Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.9 LAccepted-AOC OLD JAIL ROAD NEAR JILA GARDEN RAJKOT 360001 | RAJKOT | GUJARAT | 360001 | L1 | Accepted-AOC work order | |
| 2 | L2₹46.9 L+₹1.0 L (2.23%)Rejected-Finance 801 VENUS BENECIA PAKVAN DINING LANE OPP RAJPATH CLUB S G HIGHWAY BODAKDEV AHMEDABAD 380053 | AHMADABAD | GUJARAT | 380053 | L2 | Rejected-Finance L2 | |
| 3 | L3₹52.8 L+₹6.9 L (15.1%)Rejected-Finance 107 265 BRAHAMA NAGAR KANPUR UP 208012 | KANPUR NAGAR | UTTAR PRADESH | 208012 | L3 | Rejected-Finance L3 | |
| 4 | L4₹54.2 L+₹8.3 L (18.1%)Rejected-Finance C 5 26 4 4 NEELGIRI ASSOCIATION BELAPUR ROAD SECTOR 5 CBD BELAPUR NAVI MUMBAI MAHARASHTRA 400614 | THANE | MAHARASHTRA | 400614 | L4 | Rejected-Finance L4 |
| Sl No | Description | Qty | Unit | DOSHI ELECTRIC ENGG. CO. L1 | POWER AUTOMATION AND CONTROLS L4 | Awasthi Electric Works L3 | ABHISHEK INTEGRATIONS LIMITED L2 |
|---|---|---|---|---|---|---|---|
| 1.10 | Supply,Installation,Testing and Commissioning of outdoor compact substation comprising of following along with (i)11kV, 630A, Horizontal Draw Out VCBs(3 Nos-One incomer and two outgoings) with 230V AC Motor Operated Spring Charging Mechanism with 24V DC Closing /Opening Shunt trip coils,Auxillary switch, Mechanical On/Off Push Button, mechanical Operating Counter with metering Cubical, Auxiliary Relay, Under Voltage Relay, 8 Window Annunciator,Battery Power Pack with 7AH Battery & in built charger for 24V Circuit,CTs,PTS,Protection relays,Indicating lamps.
(ii)250 KVA, 11/0.433 KV, 3 Phase, 50HZ, ONAN Cooled Oil immersed Copper Wound Step Down “BIS Marked ” Transformer Complete with first filling of IS:335 ISI Marked Filtered & Dehydrated Transformer Oil, having 7 position Off-Circuit tap changer withtapping range +7.5% to -7.5% in steps of 2.5% each with all standard fittings & accessories including OTI, WTI & Marshalling Box .The Transformer as per comply with BIS-1180(Part-1)2014 EEL- 3 with amendment no.- 4 and Losses @50% Load - not more than 864W and Losses @100% Load - not more than 2488W.
(iii)LT Panel comprising of LV Side Incomer – 01 No,400 Amp 4 Pole 35 KA four ploe 415V MCCB with thermal magnetic
based release with O/L & S/C protection, RYB Indication Lamp,,Ammeter,Voltmeter - 500A/5A LT CT Cl:1.0.
(iv)Enclosure Section:Space Heater with ON/OFF Switch and Thermostat, Single phase switch with socket, LT Cubical illumination Lamp with Door Limit switch and MCB’s for AC / DC Control,MS Steel Sheet enclosure suitable for Outdoor Installation with MS base channel,Provision for receiving Incoming cables through Bottom entry and out going through Bus bar to Transformer panel, Excluding Termination Kit & Glands,Provision for receiving Incoming through bus duct by bus bar and Outgoing thro cable box bottom entry Excluding Termination Kit & Glands,Bus bar and earth bus of adequate rating,Paint shade: Siemens Grey ( RAL 7032).
(v)Providing RCC foundation suitable for the structural load of the compact substation,considering the site soil bearing capacity and as per OEM recommendations with provision for cable entry and foundation shall be at suitable height above ground level to avoid water entry.
(vi)Provision of roofing and supporting steel structure suitable for the compact substation.
(vii)All other miscellaneous works and internal connections etc for sucessful commissioning of the installation. | 1 | Job | 29,50,000 ₹29,50,000 | 31,70,000 ₹31,70,000 | 31,05,000 ₹31,05,000 | 28,98,000 ₹28,98,000 Lowest |
| 1.20 | Supply of HT Three Core Power Cables of size 3 Core 120 sq.mm - Aluminium Conductor A2XFY 11 KV Earthed Cables with Stranded Compacted Circular Aluminium Conductor, Conductor Screen with Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with Extruded Semi Conducting Compound in Combination with Copper Tape, Cores Laid Up,Innersheath of PVC, Galvanised Steel Flat Strip Armoured, & Overall PVC Sheathed Cable Conforming to IS 7098 (Part-2) 2011 with upto Date Amendments | 200 | Meters | 1,200 ₹2,40,000 | 1,000 ₹2,00,000 Lowest | 1,400 ₹2,80,000 | 1,001 ₹2,00,200 |
| 1.30 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 11 KV grade upto 120 sq.mm direct in ground including excavation,sand cushioning,protective covering,refilling the trench etc as required. | 40 | Meters | 500 ₹20,000 | 350 ₹14,000 | 560 ₹22,400 | 180 ₹7,200 Lowest |
| 1.40 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 11 KV grade upto 120 sq.mm in the existing RCC/HUME/METAL pipe as required. | 80 | Meters | 80 ₹6,400 | 300 ₹24,000 | 100 ₹8,000 | 30 ₹2,400 Lowest |
| 1.50 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 11 KV grade upto 120 sq.mm in the existing masonary open duct as required. | 80 | Meters | 60 ₹4,800 | 250 ₹20,000 | 80 ₹6,400 | 30 ₹2,400 Lowest |
| 1.60 | Supply of LT Power Cables - Aluminium stranded conductor A2XFY, XLPE Insulated, Cores Laid Up, PVC Innersheathed, Armoured with galvanised steel strip, Extruded PVC Type ST2 Outer Sheathed, 650 V(Conductor to earth)/1100 V(between conductors) grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.
3.5 core 400 sq.mm | 200 | Meters | 2,000 ₹4,00,000 | 1,911 ₹3,82,200 Lowest | 2,450 ₹4,90,000 | 1,955 ₹3,91,000 |
| 1.70 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 1.1 KV grade and size above 185 Sq.mm and upto 400 sq.mm direct in ground including excavation,sand cushioning,protective covering,refilling the trench etc as required. | 20 | Meters | 500 ₹10,000 | 350 ₹7,000 | 500 ₹10,000 | 180 ₹3,600 Lowest |
| 1.80 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 1.1 KV grade and size above 185 Sq.mm and upto 400 sq.mm in the existing RCC/HUME/METAL pipe as required. | 100 | Meters | 100 ₹10,000 | 300 ₹30,000 | 150 ₹15,000 | 80 ₹8,000 Lowest |
| 1.90 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 1.1 KV grade and size above 185 Sq.mm and upto 400 sq.mm in the existing masonary open duct as required. | 50 | Meters | 80 ₹4,000 Lowest | 250 ₹12,500 | 120 ₹6,000 | 80 ₹4,000 Lowest |
| 2.00 | Laying and fixing of one number PVC/XLPE Insulated PVC sheathed power cable of 1.1 KV grade and size above 185 Sq.mm and upto 400 sq.mm(Clamped with 40 X 3 mm MS flat clamp) on wall surface as required. | 10 | Meters | 200 ₹2,000 | 350 ₹3,500 | 250 ₹2,500 | 80 ₹800 Lowest |
Tender Value
₹57.6 L
EMD Value
₹1.7 L
Closing Date
2 Mar 2026, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Manager(EE), Juhu Airport,Mumbai-56
Manager(EE), Juhu Airport,Mumbai-56
Provision of Redundant Power Supply and Other Works in Transmitting Station at Andheri West
2026_AAI_261876_1
AAI/WR/M(E-E)/JUHU/e-06/25-26
Open Tender
Electrical Works
Item Rate
120 days
AAI, Juhu Airport, Mumbai-56
as per NIT
2 documents required · 2 mandatory
₹1,180
₹1.7 L
12 Oct 2026
9 Feb 2026
4 Mar 2026
9 Feb 2026
2 Mar 2026
9 Feb 2026
9 Feb 2026 - 20 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.1 | Supply,Installation,Testing and Commissioning of outdoor compact substation comprising of following along with (i)11kV, 630A, Horizontal Draw Out VCBs(3 Nos-One incomer and two outgoings) with 230V AC Motor Operated Spring Charging Mechanism with 24V DC Closing /Opening Shunt trip coils,Auxillary switch, Mechanical On/Off Push Button, mechanical Operating Counter with metering Cubical, Auxiliary Relay, Under Voltage Relay, 8 Window Annunciator,Battery Power Pack with 7AH Battery & in built charger for 24V Circuit,CTs,PTS,Protection relays,Indicating lamps.
(ii)250 KVA, 11/0.433 KV, 3 Phase, 50HZ, ONAN Cooled Oil immersed Copper Wound Step Down “BIS Marked ” Transformer Complete with first filling of IS:335 ISI Marked Filtered & Dehydrated Transformer Oil, having 7 position Off-Circuit tap changer withtapping range +7.5% to -7.5% in steps of 2.5% each with all standard fittings & accessories including OTI, WTI & Marshalling Box .The Transformer as per comply with BIS-1180(Part-1)2014 EEL- 3 with amendment no.- 4 and Losses @50% Load - not more than 864W and Losses @100% Load - not more than 2488W.
(iii)LT Panel comprising of LV Side Incomer – 01 No,400 Amp 4 Pole 35 KA four ploe 415V MCCB with thermal magnetic
based release with O/L & S/C protection, RYB Indication Lamp,,Ammeter,Voltmeter - 500A/5A LT CT Cl:1.0.
(iv)Enclosure Section:Space Heater with ON/OFF Switch and Thermostat, Single phase switch with socket, LT Cubical illumination Lamp with Door Limit switch and MCB’s for AC / DC Control,MS Steel Sheet enclosure suitable for Outdoor Installation with MS base channel,Provision for receiving Incoming cables through Bottom entry and out going through Bus bar to Transformer panel, Excluding Termination Kit & Glands,Provision for receiving Incoming through bus duct by bus bar and Outgoing thro cable box bottom entry Excluding Termination Kit & Glands,Bus bar and earth bus of adequate rating,Paint shade: Siemens Grey ( RAL 7032).
(v)Providing RCC foundation suitable for the structural load of the compact substation,considering the site soil bearing capacity and as per OEM recommendations with provision for cable entry and foundation shall be at suitable height above ground level to avoid water entry.
(vi)Provision of roofing and supporting steel structure suitable for the compact substation.
(vii)All other miscellaneous works and internal connections etc for sucessful commissioning of the installation. | 1 | Job | - | - |
| 1.2 | Supply of HT Three Core Power Cables of size 3 Core 120 sq.mm - Aluminium Conductor A2XFY 11 KV Earthed Cables with Stranded Compacted Circular Aluminium Conductor, Conductor Screen with Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with Extruded Semi Conducting Compound in Combination with Copper Tape, Cores Laid Up,Innersheath of PVC, Galvanised Steel Flat Strip Armoured, & Overall PVC Sheathed Cable Conforming to IS 7098 (Part-2) 2011 with upto Date Amendments | 200 | Meters | - | - |
| 1.3 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 11 KV grade upto 120 sq.mm direct in ground including excavation,sand cushioning,protective covering,refilling the trench etc as required. | 40 | Meters | - | - |
| 1.4 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 11 KV grade upto 120 sq.mm in the existing RCC/HUME/METAL pipe as required. | 80 | Meters | - | - |
| 1.5 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 11 KV grade upto 120 sq.mm in the existing masonary open duct as required. | 80 | Meters | - | - |
| 1.6 | Supply of LT Power Cables - Aluminium stranded conductor A2XFY, XLPE Insulated, Cores Laid Up, PVC Innersheathed, Armoured with galvanised steel strip, Extruded PVC Type ST2 Outer Sheathed, 650 V(Conductor to earth)/1100 V(between conductors) grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.
3.5 core 400 sq.mm | 200 | Meters | - | - |
| 1.7 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 1.1 KV grade and size above 185 Sq.mm and upto 400 sq.mm direct in ground including excavation,sand cushioning,protective covering,refilling the trench etc as required. | 20 | Meters | - | - |
| 1.8 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 1.1 KV grade and size above 185 Sq.mm and upto 400 sq.mm in the existing RCC/HUME/METAL pipe as required. | 100 | Meters | - | - |
| 1.9 | Laying of one number PVC/XLPE Insulated PVC sheathed power cable of 1.1 KV grade and size above 185 Sq.mm and upto 400 sq.mm in the existing masonary open duct as required. | 50 | Meters | - | - |
| 2 | Laying and fixing of one number PVC/XLPE Insulated PVC sheathed power cable of 1.1 KV grade and size above 185 Sq.mm and upto 400 sq.mm(Clamped with 40 X 3 mm MS flat clamp) on wall surface as required. | 10 | Meters | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 15.54 MB
BOQ_309425.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .