Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.2 LAccepted-Finance | L1 | Accepted-Finance Financial Bid accepted. |
Tender Value
Refer Docs
EMD Value
₹10,966
Closing Date
25 May 2022, 11:00 amClosed
The Executive Engineer (E) BSNL ED Mumbai
The Executive Engineer E BSNL Electrical Division 5th Floor A Wing BSNL Admin Bldg Juhu Tara Road Santacruz West Mumbai 400054
One time repair and attending initial defects of 6 x 7 TR HPAC (M/s Emerson Make) at NIB, 11th Floor, Fountain Telecom Bldg II, Mumbai (SH Miscellaneous urgent repairing of HPAC units)(2nd call)
2022_BSNL_114559_1
NIT No. 21/EEE/BSNL/ED/MI/2021-22
Open Tender
Electrical Works
Item Rate
30 days
Mumbai
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
AO (F and A) BSNL
₹10,966
1 Jun 2022
30 Apr 2022
26 May 2022
30 Apr 2022
25 May 2022
30 Apr 2022
Amount
Part B ( Replacement of Electronic controller , Blower motor )
Arranging visit of Technician of authorized dealer M/s Emerson (Vertiv) for health check of 06 Nos. 7 TR HPAC, identification & replacement of faulty spares complete with testing etc. as required
Repairing of 7 TR single circuit high precision type package type AC unit (M/s Emerson ) by replacing following defective/worn out accessories of approved make i/c pumping down of refrigerant system, fixing, jointing, modification if required
Outdoor unit PCB (FSC Board ) - Control card for Condenser unit suitable for M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030)
Electronic Expansion Valve Driver unit (EVD evolution user interface unit complete with display and base) of M/s Carel suitable for M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030).
Supply and installation of IOC Card controller (ICOM Board) suitable for M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030). complete by making Master-slave configuration for sequential running of package A.C. units for equal running hours , communication with each other units for controlling the desired condition with group action , setting of all parameters, etc. by hiring Manufacturers / authorized Dealer 's representative & offering testing to BSNL representative etc. as required with testing and commissioning etc. as required. (Note :- This item shall be replaced upon actual verification & testing from technician of authorized dealer of M/s Emerson )
LP Cut Out Switch M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030).
Replacement of condenser Fan (outdoor) suitable for three phase,400V,50Hz.AC supply 28'' dia.0.62 KW ,1.7/1.05 A,900/600 RPM.(Make :ZIEHL-ABEGG)
Supplying and Charging of Refrigerant Gas ( R-407 ) for charging in the existing AC Package unit i/c testing etc as reqd.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .