch including providing 1No box type MS Fan hook in ceiling whereever required, 2 module type electronic five stepped speed regulator etc., complete in all respects. 23 Pts
d) Wiring to 6A common socket point controlled by 1 No 6A, 250V gr flush type modular SP switch including 6A 3 pin universal flush type modular socket complete in all respects. 5 Pts
e) Wiring to 6A, 3pin universal 250V gr. flush type modular Independent socket outlet point controlled by 2 No. 6A 250V gr. Modular type SP switch.complete in all respects. 42 Pts
8 Power point Point wiring
a) Wiring to flush type 16A Power socket outlets from the nearest DB in concealed/opened wiring system as per site requirement using suitable size 2mm thick rigid PVC conduit with all conduit accessories such as junction boxes, bends, reducers, clamps, collars, elbows etc., and wiring with 2 runs of 4 Sq.mm for phase and neutral and 1 run of 2.5 sq.mm for earthing FRLS multistranded copper PVC insulated 1100V gr Wire with ISI mark including suitable size modular type MS concealed/PVC box with base plate, glossy finish front cover etc., including supply and fixing of universal flush type modular 16A, 250V gr. power socket outlet & 16A, 250V gr. flush type modular SP switch with neon indicator including with necessary interconnections, chipping the wall & replastering to smooth finish by using chicken mesh wherever necessary complete in all respects & as directed by Engineer-in-charge. 10 Pts
Supply & laying in the already excavated cable trench/fixing on wall/duct wall with necessary M.S clamps / encasing in pipes etc., testing & commissioning of following size XLPE insulated Aluminium(Al) conductor 1.1KV gr., earthed Armoured(Arm) U.G cables as directed and as per technical specification and as detailed below. (Note:- Excavation, sand & Brick Protection, concrete cutting, reconcreting, casing pipes will be measured separately.)
a) 4C x 16 Sqmm.Al Arm LT cable. 100 Mtrs
b) 3C x 4 Sqmm.CU Arm LT cable. 100 Mtrs
10 Cable end terminations
Supply and connecting indoor type cable end joints for the following size 1.1 KV gr., Aluminum(Al) conductor XLPE insulated armoured(Arm) UG cables by employing necessary single compression glands, terminals, bolts & nuts etc., complete in all respects and as detailed below:
i) 4C x 16 Sqmm.Al Arm LT cable. 10 Nos
ii) 3C x 4 Sqmm.cu.Arm LT cable. 10 Nos
Supply and embedding on wall/floor/ceiling, 2mm thick following dia PVC conduit, including necessary conduit accessories like reducers, junction boxes, connector blocks, elbows etc., complete in all respects including chipping the wall/floor and replastering to smooth finish to match with the existing wall/floor finish using chicken wire mesh wherever necessary as per site condition and as directed by Engineer-in-charge.
b) 25MM PVC Conduit 200 Mtrs
c) 20MM PVC Conduit 100 Mtrs
12 Telephone Socket
a) Supply, Fixing, in flush with wall as per site condition, suitable size modular MS box with base plate, glossy front cover for supply and housing of 1 No. of Twin RJ-11 telephone socket outlets with shutter including necessary interconnections, chipping the wall and replastering to smooth finish to match the existing wall wherever necessary as per site condition. Complete in all respects and as directed by Engineer-in-charge. 30 Nos
b) Supply & drawing of 0.5 mm dia copper conductor PVC insulated 5 pair colour coded and twisted unarmoured telecommunication cables in the existing PVC conduit as per standard practice including necessary inter connections & end terminations. 400 Mtrs
c) Supply & fixing on wall/grouted to floor upto 1200mm above ground level as per site requirement using suitable size MS angle iron frame work finished with two coats of enamel spray paint over a good primer & providing 20 pair krone type telephone connector junction box including krone connector with necessary mounting frame housed in suitable size FRP box with hinged lockable cover complete in all respects. 2 Nos
13 Supply & fixing in flush with wall/on Aluminium partition as per site condition, testing & Commissioning of 1 Module RJ-45 sockets for Data points including supply of suitable size modular type MS concealed/open mounting box with base plates, front covers, etc., with necessary interconnections and chipping the wall, replastering to smooth finish etc., wherever required complete as directed by Engineer-in-charge. 70 Nos
14 Supply and drawing in the existing PVC conduits / wall / above false ceiling, Cat 6 UTP 4-Pair cable including necessary interconnections complete for LAN & Internet point as directed by Engineer-in-charge. 2500 Mtrs
15 Supply and fixing on wall/ partition wall using necessary mounting arrangements for 80x50mm size DLP-PVC adaptable trunking system including cover and with separation partition for laying power and Data/Telephone cables/wires with full top cover, necessary accessories such as end caps, flat angle, T joints, external/internal angle, flat junction, Body joint, cover joint, required cabling accessories etc., complete in all respects as directed by Engineer-in-charge. 50 Mtrs
16 Supply and fixing on wall/ partition wall using necessary mounting arrangements for 32 x 16 mm size DLP PVC adaptable trunking system with separation partition for laying power and Data/Telephone cables with full top cover, necessary finishing such as end caps, flat angle, T joints, external/internal angle, flat junction, Body joint, cover joint, required cabling accessories etc., complete in all respects as directed by Engineer-in-charge. 50 Mtrs
17 Design, Fabrication, Supply and fixing/grouting in wall of suitable size MS angle iron supports/ flat/ brackets as per site requirement for painting the same with two coats of synthetic enamel paint over a coat of zinc chromite primer for supporting the compressed air line complete in all respects and as directed by EIC/OIC. 10 Kgs
18 Supply & fixing on wall/column factory-built powder coated sheet metal enclosed using suitable angle iron frame work 16A 250V gr. 3Pin (P+N+E) Industrial Plug & Sockets and controlled by 16A 250V gr. DP MCB with DIN channel overload & short circuit protection & necessary interconnections complete as directed by Engineer in charge. 5 Sets
a) Supply, providing and fixing Cast Iron Pipe earth station confirming to IS 3043 complete with 2750mm long, 100 mm Inner Dia(ID),13mm thickness CI Pipe, with 2 part clamp made out of GI flat 50x6 mm continously welded around the pipe using cast iron welding electrodes as per drawing. The cost also incudes excavation for earth pit, providing & laying homogenous mixture of charcoal lumps, salt & sand all around the pipe as per specification, supplying and fixing of RCC Collar of size 450 mm dia, 450 mm height and 50 mm thick over Cement concrete base of minimum size 150mm width & 100mm thick all around below collar shall be provided using 1:2:6 CC after necessary excavation, refilling of soil, consolidating, ramming, leveling of soil etc., supplying & fixing the label board (MS Plate of size 300mmx200mmX2mm) welding to the elctrode complete as per specification, standard drawing, instructions of EIC. 1 No
b) Supply, fixing & connecting the 50X6mm(300sqmm) size G.I strip on wall / clamping to the existing duct wall / fixing on steel structures/ laying 2 ft. below the ground level including excavation, refilling, consolidation & levelling of soil after laying for interconnection between the earth pits and the LT panels earthing as directed by Engineer-in-charge. 10 Mtrs
c) Supply, fixing & connecting the 25x3mm size G.I strip on wall / ceiling / laying 2 ft. below the ground level including excavation, refilling, consolidation & levelling of soil after laying for interconnection between the earth pits and the DBs earthing as directed by Engineer-in-charge. 30 Mtrs
d) Supply and fixing on the wall 8 SWG GI wire complete with necessary interconnections using suitable bolts & nuts to effect proper earth continuity as per standard practice. 40 Mtrs
24 Disconnecting and removing existing lighting fixtures(75 Nos), fans(20 nos), smoke detectors with wiring(25 nos), conduits/casing capping(200 mtrs), connected cables(200 mtrs), LDBs( 05 nos),switch boards(20 nos) and handing over to the plant Engineering Department at Plant maintenance office MCSRDC Division including loading, transportation, unloading etc., complete in all respects. The scope also includes disconnecting the existing cables from panel, complete in all respects and as directed by the engineer-in-charge. 1 LS
1. The quantity indicated are only approximate.
2. The tenderers are requested to visit the site and acquaint themselves with the present conditon and quote accordingly.
3. No extra claims will be entertained at a later stage.
Sub-Total of Part 'B' - Electrical Works (Excluding GST)
Part 'C' - Fire Alarm Works
1 Supply, installation on wall Erection, testing & commissioning of Microprocessor based analog addressable type two loop fire alarm control panel with built in loop card and battery which shall have backup time of 24 hours. Panel shall have capacity to hook minimum 176 devices per loop i.e. 88 detectors & 88 modules, with LCD display, fully programmable from panel keypad with stage alarm facilities like hooter, fire / fault indicator, audio-visual signals, incorrect addressing, unauthorised device removal or exchange, battery charger. The battery charger shall have automatic boost and trickle charging arrangement. Including supply, installation and connectivity of Auto dialer with addressable control module main control panel with minimum 10 telephone nos.connectivity.The panel shall have option of being connected via TCP/IP i.e. networkable on LAN / WAN compliant. System shall be designed as per the technical specification and shall comply to EN54 / IS2189 /UL standards. 1 No
2 Supply & fixing of Addressable type multisensor detector with heat and smoke combination with base and inbuilt short circuit isolator or isolator mounted with the base or seperate isolator module to be provided for each detectors. complete in all respects as per technical specification and shall comply BS-5839/EN54/IS2189 standard for installation and product shall be UL / FM / Vds approved. 33 Nos
3 Supply & fixing directly to the ceiling at approx. 3 to 4 mtrs height testing & Commissioning of Analogue Addressable type heat detector with base and inbuilt short circuit isolator or isolator mounted with the base or seperate isolator module to be provided for each detector complete in all respects as per technical specification and shall comply BS-5839/EN54/IS2189 standard for installation and product shall be UL / FM / Vds approved. 1 No
4 Supply, fixing, testing and commissioning of Response Indicator to indicate the status of detectors above false ceiling as per the technical specification and shall comply to EN54 / IS 2189 / UL /Vds standards. 11 Nos
5 Supply and fixing on wall, testing and commissioning of Addressable type Manual Call point resettable type with inbuilt short circuit isolator as per technical specification and shall comply to BS-5839/EN54/IS2189 standard for installation and product shall be UL/FM/Vds approved. 2 Nos
6 Supply, erection on wall at approx. 4 mtrs height testing & Commissioning of Addressable type Audio Alarm unit (Electronic hooter) with strobe (Red Lens) with inbuilt short circuit isolator (in case short circuit isolator is not inbuilt, separate short-circuit isolator to be provided and the cost of same has to has to be included in the cost this item itself). It shall have built in facility to set the sound decibel and tone complete in all respects, as per technical specification and shall comply to EN54/ IS2189/ UL/Vds standards. 2 Nos
7 Supply, installation, integrating with the existing main FACP, testing & Commissioning of Auto dialer with addressable control module connected to main control panel including connected cabling/wiring complete in all respects, as per technical specification. 1 No
8 Supply, erection at approx. 6 mtrs height, testing & commissioning of fault isolator module for isolation of short circuit, with necessary interconnections complete in all respects, as per technical specification and shall comply to EN54 / IS 2189 / UL /Vds standards.(These isolator modules will be incorported as per the requirment at site.) 2 Nos
9 Supply, laying and fixing directly to the ceiling/on wall / above false ceiling existing pipe etc, testing & commissioning of 2 Core X1.5 sqmm copper XLPE /PVC insulated FRLS with ISI mark Un-armoured copper cable along with required accessories, terminations glands as directed by EIC to complete the installation as per the technical specification. 160 Mtrs
Sub-Total of Part 'C' - Fire Alarm Works (Excluding GST)
Total of (Excluding GST)
Grand Total (Including GST)
HINDUSTAN AERONAUTICS LIMITED
Facilities Management Division
Pre-Qulification Profile (To Be uploaded along with Part A)
Tender Ref No. or Contract No.: HAL/FMD/R-179/23-24
Name of Work: Refurbishing Works including Civil Interiors, Electrical and Fire Alarm System for CS Cell at MCSRDC Building, HAL (Bangalore).
Estimated Amount in Rs.: 7950000
Tender Notice Date : 21.03.2024
PROVISIONAL GST ID NO. for HAL 29AAACH3641R1Z3
Sl.No Description Details Enclosed / Not Enclosed Remarks
1 Name of the Individual / Firm / Company: * Mandatory Please Enter Name of the Individual/firm/company
2 Type of ownership PlsEnter Type of Ownership
If Other, please specify
3 Details of Constitution or Legal Status such as certificate of incorporation, shops and establishments, Contractor registration No etc., Pls enter Details of Constitution
4 Address for correspondence: Pls Enter Address
5 (a) PAN No.: Pls Enter Pan NO
5 (b) Service Tax Registration No
5 (c ) Goods and Service Tax ID No.
6 Contact details
Contact person name Please Enter Contact person Name
Mobile No. Pls Enter Mobile No
Ph. No. with STD code
FAX No. with STD code
7 Registered Contractor
If Registered Contractor with HAL Yes/ No Related Document to be Uploaded to eProcurement Portal * Category: E= 75 Lakhs - Lessthan= 100Lakhs F= 50Lakhs - Lessthan 75 Lakhs G = 25Lakhs - Lessthan 50 Lakhs H = 10Lakhs - Lessthan 25 Lakhs I = 5Lakhs - Lessthan 10 Lakhs J = 2Lakhs - Lessthan 5 Lakhs K = Lessthan 2Lakhs 0 7 E 1
Registration No. 199999 7 F 2
Category 200000 6 G 3
PEMD Amount ( If paid ) 499999 6 H 4
8 I.T Returns for past 03 years 999999 5 J 6
2023-24 Pls Select 'Yes' ' No' for IT Return for All Three years 1000000 4 K 7
9 Average annual financial turn over during the last 3 years, ending 31st March 2023 of the previous financial year [ should not be less than 30% of Amount put to tender] 4999999 3
YEAR TURN OVER IN Rs. Enclosed / Not Enclosed REMARKS 5000000 2
2022- 2023 Rs. Pls Enter Turn over in Rupees for all the 3 years 7499999 2
Average annual Financial turn over
Avg Annual Turnover criteria is not met 10000000 1
10 ESI & PF Nos with proof Nos Enclosed / Not Enclosed
ESI Registration No/. with proof if any Remarks If any
PF Registration No. with proof if any
11 Bank(s) details: [Copy of the cheque leaf to be uploaded]
Bank Account No. Related Document to be Uploaded to eProcurement Portal (Note Canceled cheque leaf to be uploaded)
Name of the Bank
Type of Account
12 Latest Bankers Solvency Certificate from Nationalized/ scheduled Bank issued NOT before 12 months from the last date of Tender submission solvency cal
Name of Bank & Branch Pls Enter Details to 'Name of the Bank' , 'Date of Issue','Value in Rs 1900-06-28T00:00:00Z 0 40000
Date of Issue 200000 40000
Value in Rs. 200001 150000
Solvency value is NOT as per NIT
13 Experience of having successfully completed similar works during last 7 years ending last day of previous month. [Latest work experience certificate may be uploaded] (i) THREE similar completed works each costing not less than the amount equal to 40% of the estimated cost. (ii) TWO similar completed works each costing not less than the amount equal to 50% of the estimated cost. (iii) ONE similar completed work each costing not less than the amount equal to 80% of Amount put to the tender. 500001 250000
Completed similar works during last 7 years Pls Select %of similar works completed during last 7 years 1000000 250000
Work NoI Type of Work: [ Incase of private works the same shall be supported with TDS certificate] Related Document to be Uploaded to eProcurement Portal 1000001 500000
Brief Description of Work: Please enter Details for Work No 1 2000000 500000
Completed value of Work in Rs. 2000001 1000000
Date of Commencement of Work 4000000 1000000
Date of Actual Completion of Work: 4000001 2000000
Work No II Type of Work: [ Incase of private works the same shall be supported with TDS certificate] Related Document to be Uploaded to eProcurement Portal 10000000 2000000
Brief Description of Work: Pls Enter Details for Work No II
Completed value of Work in Rs.
Date of Commencement of Work:
Date of Actual Completion of Work: work done
Work No III Type of Work: [ Incase of private works the same shall be supported with TDS certificate] Related Document to be Uploaded to eProcurement Portal 2555
Brief Description of Work: Pls Enter Details for Work No III
Completed value of Work in Rs.
Date of Commencement of Work:
Date of Actual Completion of Work:
14 Details of person holding the power of Attorney (If different from contact person)
Name Related Document to be Uploaded to eProcurement Portal
Mobile No. Pls Enter Details for Person holding Power of Attorney
Ph. No. with STD code
FAX No. with STD code
15 DECLARATION I
The document being viewed / downloaded from the website and having read & understood all the contents of the tender document mentioned under terms and conditions including price bid do hereby accept all the terms and conditions laid down in the said Tender document and will abide by the same on acceptance and ward of work.
16 DECLARATION II
I/We declare and confirm that - 1. All information and attachments submitted along with this offer are true and correct. 2. I/We are aware that any false information provided herein will result in the rejection of my offer. 3. I/We shall not make refund claims of expenditure incurred in processing this offer. 4. I / We aware that document sought only be uploaded for evaluation of offer. Pls Accept the Delaration II
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
raw.json
RAW_JSON
TN52.pdf
TENDER_DOCUMENT • 2.50 MB
179TBF.pdf
TENDER_DOCUMENT • 3.03 MB
179PQF.pdf
TENDER_DOCUMENT • 0.21 MB
electricaldrawing1.pdf
TENDER_DOCUMENT • 0.30 MB
electricaldrawing4.pdf
TENDER_DOCUMENT • 0.11 MB
electricaldrawing2.pdf
TENDER_DOCUMENT • 0.29 MB
179ECSForm.pdf
TENDER_DOCUMENT • 0.46 MB
179PB1.xls
TENDER_DOCUMENT • 0.13 MB
179UNDERTAKING.pdf
TENDER_DOCUMENT • 0.42 MB
179PBF.pdf
TENDER_DOCUMENT • 0.47 MB
electricaldrawing3.pdf
TENDER_DOCUMENT • 0.27 MB
179CHECKLIST.pdf
TENDER_DOCUMENT • 0.11 MB
179PQ.xls
TENDER_DOCUMENT • 0.36 MB
179AMD01.pdf
TENDER_DOCUMENT • 0.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .