Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹15.2 CrAccepted-Finance 5 MEERA BAI MARG LUCKNOW UTTAR PRADESH 261001 | SITAPUR | UTTAR PRADESH | 261001 | ₹15.2 Cr | L-1 | Accepted-Finance Document OK |
| 2 | L-2₹15.4 CrAccepted-Finance 53 VAISHAILI ENCLAVE SECTOR 9 INDIRA NAGAR LUCKNOW | LUCKNOW | ₹15.4 Cr | L-2 | Accepted-Finance Document OK |
| 3 | Rejected-Technical | - | - | Rejected-Technical Required work experience is not attached |
| 4 | Rejected-Technical JHARIA BENIGANJ HARDOI | BENIGANJ | HARDOI | UTTAR PRADESH | - | - | Rejected-Technical Similar nature work experience is not attached |
Tender Value
₹16.1 Cr
EMD Value
₹82.6 L
Closing Date
9 Mar 2026, 5:00 pmClosed
DDE/M, Mandi Parishad, Lko
Kisan Mandi Bhawan, Vibhuti Khand, Gomti Nagar Lko
Internal electrification, external electrification, fire alarm, PA system, fire fighting, CCTV, Lift, ventilation, construction of boring and 1 year operation at Kisan Agrimall, Vikalp Khand, Gomti Nagar, Lucknow
2026_RKUMP_1117272_1
E/M/325/2026-1036
Open Tender
Electrical Works
Vikalp Khand, Gomti Nagar
Please refer Tender documents.
2 documents required · 2 mandatory
₹29,500
DDE/M, Mandi Parishad, Lko
₹82.6 L
23 Apr 2026
20 Feb 2026
10 Mar 2026
20 Feb 2026
9 Mar 2026
20 Feb 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq . mm + 1 X 2.5 sq. mm earth wire
2 X 4 : sq. mm + 1 X 4 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
2 X 10 sq. mm + 1 X 6 sq. mm earth wire
4 X 10 sq. mm + 1 X 6 sq. mm earth wire
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 & 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying and fixing of following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 Amps switch
3 pin 5/6 Amp socket outlet
Extra for fixing the Louvers/ shutters complete with frame for exhaust fans of all sizes.
Supplying of following size exhaust fan complete with gravity louver and connection with 3 core flexible wire as required. 300mm EXHAUST FAN
Supplying and fixing following way ,single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
4 way Double door
6 way Double door
8 Way Double door
Supplying and fixing following rating, double pole, 240 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required
40 amps DP MCB
63 amps DP MCB
Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required
40 amps 4P MCB
63 amps 4P MCB
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB),having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. As required. 40 amps
Supplying and fixing following rating, 4 pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB),having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. As required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying, drawing, connecting and testing of 0.5 mm dia annealed copper conductor PVC insulated PVC sheathed telephone wire in existing conduit/wire way duct etc. as required of following sizes: 2 Pair (4 core)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required
3 Module
4 Module
6 Module
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required
Telephone socket outlet
RJ-45 Data Socket outlet
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 2 run of cable
Supplying and drawing co-axial TV cable RG-Grade , 0.7 mm solid copper conductor pe insulated shielded with fine tinned copper braid and protected with pvc sheath in the exsisting surface /reccessed steel /pvc conduit as required.
Supply and erection& erection of suitable 16 Guage M.S. box with 5 Amps rated terminal modules and covered with 5 mm thick perspex sheet/M.S. cover flush mounted in wall as required complete. 1O Pair Telephone junction box
Supplying,installation,testing and commissioning of Passive Infrared(PIR) technology based occupancy sensor having high preformance, non regulating programmable type, suitable for connected load upto 10Amp , for mounting height up to 2.8 mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming at site etc. completeas required.
Supply and fixing of IP 20, Front Lit, Mid Power SMD type LED Light, recess Surface mounting round 18 Watt to 20 Watt, Cut out Min 150 mm, Height Min 40 mmm LED Down Lighter having Powder coated die cast, aluminium housing with heat sink, High purity/transmisivity UV abilized Non yellowish, diffuser/ Reflector, for uniform light, distribution, detachable driver set, suitable for 24 Hr Continuous Operation, Complete in All respect
Supply & fixing of water tight-oblong 10 watt LED Bulkhead luminaire having pressure die cast housing with driver set confirming to IP65 and above protection, IK 08, High purity/ transmisivity UV Stabilized Non yellowish diffuser/ for uniform light distribution, detachable driver set, open and short circuit protection, suitable for 24
Supply and fixing of LED Tube Light with heavy duty Metal Box type Tube Light fitting 1x22 watt suitable for upto 1x 22 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended complete in all respect
Supply and fixing of LED Tube Light with heavy duty Metal Box type batten Light fitting 2x22 wall suitable for upto 2x22 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended Complète in all respect
Supply and fixing of 18-22W LED Batten fitting with Extruded Aluminuin housing, special polycarbonate diffuser for glare free light distribution and suitable mounting for on both surface & suspended, Compélete in all respect...
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. without charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Supply and laying of 25mm x 5mm copper strip at 0.50 meter below ground as strip earth electrode including connection / terminating with nut ,bolt spring washer etc. jointing shall be done by overlaping and with 2 sets of brass nut bolt&spring washer spaced at 50mm)
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required.
Jointing copper/G.I. tape (with another copper/GI tape, base of the finial or any other metallic object) by riveting/ nut bolting/ sweating and soldering etc as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run)
Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For vertical run)
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supply and Laying of Aluminium Conductor PVC insulated armoured served sheathed cables 1100V grade on cable tray as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.
10sqmm 2core
25 sq. mm 3-1/2 core
35 sq. mm 3-1/2 core
50 sq. mm 3-1/2 core
70 sq. mm 3-1/2 core
120 sq. mm 3-1/2 core
150 sq. mm 3-1/2 core
185 sq. mm 3-1/2 core
240 sq. mm 3-1/2 core
Supply and Laying of Aluminium Conductor PVC insulated armoured served sheathed cables 1100V grade at a depth of 750mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 400 sq. mm 3-1/2 core
6sqmm 3core
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kv grade as required.
6sqmm 2core
10sqmm 2core
25 sq. mm 3-1/2 core
35 sq. mm 3-1/2 core
50 sq. mm 3-1/2 core
70 sq. mm 3-1/2 core
120 sq. mm 3-1/2 core
150 sq. mm 3-1/2 core
185 sq. mm 3-1/2 core
240 sq. mm 3-1/2 core
400 sq. mm 3-1/2 core
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray With perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
225 mm width X 62.5 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 2.0 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
750 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
225 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 2.0 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
750 mm width X 75 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
225 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
225 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 2.0 mm thickness
Exhaust and Fresh Air Fan Sections : Supply, Installation, Testing & Commisioning of AMCA Certified (For Air and Sound Performance) tube axial flow fans of different capacities in standard GI/M.S. contruction as mentioned below. Entire fan model and AMCA Seal shall apear in techncial submittal of fan. All the fans shall be synthetic enamel painted/ hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at fan inlet. The electric motor coupler shall be IE-02 squirrel cage induction type conforming to IS-325, IP-55 rated with class `H' insulation. Motor shall be of high temperature resistance "Class H Smoke Spill" 250°C for 2 hours. Fans shall be EN 12101-3 Certified and CE/UL Listed for high temperature. Motor make shall be same as that mentioned on the fire certificate. Fan efficiency should not be less than 65%, and noise level should not be more than 70 db @ 3 m distance when measured under hemisperical reverberant room conditions. Quoted price shall be inclusive of sound attenuator at the outlet of the fan as shown in the approved shop drawings, all accessories like bird screens, vibration isolators,mounting brackets/feet/ duly enamel painted M.S structure etc. Fans mentioned as outdoor type shall be good for outdoor installation with proper cowl and mounting arrangement as per approved shop drawings. Fans shall be as per specifications and design drawings. Axial Flow Fans shall follow the design parameters as mentioned below: (Make- Kruger / greenheck / flaktwood / zeco /LTI /Nicotra /Systemair / Witt-India / airflow)
25000 cfm at 50 mm static (For Basement+LGF Fr.)
22000 cfm at 50 mm static (For Basement Fr.)
19000 cfm at 50 mm static (For Basement+LGF Ex.)
16000 cfm at 50 mm static (For Basement Ex.)
2000 cfm at 30 mm static (For Pump Room)
3500 cfm at 30 mm static (For Electrical Room)
9500 cfm at 30 mm static (For Staircase)
9000 cfm at 30 mm static (For Staircase)
6500 cfm at 30 mm static (For Liftwell)
6000 cfm at 30 mm static (For Liftwell)
2000 cfm at 30 mm static (For Liftwell)
Final CFD Analysis report should be done by Original Equipment manufacturer inorder to get actual jet fan quantity and jet fan positioning.
Supply, Installation, Testing and Commissioning of Logic Supervisory Controllers . The System should have Inbuilt Graphic Software to view the Basement Ventilation system including Sensors feedback, Actual reading, Fan command and running status through Graphic software.
Variable Frequency Drive: Supply, Installation, Testing & Commissioning of variable frequency drives for following Tube axial fan. Variable frequency drives shall be provided with necessary temperature sensors and controllers complete with control wiring in all respect as required and as per the specifications. The VFD shall exhibit IP-55 protection. The drives shall be suitable for the following motor rating. VFDs shall be housed in AHU/ FAN panels. (Make: Siemens/Schnieder/Danfoss/ABB/Fuji/Allen Bradley/Honeywell or equivalent)
Jet Fans: Supply, Installation, Testing and Commissioning of Ductless Ventilation System / Jet Fans as per the specifications and layouts, suitable for Normal Ventilation and Smoke Extraction Application in case of emergency i.e. 250 to 300 Deg C for 2 Hrs operation. The Dia of jet fans shall be 315 mm. Each fan shall be complete with motor and impeller. The complete fan shall be certified as tested for 300 Deg C for 2 hours operation. The Motor shall be suitable for operation on 415±10% Volts, 50 Hz, 3 Phase AC power supply. (For Car Parking of Basement) (Make: Kruger /Coolvent / united air-tech / constorium / witt-India / Fanair / ventilair / marut-air or equivalent)
CO-Sensors: (Make: Danfoss/Honeywell/Siemens or equivalent) Supply, Installation, Testing and Commissioning of CO-Sensors at Basement Floor Car Parking
Ducted Inline Type Exhaust fans : Supply,installation,testing and commissioning of ducted Inline type exhaust fans complete with motor ,fan, exhaust Louvers as per drawings and specifications. of following sizes :
1000 cfm at 30 mm static
500 cfm at 30 mm static
Propeller Type Exhaust Fans : Supply,installation,testing and commissioning of propeller type free discharge exhaust fans complete with motor , fan ,exhaust Louvers as per drawings and specifications of following sizes :
150 mm dia (free discharge)
100 mm dia (free discharge)
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
Thickness 0.63 mm (24 Gauge) Sheet
Thickness 0.88 mm (22 Gauge) Sheet
Thickness 1.00 mm (20 Gauge) Sheet
Dampers: Supply, Installation, Testing and Commissioning of GI volume control dampers complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
FIRE DAMPERS: Supply, installation, testing and commissioning of multi blade sleeve type combined motorised fire & smoke dampers with spring return actuator. The damper shall be of atleast 1.5 hr. fire rating. The damper shall be as per CBRI approval.The damper shall be constructed out of 16G galvanised sheet steel. It shall be complete with control panel, spring return actuator, sensor . Cost to include control cabling between firedamper control panel , actuator and fan starter panel for necessary inter-locking / for tripping of AHU fan motor.The fire dampers shall be installed at locations shown in approved shop drawings and as per specifications.Vendor to comply all Tender Specifications.
Smoke & Fire Dampers.
Control Panels with actuator suitable for 10-12 NM torque
BIRD SCREEN: Supply, installation, testing & balancing of factory made Bird screen made out of galvanized steel mesh in 20G having diamond pattern with GSS flanges and necessary cross bracings suitable for Fresh/ Exhaust air fans on terrace, complete as per specification & approved shop drawings.Vendor to comply all Tender Specifications.
Canvas Cloth: Supply, Installation, Testing and Commissioning of flexible canvass cloth connection at oulet of each Ducted Indoor Unit with zipper to facilitate temperature measurement
Supplying & fixing of powder coated extruded aluminium conoutinous Supply Grills with louvers and volume control dampers as per spesifications
Supplying & fixing of powder coated extruded aluminium conoutinous Return Air Grills with louvers but without volume control dampers as required.
Supplying & fixing of Supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring and removable core.
Supplying & fixing of Supply air diffusers of powder coated aluminium without aluminium volume control dampers with anti smudge ring and removable core.
Charges for making opening in RCC Slab and repairing of the same for Ducting and Piping. Upto 1.00 Sqm size
Charges for making opeing in walls for passing the Supply & Return Air Ducting and Piping
upto 0.50 Sqm size
from 0.51 Sqm to 1.00 Sqm size
Supplying Installation Testing and Commissioning of 5MP/6 MP IP IR Bullet Camera having following specifications, type of lens and features etc :- 1) Type of Camera: Bullet Camera 2) Image Sensor: 1/2.8" or better progressive Scan CMOS get color image even at night condition 3) Signal System: PAL/NTSC 4) Minimum Illumination: 0.006Lux@ F1.4, AGC ON, 0 lux with IR or better 5) Imaging: 1/3s to 1/30000s, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking. 6) On Screen Display: Camera should display Camera title, Date & Time in live & recorded video both. 7) Signal to Noise Ratio: > 50 dB 8) Lens Type & Focus: as given below. 9) Day & Night: True Day & Night High Performance Mechanical IR cut filter with auto switch, IR SourceInbuilt IR LED's with effective distance upto 50 Mtrs integrated IR and 30 Mtrs for colour view in night. 10) Video Compression (Minimum): H.265 or better, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 11) Wide Dynamic Range: WDR (120dB or more) 12) Digital Noise Reduction: DNR (2D/3D) On/Off 13) Streaming: Triple streaming, configurable 14) Video Streaming & Frame Rates: Triple streaming , configurable Main stream: 5MP/6MP @25/30 fps, Sub streams: D1@25/30 fps or better
15) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser 16) Profile Management: User configuration import, export 17) Security: User Authentication, Digital Water Marking 18) Onboard Storage: Camera should support built-in Micro SD/SDHC/SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card. 19) Recording Management: Format SD, overwrite, storage management, video to NAS device, 20) Edge Analytics: Tripwire, Intrusion, Motion Detection 21) Alarm Trigger : Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection 22) Alarm Support: It should have 1/1 Alarm In/ Out Port 23) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out Port for external Mic. and Speaker (As per site requirement) with G.711U/A / G.711Mu/ AAC/ G.726 audio compreesion 24) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast, 25) System Capability: ONVIF 26) VMS: Camera shall support open source VMS 27) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, account lockout, video encryption, IP/MAC filtering, HTTPS, trusted upgrade.
28) Ethernet: 1 RJ 45 10/100 Ethernet port 29) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE—to ensure continuous operation in the event of a failure in one power source. 30) Power Requirement: 12VDC/24V DC/PoE (802.3af)/ePoE 31) Enclosure: IP67 weather proof, IK10 32) Operating Condition: Ambient Temperature:- (-)05°C to 50°C, humidity 95% (max) (non-condensing) 33) IR life: 40000 hours or higher 34) Video Bit rate: 32 KBPS - 8 MBPS or better 35) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS 5MP/6MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized lens outdoor Bullet Camera.
Supplying Installation Testing and Commissioning of 5/6MP IP IR Dome Camera having following specifications and features etc :- 1)Type of Camera: Dome Camera 2) Image Sensor: 1/2.8" or better progressive Scan CMOS get color image even at night condition 3) Signal System: PAL/NTSC 4) Minimum Illumination: 0.008Lux@ F1.4, AGC ON, 0 lux with IR or better 5) Imaging: 1/3s to 1/30000s Shutter Support, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking. 6) On Screen Display: Camera should display Camera title, Date & Time in live & recorded video both. 7) Signal to Noise Ratio: > 50 dB 8) Day & Night: True Day & Night High Performance Mechanical IR cut filter with auto switch, IR Source- Inbuilt IR LED's with effective distance upto 50 Mtrs integrated IR 30 Mtrs for colour view in night. 9) Video Compression (Minimum): H.265 or better, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 10) Wide Dynamic Range: WDR (120dB or more) 11) Digital Noise Reduction: DNR (2D/3D) On/Off 12) Streaming: Triple streaming, configurable 13) Video Streaming & Frame Rates: Triple streaming , configurable Main stream: 5/6MP @25/30 fps, Sub streams: D1@25/30 fps or better 14) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser
15) Profile Management: User configuration import, export 16) Security: User Authentication, Water Marking 17) Onboard Storage: Camera should support built-in Micro SD/SDHC/SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card. 18) Recording Management: Format SD, overwrite, storage management, video to NAS device, 19) Edge Analytics : Tripwire, Intrusion, Motion Detection 20) Alarm Trigger : Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection 21) Alarm Support: It should have 1/1 Alarm In/ Out Port 22) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out Port for external Mic. and Speaker (As per site requirement) with G.711U/A/ G.711Mu/ AAC/ G.726 audio compression 23) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast, 24) System Capability: ONVIF 25) VMS: Camera shall support open source VMS 26) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, , account lockout, video encryption, IP/MAC filtering, HTTPS, trusted upgrade. 27) Ethernet: 1 RJ 45 10/100 Ethernet port
28) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE—to ensure continuous operation in the event of a failure in one power source. 29) Power Requirement: 12VDC/24VDC/PoE (802.3af)/ePoE 30) Enclosure: IP67 weather proof, IK10 31) Operating Condition: Ambient Temperature:- (-) 05°C to 50°C, humidity 95% (max) (non-condensing) 32) IR life: 40000 hours or higher 33) Video Bit rate: 32 KBPS - 8 MBPS or better 34) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS 5MP/6MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized lens Dome Camera.
Supplying Installation Testing and Commissioning of following Channel Network Video Recorder (NVR) with camera licenses to record for all channels having specifications and features etc as mentioned below : 1) Network Video Recorder Embedded/ Installed OS (Linux) along with Camera Licenses to record per NVR and to provide a live view, storage and simultaneously Multi-channel playback of all IP camera or more and must be ONVIF with minimum support of 384 Mbps incoming Bandwidth. 2) NVR should support video compressions : H.265 or better, H.264, MJPEG. 3) Must support 1 channel RCA Input, 2 channel RCA Output for Two-way Talk with G.711U/A, G.711u, PCM, G726 audio compressions. 4) Intelligent auto power on when power resumes after power outage. 5) Storage: It should support minimum 8 SATA Slots with 20TB capacity/ Slot and RAID support of RAID 0/1/5/6/10. 6) Connectivity Interface : 2 Nos. x 10/100/1000 Mbps Ethernet Ports, 1x RS485, 1x RS232, 1x eSATA Port 7) Backup Interface : Its should have 4 Nosx USB port (2x USB3.0, 2xUSB2.0) 8) Video Output Ports: 2x HDMI and 2 VGA 9) Alarm Ports: It should have 16/8 Ch In/ Out ports to connect various type of external sensors and output devices like hooter/ Siren etc. 10) Email & SMS Altert options: Option for SMS/ Email Alerts to minimum 5 designated mobile number for power failure, HDD failure, vandalism, tempring, network disconnection and panic
11) Web & Mobile Application: Web, Mobile app ( For iPhone, iPad, Android Phone) for alerts and viewing. 12) Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6, UDP, DHCP, DNS, SMTP, UPnP, IP Filter, PPPoE, FTP, DDNS, Alarm Server, IP Search, Multicast, Auto Registration, ONVIF (Profile T, Profile S, Profile G), CGI, SDK and OEM Cloud for remote monitoring without any public IP need. 13) Standards: CE, FCC, RoHS, BIS Certified 14) Power Supply : Should support AC100-240V, 50/60Hz Power supply. 15) Operating Condition : -5°C to 50°C, humidity 90%(max) (non-condensing) 16) The VMS application shall support all the features & functionalities of the offered cameras. 17) VMS should consist Licenses for all channels to record Cameras with General, motion detection, intelligent, alarm and POS recording modes. VMS should be provided with Camera Licenses , with no dependency of VMS licenses by binding with the MAC address of the cameras to achieve the functionality. 18) The NVR OEM shall be responsible for providing a mobile application compatible with both Android and iOS devices, enabling remote monitoring and playback of cameras/NVR footage. 19) The OEM must provide its own DDNS server hosted in India, eliminating the need for a public IP address for remote monitoring over the Internet. 20) Must support Continuous, Alarm, Motion, Instant, Panic Recording Mode
21) It should support Resolution: 32MP; 24MP; 16MP; 12MP; 8MP; 5MP; 4MP; 1080p; 720p; D1; CIF; QCIF 22) When alarm recording is enabled and an event occurs, you can click the alarm icon on monitoring page to view the alert details. The snapshot function is supported on monitoring and playback page 23) The Network Video Recorder (NVR) shall be configured to send email whenever a system message is created or an alarm event occurs. The email server shall be a valid SMTP server. Each recipient email address shall be configured to receive any combination of critical, warning, or informational messages or alarm notifications. When an alarm occurs, the email message includes the NVR name, time of alarm and a list of camera that is configured to record upon alarm 24) It should have Web and GUI interface. 25) Built-In Artificial Intelligence: NVR should have built-in AI :- - 2 Channel face detection and recognition, - Minimum 4 Channel perimeter protection, - Minimum 8 Channel Smart Motion Detection 26) Face Recognition Database capacity: It should support total Blacklist and Whitelist capacity of Minimum 20,000 Faces or more with Face Detection speed of 12 face images/sec and facility to add Name, gender, birthday, address, credential type, credential No., countries & regions and state to each face image.
33) VCA (Video Content Analytic): Should support multiple video contented analytics based on camera analytics 34) Analytics by NVR: Perimeter protection and face recognation 64 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16/25/36/64, 2nd screen: 1/4/8/9/16
Supply, installation, testing, and commissioning of Advanced software for Windows OS to control big CCTV systems containing multiple recorders and IP cameras. Make Honeywell /Impulse/Pelco/ Bosch / Axis/same as CCTV camera
Supplly, configuration, and implementation of camera channel licenses on VMS Software. Make Honeywell /Partizan / Bosch / Axis
S/I/T/C following capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications. 8TB (Terabytes)
Supply, Installation, Testing & Commissioning of 24-Port Gigabit PoE+ Smart Switch with 2 SFP Ports Make Netgear / Planet / Cisco
Supply, Installation, Testing & Commissioning of SFP Transceiver 1000 BASE-T Copper RJ45 GBIC Make Netgear / Planet / Cisco
Supply, Installation, Testing & Commissioning of 8-port Multi-Gigabit Smart Switchwith 10G Copper / Fiber Uplinks. Make Netgear / Planet / Cisco
Supply, Installation, Testing & Commissioning of 16-port Multi-Gigabit Smart Switchwith 10G Copper / Fiber Uplinks. Make Netgear / Planet / Cisco
LED Display S/I/T./C of following size LED display (LED monitor) industrial grade with 3840x2160 resolution or better, USB playback, bluetooth and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits or better, Video wall mode should be available, contrast ratio: 1200:1, OPS slot, viewing angle (H/V): 170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and programmable with remote (remote shall be supplied with system), Key Board, Optical Mouse, etc. as required. 55 inch or larger
Supply, Installation, Testing and Commissioning of Workstation PC with standard configuration, Keyboard: 12 function keys; Chassis: Workstation; Dual Graphics Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000; Hard disk: 1TB, 7200 RPM 3.5" SATA 6Gb/s Hard Drive; Operating system: Windows 10 Professional 64 Bit or latest with monitor, 22" LED Monitor. Make HP/CoreIP / Dell
Supply, Installation, Testing and Commissioning of Single Face Plate for mounting IO with required back box. Make Legrand/Digisol/Derwiser/Commscope
Supply, Installation, Testing and Commissioning of Cat6 Information Outlet (IO) Make Legrand/Digisol/Derwiser/Commscope
Supply, Installation, Testing and Commissioning of CAT6 UTP RJ-45 Patch Cords Solid Conductor 3ft Make Legrand/Digisol/Derwiser/Commscope
Supply, Installation, Testing and Commissioning of Unloaded CAT6 jack panel Make Legrand/Digisol/Derwiser/Commscope
Supply, Installation, Testing and Commissioning of 4 pair, U/UTP, 24 AWG solid copper CAT6 cable Make Legrand/Digisol/Derwiser/Commscope
Supply, Installation, Testing and Commissioning of Rack 6U, 600 x 500 mm pole mount welded section side integrated network rack Make Legrand/Dynamic Rack/Commscope
Supply, Testing, and Comissioning of 24U (600W/800D) floor mount rack with 1 Nos. Front Glass Door - 24U - 600W - Cam Lock - Ventilation - Duscky Fine Tex. - Assembly, 1 Nos. Rear Door - 24U - 600W - Cam Lock - Square Slot Ventilation - Duscky Fine Tex. - Assembly, 1 Nos. 3 Inch Castor Set, Four Fans, 4 Nos. Metal Cable Manager - 01U - Plastic Cable Loop's Mountable - Black Fine Tex. - Assembly, 3 Nos. Mounting Hardware Packet { Containg 1 Nos Each Of 3 } - 20 Set, 1 Nos. Power Distribution Unit - 06/16 Amp Indian-Standard - 10 Socket - Single Pole / Screw Mountable / 16 Amp MCB / Alternating Current - 16 Amp 3 Pin Plug with Power Cable 2.5 sq.mm 3 meter Length, 2 Nos. Metal Cable Channel - 100 mm Width - 800 mm Height - Pastal Fine Tex. - Assembly, 1 Nos. Earthing Strip - 150mm - Nickel Plating - Assembly, and IP20. Make Legrand/Dynamic Rack/Commscope
(A) Supplying Installation , testing and commissioning of electric driven Main Fire Pump suitable for automatic operation and consisting of following , complete in all respects , as required: (B) Horizontal type ,centrifugal pump of cast iron body & bronze impeller with stainless steel shaft , mechanical seal conforming to IS 1520. (C) Suitable HP squirrel cage induction motor ,TEFC, synchronous speed 1500 RPM , suitable for operation on 415 volts, 3 phase 50HZ, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with class 'F' insulation,conforming to IS -325. (D) M.S. fabricated common base plate , coupling, coupling guard , foundation bolts etc. as required. (E) Suitable cement concrete foundation duly plastered with anti vibration pads.
2850 lpm at 70 m Head
2280 lpm at 56 m Head
(A) Supplying Installation , testing and commissioning of , complete in all respects , as required: (Jockey Pump). (B) Horizontal type ,centrifugal pump of cast iron body & bronze impeller with stainless steel shaft , mechanical seal conforming to IS 1520. (C) Suitable HP squirrel cage induction motor ,TEFC types suitable for operation on 415 volts, 3 phase 50HZ, AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with class 'F' insulation,conforming to IS -325. (D) M.S. fabricated common base plate , coupling, coupling guard , foundation bolts etc. as required. (E) Suitable cement concrete foundation duly plastered with anti vibration pads.
180 lpm at 70 m Head
180 lpm at 56 m Head
Supply, installation,testing & commissioning of electrically driven Terrace Pump suitable for automatic/manual operation consisting of the following: Horizontal centrifugal end suction type fire pump running at 2900 r.p.m including bypass arrangement Gland arrangement shall be included Squirrel Cage,TEFC induction motor suitable for 415 10%V,3 phase.50 Hz A.C.supply of suitable H.P.for the above pump running at 2900 r.p.m conforming to IP 55 pralecting and class 'F' insulation. Common bed plate for mounting pump & motor of requisite strength manufactured out of M.S. channel as Jeer manufacturer's recommendation. 7.5 H.P,2900 RPM, 450 LPM, 35 Mtr HEAD (Horizontal End Suction) (01-Stage-1 orAs per manufacturer recommendation.
Poviding laying , testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/3589 i/c fitting like elbow, tees, flanges,tapers, nuts bolts , gaskets etc. in ground including welding excavations & providing cement concrete blocks as supports , anticorrosive tratment with coltar / asphalt tape as pr IS 10221, refilling the trench etc. of following sizes complete as required. 150 mm dia
Poviding laying , testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including welding ,fitting like elbow, tees, flanges,tapers, nuts bolts , gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint required shade complete as required :
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia (wall thickness 6.3 mm)
Supplying & fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Tpe- A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel
Supplying & fixing single headed External yard hydrant valve with 1 No.63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (Tpe- A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel
Supply and Installation weather proof lockable cabinet of size not less than 900X600X450 mm made out of 20gauge MS (as per BOQ) powder coated sheet of fully welded construction with hinged double front door partially glazed (3 mm glass panel).with locking arrangement, stove enamelled fire red paint (shade No. 536 of IS:5) including necessary locking arrangement and shall be painted with one coat of primer and two coats of synthetic enamel paint of approved shade. (External Cabinet).
Providing and fixing angle iron (40 mm x 40 mm x 5 mm) MS door frame with 16 G MS sheet, 900x2100 door capable of accommodating fire hose reel, landing valve, hose pipes, fittings & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) Cost of fire extinguishers not included in item rate.
Supplying ,fixing,testing and commissioning of butterfly valve of PN 1.6 rating ISI marked complete with ns, bolts, washers,gaskets conforming ti IS 13095 of following sizes as required :
65 mm dia
80 mm dia
100 mm dia
150 mm dia
Supplying ,fixing,testing and commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle , bronze/ gun metal seat, ISI marked complete with nuts, olts, washers,gaskets and conforming to IS 780 of following sizes as required :
100 mm dia
150 mm dia
200 mm dia
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to educe pressure at the outlet to the level of 3.5kg/cm2 complete as required :
Providing , intalllation, testing and commissioning of non - return valve of following sizes complete with rubber gasket, GI bolts, nuts, washers etc. as required:
80 mm dia
100 mm dia
150 mm dia
Providing , intalllation, testing and commissioning of Y-strainer fabricated out of 1.6 mm thick stailnless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.
80 mm dia
100 mm dia
150 mm dia
200 mm dia
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Stainless Steel (Grade 304)
Supplying and fixing first - aid Hose Reel with MS construction spray painted in post office red, conforming ti IS 884 complete with the following as required : 20 mm nominal internal dia water hose thermoplastic (Textile reinforced ) type-2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipments on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. pipe and socket. 30m
Supplying and fixing 63 mm dia, gun metal short branch pipe with 20 mm nominal internal diameter size nozzle confoming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Stainless Steel (Grade 304)
Supplying and fixing of fire brigade connection of cat iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
2 way -100 mm dia M.S. Pipe
4 way -150 mm dia M.S. Pipe
Supplying and fixing air vessel made of 250 mm dia , 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser , drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required.
Providing, fixing, testing and commissioning of Air vessel of 400mm dia for pressurization of fire system complete with valves at outlet / drain to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, outside with one coat of primer & two coats of synthetic enamel paint of approved shade complete as required to operate commonly main fire pump, sprinkler pump & jockey pump at drop of pressure, automatically at required pressure setting. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge. working pressure:- 7 kg/sqcm test pressure: 10 kg/sqcm (Make: Lifeguard/Chawla/Firex/Getech/Newage)
Providing fixing, testing & commissioning of 15 mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :
Pendent Sprinkler
Upright Sprinkler
Horizontal side wall spirinkler
Providing fixing, testing & commissioning of adjustable type rossette plate.
Providing fixing, testing & commissioning of Draw out connection 100 mm
Providing fixing, testing & commissioning of Foot Valve connection 150 mm
Providing fixing, testing & commissioning of Foot Valve connection 100 mm
Providing, fixing, testing & commissioning of Air release valve with 15mm dia
Providing and fixing 25 mm dia inspection & testing assembly with Test valve, union with corrosion resistant orifice & connection to drain
Providing and fixing of pressure switch in M.S. pipe line including connection etc. as required :
Providing and fixing flow switch in following sizes pipe including connection etc. as required : 100 mm dia
Providing and fixingin position the industrial type pressure gauge with brass valve complete as required.
Providing fixing, testing & commissioning of installation control valve of cost iron body , brass/bronze working parts comprising of water motor alarm , bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates , pressure gauges, emergency releases , stainer, pressure switch, cock valve complete with drain valve and bypass , test control box, ball valves, MS pipe of required size, flanges,orifice plate, gasket etc of following sizes as required :
100 mm dia
150 mm dia
Supplying , installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer , nipple, 2 side bracket, stockbar of following sizes complete as required.
Supplying , installation, testing & commissioning of deluge valve (to be used for water curtains) UL listed with wet pilot basic trim assembly for DVA with test and alarm, drip and drain valve with water motor gong complete as required .
80 mm dia
100 mm dia
Providing installation , testing & commissioning of water curtain nozzle 15mm dia nickel chrome plated brass, BSPT, K-factor as per design consideration complete as required.
Providing installation , testing & commissioning of welectric release trim assembly for deluge wall with two way solelnoid valve ,weather proof operation on 24 volts DC supply complete as required.
Supply, installation, testing and commissioningof ball valves with screwed ends confirming to IS 1703 -1977 with unions, etc.including all the necessary fixing materials complete. (Make: Kirloskar/Audco/Advance/Zoloto/Sant)
Providing, fixing, testing & commissioning of resilient rubber bellows single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe flanges. It should be complete as per manufacturer's specifications & as (Make: Resisto easy-flexo / d. wren)
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia
Supply and fixing of CO2 type Fire extinguisher 4.5kg. Capacity (ISI Marked is :15683)Complete with initial Charge and wall Bracked along with supply of all materials and labour for proper completion of work.
Supply and fixing of Fire extinguisher ABC Type 4.00kg.Capacity (ISI Marked is :15683)Complete with initial Charge and wall Bracked along with supply of all materials and labour for proper completion of work.
Providing and fixing Fire related signages printed on photoluminescent U1000 aluminium sheet of 1.0 mm (+-10%) containing Lumigen II as base chemical, covered under UV stablized coating and of appropriate size including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. complete in all respects as directed by Engineer-in-charge.
Providing and fixing of emergency exit light.
Providing and fixing mechanical foam type (ISI marked) fire extinguishers consisting of welded M.S. cylindrical body squeeze lever discharge valve 30 cm long high pressure discharge hose, discharge nozzle, suspension bracket as per ISI marked finished externally with red enamel paint and fixed to wall with brackets complete with internal charger. Capacity 50 lit.(Trolley mounted) (Make: Cease Fire / Lifeguard / Omex / Minimax/ Kalpex / Safeguard)
Ten loop panel
Four loop panel (Make: Honeywell/Johnson Control/Edward/ Siemens/Bosch or equivalent)
Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required.
Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required.
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.
Supplying, installation, testing & commissioning of addressable fire control module complete as required.
SITC of Intelligent Addressable, Supervised Monitor Module monitoring Potential-free, Normally Open Dry Contact input. The Monitor Module shall have operating temperature range from 0°C to 70°C and a humidity tolerance of up to 93% RH, Non-Condensing with weatherproof enclosure
Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required.
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.
Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required.
Supplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required.
Supplying, installation, testing & commissioning of digital audio amplifier 50 Watt, 25V rms operating at 240 volt AC supply complete as required.
Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. speaker cable Two pair, 2-core, 1.5 sqmm
Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.
(xi) Type of doors:- (a) Car: Power operated, centre opening horizontal sliding stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish). (b) Landing doors: stainless steel scratch proof . (xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car. (xiii) Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator. (xiv) Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 2 hours Fire rated, Overload detection and protection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder. (xv) In case of failure of ARD or other electronic Customization as per site requirement and proper completion of work.
Supplying, installation, testing and commissioning of Fully automatic(by Level Controllers with sensing probes) MBBR Technology based Sewage Treatment Plant process below and above ground with sewage and effluent handling capacity as given below. The STP shall be designed as water retaining structures in RCC or MS structure including necessary chemical dosing as required by the manufacturer's design. All the equipment, piping, pumps, blowers and electrical to be housed in a plant room nearby. Inlet, outlet overflow, vent, M.S. cover, drain channel with M.S. gratings sumps if required to be provided as per the site condition. (The total system to be designed as a Trunky project which includes detailed design engineering of civil/ structural /Biological/ Electro-Mechanical and treated effluent should meet the acceptable parameter The STP shall be designed based on the following Inflow parameters: * PH : 6.5 - 8.5 * BODs : 300-400 * S. Solids : 200 - 450 Mg/l * COD : 600 - 800 mg/L * Oil & Grease : 50-100 mg/L * PH : 6.0 - 8.5
* BODs :less than 20 mg/l * S. Solids :Less than 20 mg/l * COD :Less than 100 mg/l * Oil & Grease :Less than 5 mg/l Associated civil work for STP including foundation of pumps & equipment, M S structural work etc. is included in this scope Supply of all required Civil & Mechanical/Electrical shop drawings to be prepared by the contractor and approved by Project Manager. Contractor shall include all electrical mechanical items as required to operate the system automatically/ manually and also include in his rates level controller, electrical wiring cables earthing main control panel and connection to be various equipment’s, other accessories complete as required. Only main power supply with the earthing to be STP main control panel shall be provided by the owner through other agencies. STPshould follow all the concern Indian CPCB and Local norms and to be got approved from statuatory authority.Bypass arrangement shall be provided as shown in the drawings such that equalization tank pump can be used to pumpout sewage to external manhole incase of maintenance of STP. A S.T.P OF CAP - 65 KLD.
DC/RC Drilling including Hiring Transportaion, Erection, Dismantling with Loading and unloading of Rig and assosiated T&P complete in all respect including required all material labour & T&P etc.
Drilling up to 100 mtr. Deep (600mmØ)
Drilling from 101 mtr. To 200 mtr. Deep (600mmØ)
Electric logging of Borehole
Zone Testing for QPV Areas including all Materials, T&P and Labour ete for Completion of work.
Tubewell Assembly Supply of 300 mm dia M.S.E.R.W. 7.20 mm thick plain pipe. (As per IS 4270)
Tubewell Assembly Supply of 300 mm dia M.S.E.R.W. 7.20 mm thick slotted pipe (as per IS 8110)
Tubewell Assembly Supply of 200 mm dia M.S.E.R.W. 7.20 mm thick slotted pipe (as per IS 8110)
Tubewell Assembly Supply of 200 mm dia M.S.E.R.W. 7.20 mm thick plain pipe. (As per IS 4270)
MS Ring 200 mm ø MS. Ring made by 150 mm x 12 mm Flat
MS Ring 300 mm ø MS. Ring made by 175 mm x 16 mm Flat
Reducer 300 x 200 mm
MS clamp as per IS 2800 300mm ø MS. SI clamp
MS Bail plug As per IS 2800 200 mm ø M.S. Bail Plug
300 mm ø MS Well Cap
Lowering of above Tubewell assembly including Carting upto site and welding of parts complete in all respect with all required material T&P labour etc.
Lowering up to 100 Mtr. Deep 200 MMØ MSERW Plane/Slotted Pipe
Lowering from 101 mtr. To 200 mtr. Deep 200 MMØ MSERW Plane/Slotted Pipe
Lowering up to 100 Mtr. Deep 300 MMØ MSERW Plane/Slotted Pipe
Supplying and unconsolidated packing of gravel with suitable size
Development of Tube well by Air compressor 350 PSI complete in all respects
Development of Tube well by O.P. Unit 3 cusec
SITC of Energy efficiant AC Submmercible Pumping plant including Soft Starter with submercible flat cable of suitable length, main Piping & Valves with 8 Nos Column Pipes, Distance piece for Rising Main and Bypas side, NRV cum Pump and Column Pipe Jointer, Power wiring, Chemical earthing, Painting, wiring of pump house (internal & External) and Installation Job of Pumping Plant complete in all respect with all required material, T&P labour etc (80 mm Dia size Main piping And valves) 15hp
Supply and carting up to site of work of the following dia DI butterfly/sluice valves class I working pressure 10 Kg/cm2 confirming to IS: 780/1969 or its latest amendments including valve fittings & Dismantling Joints as per requirement F.O.R. destination and lowering them into the already prepared trenches fixing in position and jointing them with pipelines and testing etc. complete and also including supply of jointing materials etc. complete .including all taxes and insurance as per instructions of Engineer -in -charge. sluice valve - 80 mm dia
3Mtr. Long Column Pipe as per IS 1239 with Necessary packings and nut & Bolts etc.
Domestic Water Pump (Hydro pneumatic System With Variable Speed Pumps) Providing, fixing and testing of packaged fixed drive type skid mounted hydro pneumatic system comprising of :- Vertical, inline multistage centrifugal pumping set with stainless steel SS-304 stage casing and SS-304 impellers with stainless steel SS-316L shaft as per IEC standards and GJL250 cast iron suction & discharge casing, connected to TEFC ventilated induction motor of 2 pole, 2900rpm, suitable for 400/440 Volts, 3 phase, 50 Hz A.C. supply No. of Pumps: 3 (2 Working +1Standby)=1 set Pressure vessel of non corrosive FRP composite construction lined with NSF and/or FDA listed material, like high density polyethylene with fully replaceable polyurethane. Air cell burst pressure of minimum of 5 times the vessel operating pressure and cycle tested for 2,50,000 cycles. No. and capacity of Pressure Vessel – 01 Nos. x 200 Ltrs (Make: Lubi/Crompton/KSB)
Control Panel with programmable logic controller (PLC) for cyclic operation of pumps. Pump working sequence should change after every operation. Contractor overload relays and MCBs should confirm to IEC 898 – 1995/ specifications. Blinking indications for pumps start, trip, low level trip, health supply should be provided in the panel along with the ammeter & voltmeter. Control panel should also consist of cooling fan. Pressure switches bellow type fitted with micro switch and having maximum pressure and differential scale should confirming BS-6134 standards and IP55 protection class. Stainless steel suction and delivery header, ball valve on each pump on section delivery side, non return valves, Y stainer complete in all respect. Ball valves to be used should be Hot Pressed brass OT-58 with stainlesssteel ball and P.T.F.E seal and O-Ring. NRVs to be used should be with Springs and O-Ring arrangement. Complete set system to be mounted on a common base frame and shall follow following duty. For Domestic Water Supply Set of Two Pumps( 1Working+ 1 Standby) Capacity : app. 450 lpm Head : app. 60 m
Drainage Sump Pumps Submersible pumps for basement drainage & Pump Room drainage. Submersible single stage single entry pumps with C.I.body and C.I. two vane enclosed type impeller connected to TEFC submersible motor for 415 volts, 3 phase, 50 cycles including MCC panel with level controllers, auto control, sequential change over facility with one proper working at low level & two proper working at high level with an audible alarm including all interconnectivity cables, with both pumps connected to common outlet header including valves, non return valves, lifting chains etc. complete in all respect No. of Pumps: 2 (1 Working +1 Standby)=1 set Head : app. 21 m 1.5HP
Annunciation and indication panel Minimum 4 level Multi level indicators with magnetic type sensor probes complete Supplying, installing, testing and commissioning of annunciation and indication panel with interlocking arrangement complete in accordance to specification for level controller etc with control cabling from field to MCC as required. The system shall be complete to ensure automatic operation of pump in accordance to water level in respective tanks. Providing & fixing level controllers for water pumps to start/stop the pump at set level. Including wiring, cabling from pump to panel & all other accessories as required to operate the system automatically Providing & fixing pressure switch for water pumps to start/stop the filter feed pump at set pressure. Including wiring, cabling from pump to panel & all other accessories as required to operate the system automatically.
Compact Secondary substation-(CSS)
1000 KVA, 11/.433 KV Compact Secondary substations in accordance with IEC 61330, IP compete with enclosure typically divided into three compartments, non walkable type, with cooling arrangement as may be required, complete as following: Design, engineering, manufacture, transportation,installation,testing ,supply of 11 KV (System Voltage 12 KV, BIL 95 KVp) non-extensible compact substation (CSS) with RMU , Transformer & LV cubicle and RMU configuration & ONAN Loss as per IS 1180 Lvl-II transformer configuration is given under. RMU consisting 2 Nos Load break switch shall be 630A - 21KA/3 secs and 1 No. VCB/SF6 Breaker shall be 630 A - 21KA/3secs. The CSS shall be complete with mounting of foundation, earthing, cable termination, testing and commssioning. The CSS shall be from OEM of RMU and LV euipment. LV side of CSS shall be complete with LV enclosure, LT panel with Drawout type ACB on incomer & fixed type 4P, MCCB's on LT O/G side. OUTGOING I/C 2000A FP, ACB = 01 Nos. R,Y,B ON/OFF / Trip Indication CT 2000 A/5A,Class 1.0,15VA Multifuction metre to show KVA / KWH / V/A / PF BUSBAR 2000A FP AL. Busbar (Sanctioned By Mandi Parishad
S/I/T/C of Diesel generator set of 625kVA capacity (at 40o C Ambient temperature.), with electronic governor as per specification. Also the cost shall include the freight & insurance. DG to be of prime / continuous duty application as per IS. Alternator to be provided with Class 'H' insulation & with cable termination box for LT Cables. Alternator to be provided with local isolator indoor/ outdoor type for maintenance purpose. DG set coupling to be with double bearing type, teethed gear coupling. The cost shall also include Engine Control Panel (Type: EGCP / Power Command Control) with RS 485 comm. port. DG sets shall be suitable for auto synschronising with auto load sharing and remote monitoring & control arrangement compatible with the existing electrical system and Integrable with PLC of LT Panel with all required CT's and all gears including Electrical and Electronic controller. DG set must comply CPCB-IV Norms. DG Set with Alternator with Integral Acoustic Enclosure shall include the following components and accessories complete Residential type Silencer Anti‐Vibration Mounts (as required) Battery and Charger Dynamo (24V, 160AH minimum with leads 990 Ltrs MS Fuel Tanks with float/ limit switch indicator for low & high fuel level. Required number of contacts to be provided for connecting the level limit switch for indication in DG Control Panel. Fuel system consisting of Connect Fuel Pipe with MS "C" Class Pipe with flange & gas welded joint & pipe fittings like valves & other accessories and breather drain pipes if required need to be provided
MAIN ELECTRICAL PANEL SITC of LT switchgear panels suitable for 433 V. 3 phase. 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 65kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters. The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. Panel shall have Buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover ete and having following incomming and outgoing Air Circuit Breakers, microprocessor release for overload, short circuit, instantaneous & earthfault protection with Current & Voltage metering & LCD display.
Load Management through PLC Auto changeover, Buscoupler switching Electrial & Mechnical Interlocking. Synchonization through PLC Contactor for Synchronizing System Auto mains failure and auto load balancing, load management, auto On and Off of DG set as per load requirement. Buscoupler switching. Electrial & Mechnical Interlocking. BUSBARS 2000 Amp FP busbars of aluminium alloy as per SLD. OUTGOING 2 Nos. 800 Amp TP EDO ACB 65 KA,Microprossesor based, cable entry provision, and spreader links as per load schedule. 6 Nos. 630 Amp FP MCCB 50 KA Microprossesor based, cable entry provision, and spreader links as per load schedule. 2 Nos.400 Amp FP MCCB 50 ΚΑ Microprossesor based, cable entry provision, and spreader links as per load schedule. 3 Nos.315 Amp FP MCCB 36 ΚΑ Microprossesor based, cable entry provision, and spreader links as per load schedule. 9 Nos. 250 Amp FP MCCB 36 ΚΑ thermal-magnetic trip, cable entry provision, and spreader links as per load schedule.
5 Nos. 200 Amp FP MCCB 36 ΚΑ thermal-magnetic trip, cable entry provision, and spreader links as per load schedule. 4Nos. 125 Amp FP MCCB 36 ΚΑ thermal-magnetic trip, cable entry provision, and spreader links as per load schedule. 4Nos. 100 Amp FP MCCB 30 ΚΑ thermal-magnetic trip, cable entry provision, and spreader links as per load schedule. Cable alley (min. 600 mm), removable gland plates for bottom/top cable entry. RELAYS AS PER SLD
500 KVAR APFC PANEL (Sanctioned By Mandi Parishad
SITC of APFC panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power factor correction system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 50kA as per Single Line Diagram. The APFC Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. Panel shall have Buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers, microprocessor release for overload, short circuit, instantaneous & earthfault protection with Current & Voltage metering & LCD display.
Air Circuit Breaker with microprocessor release ge metering & LCD display, with ready to clsoe indicator, should have capability to communicate ON/OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics-lcw-65 KA (1 sec). MCCB, with microprocessor release with LSIG protection function LCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON/OFF/ Trip Status on Modbus/Ethernet. (65 KA les) Incoming 1 Nos. 800 Amp TP ACB 50KA R,Y,B Phase indication Lamp with control MCB On, Off, Trip Status Indication with control MCB Multifunction Meter BUSBARS 1 Nos. 1600 Amp TPN busbars of aluminium alloy as per SLD
FLOOR PANEL (Make: L&T/Schneider/Crompton /ABB/ Siemens/L&K) UPPWD and CPRI Approved Fabrication, Supply, Installation, Testing andcommissioning of 415V,50 Hz, 3 phase,4 wire, Self-standing/wall mounting, dust and vermin proof front operated, cubicle type distribution panel, made out of 16 SWG CRCA sheets fully compartmentalized, duly rust inhibited, degreasing, zinc phosphate, etc; siemens grey color powder coated, with hinged and earthed front doors, heavy-duty rubber gaskets, removable gland plates made out of 2 mm thick sheet steel, with appropriate rated TPN bus bars & earth bus. The bus bars should be of suitably rated aluminum, having specified normal and short circuit capacities and should be insulated with heat shrinkable color-coded PVC sleeves and DMC/SMC pillars/pillar type busbar supports. Dimensions, design, and fabrication of the entire panel should be as per Indian Standard. The panel drawings should get prior approval. Cable entry shall be according to site conditions. The panel comprising of the specific components as below
Space only for 2 Nos 10-80A three phase digital dual energy meter with NC contactor housed in a 14SWG MS sheet steel box with locking arrangement complete as require Space only for 12Nos 5-40A single phase digital dual energy meter with NC contactor housed in a 14SWG MS sheet steel box with locking arrangement complete as require The Main metering Panel shall be complete with all interconnections, risers, internal wiring, labels etc complete as required.
OUTGOING 4 Nos. 63 Amp, 10 KA, TP RCBO 30 ma(Type-B) The Lift panel shall be complete with all interconnections, risers, internal wiring, labels etc complete as required.
Ventilation Panel for Lower Basement (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved Supply, Installation, Testing and Commissioning of Programmable Logic controller as per the below description and the Tender technical specs: S/I/T/C of Universal Cntroller PLC with main componentslike power, processor, input & output cards, an open protocol for interface with the BMS systems. PLC to be complete as per specs installed inside the Main Switchgear MCC panel. The PLC shall have a FULL MODBus / BACnet / Eithernet interface facility with the Central BMS system. Scope to include the Gateway or converter, Communication module, HVAC software in addition to the standard features. Minimum Specifications of a Controller are as follows (but should meet the project needs): a) 10 x analogue inputs for CO or other pollutant sensors. (0-20mA, 0-5V and 0-10V input available). b) 16 x digital inputs for fan run/fault status. c) 1 x emergency alarm (i.e. fire) digital signal inputs. d) MODBUS, BACnet and other protocols for supervisory connection with BMS system. Built-in communication Modbus slave serial link by means of connection on integrated RJ45 port (Modbus master/slave serial link on integrated RJ45 port). e) 3 x analogue outputs available to speed control groups of JetVent Fans, central car park exhaust fan or supply fan. f) 3 x digital outputs to drive speed control relays (for 2 speed fans) or other systems according to pollutant concentration. a) Programmable Logic Controller with HVAC software b) Dedicated PWM programmable output.
c) Programmable Anagol Outputs/Inputs 0 - 10 V, 0 - 20 mA, 4 - 20 mA d) Display block for displaying the controller status: 4 LEDs (PWR, RUN, ERR and EXP) and 1 LED that can be used in the application. e) Connector for a removable terminal block (1) (2 terminals) for connecting the 24 V c/a supply.f) RJ11 connector marked Prg. Port for connecting a programming port g) Connector for a removable terminal block (1) (9/10 terminals), for connecting analog inputs. h) Connector for a removable terminal block (1) (16 terminals), for connecting discrete inputs. i) Connector for a removable terminal block (1) (5 terminals), for connecting analog outputs. j) RJ45 connector, marked MBS1, for connection to the Modbus™ bus. k) RJ45 connector, marked MBS2, for connection to the Modbus bus. l) Five Modbus bus and expansion bus polarization and line terminator adjustment switches. expansion bus. n) Connector for a removable terminal block (1) (2 terminals) to connect the power supply for a remote display unit TM168 GDBp(2). o) Connector for a removable terminal block (1) (5 terminals), for connecting 3 discrete relay N/C outputs. p) Connector for a removable terminal block (1) (6 terminals), for connecting 4 discrete relay N/C outputs. q) Connector for a removable terminal block (1) (3 terminals), for connecting the discrete relay C/O output. r) Display with 6 command buttons for setting the controller parameters s) logic controllers are mounted as standard on a 35 mm DIN rail.
DOL / SD starter as per HP gratings given. Terminal block for power distribution as required. Contactor, over load relay with built in single phasing protection. Phase indicating lights and indicating light for `ON’ status.144 mm x 144 mm voltmeter and digital ammeter. Time delay relay for delayed automatic restart of motor. Wiring for microswitch for stopping the fan when fire damper closes (in case of Fire operation only).For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. MCCB/MPCB shall be Type 2 Co-ordinated with the Motor starter. Degree of Protection for the Outdoor starter panel shall be IP 55. The number of control panels shall be as follows. MCCB suitable for, upto 7.5 HP , 4P motor with DOL starter (Car park Exhaust )
MCCB suitable for 10 HP, 4P motor with STAR DELTA starter (Car park Exhaust & Fresh Air )
Ventilation Panel for Uper Basement (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved Supply, Installation, Testing and Commissioning of Programmable Logic controller as per the below description and the Tender technical specs: S/I/T/C of Universal Cntroller PLC with main componentslike power, processor, input & output cards, an open protocol for interface with the BMS systems. PLC to be complete as per specs installed inside the Main Switchgear MCC panel. The PLC shall have a FULL MODBus / BACnet / Eithernet interface facility with the Central BMS system. Scope to include the Gateway or converter, Communication module, HVAC software in addition to the standard features. Minimum Specifications of a Controller are as follows (but should meet the project needs): a) 10 x analogue inputs for CO or other pollutant sensors. (0-20mA, 0-5V and 0-10V input available). b) 16 x digital inputs for fan run/fault status. c) 1 x emergency alarm (i.e. fire) digital signal inputs. d) MODBUS, BACnet and other protocols for supervisory connection with BMS system. Built-in communication Modbus slave serial link by means of connection on integrated RJ45 port (Modbus master/slave serial link on integrated RJ45 port). e) 3 x analogue outputs available to speed control groups of JetVent Fans, central car park exhaust fan or supply fan. f) 3 x digital outputs to drive speed control relays (for 2 speed fans) or other systems according to pollutant concentration. a) Programmable Logic Controller with HVAC software b) Dedicated PWM programmable output.
c) Programmable Anagol Outputs/Inputs 0 - 10 V, 0 - 20 mA, 4 - 20 mA d) Display block for displaying the controller status: 4 LEDs (PWR, RUN, ERR and EXP) and 1 LED that can be used in the application. e) Connector for a removable terminal block (1) (2 terminals) for connecting the 24 V c/a supply.f) RJ11 connector marked Prg. Port for connecting a programming port g) Connector for a removable terminal block (1) (9/10 terminals), for connecting analog inputs. h) Connector for a removable terminal block (1) (16 terminals), for connecting discrete inputs. i) Connector for a removable terminal block (1) (5 terminals), for connecting analog outputs. j) RJ45 connector, marked MBS1, for connection to the Modbus™ bus. k) RJ45 connector, marked MBS2, for connection to the Modbus bus. l) Five Modbus bus and expansion bus polarization and line terminator adjustment switches. expansion bus. n) Connector for a removable terminal block (1) (2 terminals) to connect the power supply for a remote display unit TM168 GDBp(2). o) Connector for a removable terminal block (1) (5 terminals), for connecting 3 discrete relay N/C outputs. p) Connector for a removable terminal block (1) (6 terminals), for connecting 4 discrete relay N/C outputs. q) Connector for a removable terminal block (1) (3 terminals), for connecting the discrete relay C/O output. r) Display with 6 command buttons for setting the controller parameters s) logic controllers are mounted as standard on a 35 mm DIN rail.
DOL / SD starter as per HP gratings given. Terminal block for power distribution as required. Contactor, over load relay with built in single phasing protection. Phase indicating lights and indicating light for `ON’ status.144 mm x 144 mm voltmeter and digital ammeter. Time delay relay for delayed automatic restart of motor. Wiring for microswitch for stopping the fan when fire damper closes (in case of Fire operation only).For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. MCCB/MPCB shall be Type 2 Co-ordinated with the Motor starter. Degree of Protection for the Outdoor starter panel shall be IP 55. The number of control panels shall be as follows. MCCB suitable for, upto 7.5 HP , 4P motor with DOL starter (Car park Exhaust )
MCCB suitable for 10 HP, 4P motor with STAR DELTA starter (Car park Exhaust & Fresh Air )
FIRE PANEL
BUSBARS Electrolytic high conductivity aluminium three phase busbars rated at 200 Amp having a maximum current density of 8 amp per sq mm suitable to with stand symmetrical fault level of 50 kA at 415 volts. Section -1 OUTGOING 10No. 40 Amp, 25KA, TPN MCB complete having with KWH meter
Supply and Laying of 3 core stranded Aluminium Conductor XLPE (Cross linked polyethylene) insulated PVC bedded, galvanized flat steel strip armoured cables confirming to I.S. 7098 (Part II with latest amendments) 11 KV grade at a depth of 900 mm below ground level over a cushion of 100mm thick fine rever sand all around and protected with well burnt bricks on sides and on top put across as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 240 sqmm 3 core (Make: Polycab/Havells/RR Kabel/KEI/Finolex
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required. 240sqmm
Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable with following size of 3 Core XLPE aluminim conductor cable of grade 11 kV as required: 240sqmm
Supply installing testing & commissioning of out door type street light feeder pillar (Distribution Panel) compartmentalised design, dust tight & vermin proof made out of 14 gauge M.S. sheet, stove powder coated complete as required with following incomming & outgoing as per detail below. Incoming 100 Amp. 10 KA FP MCCB 1 No. Suitable contractor and timer for down & dusk 100 Amp. TPN Alu. Bus bar Outgoing 25Amp 10KA SPMCB 6No. 25 Amp. 10KA SP MCB 6 No. (Make: L&T/Schneider/Crompton/ABB/Siemens/L&K) UPPWD and CPRI Approved .
Supply and fixing of 6 mtr. G.1. Octagonal pole of approved make (top dia 70 mm, Bottom dia 135 mm & Base plate 16 mm thick) having 3 mm, thickness with single arm bracket length of I mtr. length in 1:2:4 RCC foundation bolt including the cost of foundation, excavation & back filling and Required T & P complete in all respect.
Supply and fixing of LED Street light Fitting with mandatory driver set, having die cast aluminium body with toughend glass/ UV stabilized PC Cover and lenses suitable for 30 Watt to 50 Wart, Confirming to , and IK07 and above, protection
Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminium housing with toughend glass UV stabilized PC Cover and lenses built with mandatory driver set suitable for 70 to 90 Watt. Confirming to IP 65/66, IK 07 and above protection.complete in all respect
Supply and fixing of decorative 8 to 16 Watt LED bollard luminaire with Base Plate made of powder coated die cast aluminium and extruded Al. housing with UV Stablized PC diffuser, SMD LEDS. Electronic driver set, confirming to IP 65/66 and IK 07 and above protection, 600-800mm height, complete in all respect.
Supply & Testing of approx 18 to 21W recessed panel light ,powder coated Aluminium housing with CCT 3000±500k, shall have minium CRI of 80 & PF minimum 0.95 with High quality PMMA diffuser with highly reflective light guiding plate for glare free & uniform light distribution Light Transmissiondiffuser. Operational range 200-270 VAC. LED shall be from Approved Make only. % THD shall not exceed 10% .surge protection minimum 2.5kv. . Lumen package shall be 80 L/Watts minimum.
Supply and Installation of PROFILE LIGHTS WITH LED STRIP indoor, 24W / 5meter (4" THICK)including driver and necessary fixing accessories as required (Make: Wipro/Trilux/ Philips/LT/Havells/ Bajaj or equivalent) Sanctioned by Mandi Parishad
Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge.
Supply of tool kit with 1 pair 11 KV rubber hand gloves as directed by Engineer Incharge.Sanctioned by Mandi Parishad
Supplying & fixing standard shock treatment charts in English & Hindi duly framed and covered with glass as directed by Engineer Incharge.
Providing Safety mat made of elastomeric polymers Material (Class B) 1.2 M wide with thickness 2.5 mm to withstand 12KV dielectric strength AS PER relevant IS Code
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Operational cost of facility including 2 electricians, 1 mechanical operator and 2 Fire man
(A) Supplying Installation , testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following , complete in all respects , as required: (Diesel Driven Pump). (B) Horizontal type ,centrifugal pump of cast iron body & bronze impeller with stainless steel shaft , mechanical seal conforming to IS 1520. (C) Suitable HP , 1800 RPM water cooled with radiactor , diesel engine conforming to relevant IS standard complete with auto statring mechanism, 12/24 volts electric staring equipment, diesel tank , exhaust pipe extended upto 0.6 mm thick aluminium sheet cladding , residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in event of fault with audio indications, painted with post office red colour etc. as required. (D) M.S. fabricated common base plate , coupling, coupling guard , foundation bolts etc. as required. (E) Suitable cement concrete foundation duly plastered with anti vibration pads.
2850 lpm at 70 m Head
2280 lpm at 56 m Head
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 8.39 MB
BOQ_2079364.xls
BOQ • 3.37 MB
TendNotice2T.pdf
Tender Documents • 8.37 MB
Download all tender documents and submit your bid