Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.3 LAccepted-AOC | L1 | Accepted-AOC DUE TO LOWEST TENDER | |
| 2 | L2₹13.3 L+₹3.6 L (36.7%)Rejected-Finance 7TH MILE UPPER SHILLONG P O NONGLYER SHILLONG MEGHALAYA | EAST KHASI HILLS | MEGHALAYA | 793009 | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹14.2 L+₹4.4 L (45.4%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹9.6 L
EMD Value
₹19,120
Closing Date
23 Sept 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
AGE (I) AF AMRITSAR
Asst Garrison Engineer (I) AF Amritsar
REPAIR TO LT DISTRIBUTION NETWORK AT AIRFORCE STATION AMRITSAR UNDER AGE (I) AF AMRITSAR
2021_MES_461336_3
AGE(I)AF/ASR/T-09/2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE (I) AF AMRITSAR
Class E Category (b) i
8 documents required · 8 mandatory
₹500
Yes
AGE (I) AF AMRITSAR
₹19,120
Yes
9 Oct 2021
2 Sept 2021
25 Sept 2021
2 Sept 2021
23 Sept 2021
9 Sept 2021
60 days
Amount
Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep for laying of cables and foundation of poles etc. and getting out complete all as spceified and directed.
Returning, filling in trenches (soil) including spreading leveling and well ramming in layers not exc 25 cm thick complete all as specified and directed.
Removal of surplus excavation soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
M&L sand cushioning with a layer of dry river sand 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts. Complete all as specified and directed Note: Punned down thickness (overall 18cm), shall be considered for measurement and payment.
M&L, locally available , sub class 'B' bricks (old size) laid flat and dry in trenches over the cable for protectionprependicular to the direction of cable adjacent to each other complete all as specified and directed.
M&L, GI pipe light grade 80 mm dia bore for cable protection fixed to pole or under road/ pavement, complete including MS clamps, nuts, bolts etc all as specified and directed.
M&L, GI pipe light grade 50 mm dia bore for cable protection fixed to pole or under road/ pavement, complete including MS clamps, nuts, bolts etc all as specified and directed.
M&L, GI pipe light grade 40 mm dia bore for cable protection fixed to pole or under road/ pavement, complete including MS clamps, nuts, bolts etc all as specified and directed.
Supply, laying, jointing, testing and commissioning of Low Tension (LT) under ground cables XLPE insulated screened PVC bedded galvanized armoured electric powder cable (heavy duty) with aluminium conductor cross sectional are 300 Sqmm 3.5 core LT, 1100 volts grade, laid in trenches, along poles or passing with through pipe or laid under floor or through on wall etc, complete all as specified and directed.
Supply, laying, jointing, testing and commissioning of Low Tension (LT) under ground cables XLPE insulated screened PVC bedded galvanized armoured electric powder cable (heavy duty) with aluminium conductor cross sectional are 120 Sqmm 3.5 core LT, 1100 volts grade, laid in trenches, along poles or passing with through pipe or laid under floor or through on wall etc, complete all as specified and directed.
Laying, jointing, testing and commissioning of Low Tension (LT) under ground cables XLPE insulated screened PVC bedded galvanized armoured electric powder cable (heavy duty) with aluminium conductor cross sectional are 70 Sqmm 3.5 core LT, 1100 volts grade, laid in trenches, along poles or passing with through pipe or laid under floor or through on wall etc, complete all as specified and directed. Note(s) : Cable will be issued by department under Sch 'B' Free for fixing (Department supply)
Laying, jointing, testing and commissioning of Low Tension (LT) under ground cables XLPE insulated screened PVC bedded galvanized armoured electric powder cable (heavy duty) with aluminium conductor cross sectional are 50 Sqmm 3.5 core LT, 1100 volts grade, laid in trenches, along poles or passing with through pipe or laid under floor or through on wall etc, complete all as specified and directed. Note(s) : Cable will be issued by department under Sch 'B' Free for fixing (Department supply)
Laying, jointing, testing and commissioning of Low Tension (LT) under ground cables XLPE insulated screened PVC bedded galvanized armoured electric powder cable (heavy duty) with aluminium conductor cross sectional are 35 Sqmm 3.5 core LT, 1100 volts grade, laid in trenches, along poles or passing with through pipe or laid under floor or through on wall etc, complete all as specified and directed. Note(s) : Cable will be issued by department under Sch 'B' Free for fixing (Department supply)
Supply, install, test and commissioning in replacement of factory made tested (Including CPRI type tested certificate ) LT panel board cubical outdoor type of size 0.75 x 0.75 x 0.40 mtrs, plate mounted suitable for , 415 volts 3 phase, 4 wire,50 HZ AC supply system having bus bar chamber with insulated aluminium bus bar of rating 400 Amp installed on proceline/ SMC insulator. The panel shall be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA MS sheet and 40X40X6 mm thick MS angle iron frame work, powder coated finished over one coat of red oxide on out side surface and painted in side with two coats of red oxide primer and rear opening type with apran for cable entery closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size (but not less than 4.0 sqmm) and comprising of the following including necessary PCC in 1:2:4 type B1 using 20mm graded stone aggregate for platform of suitable size etc all as deviated with the following fitments:- (a) MCCB 4 pole 415 volt 250 amp rating bracking capacity 36 KA incoming (Adjustable Overload 40-100%). (b) Bus bar: Providing suitable size of Bus bar of aluminium 400 amp rating with coloured heat shrinkable insuated sleeves 415 volts as per IS of suitable size mounted on DMC/epoxy insulator
Supply and fixing Three phase Voltmeter Digital type class 0.5 incl of Make HPL or equivalent to Havells,Bajaj . complete all as specified and directed.
Supply and fixing Three phase Ammeter Digital type class 0.5 of Make HPL to Havells,Bajaj complete all as specified and directed.
Supply only MCCB 630 Amp Four pole 415 volts Breaking Capacity 25 KA with Adjustable thermal & fixed magnetic setting as per sample complete all as specified and directed.
Supply only MCCB 315 Amp Four pole 415 volts Breaking Capacity 25 KA with Adjustable thermal & fixed magnetic setting as per sample complete all as specified and directed.
Supply only MCCB 250 Amp Four pole 415 volts Breaking Capacity 25 KA with Adjustable thermal & fixed magnetic setting as per sample complete all as specified and directed.
Supply only MCCB 160 Amp Four pole 415 volts Breaking Capacity 25 KA with Adjustable thermal & fixed magnetic setting as per sample complete all as specified and directed.
Supply only MCCB 100 Amp Four pole 415 volts Breaking Capacity 25 KA with Adjustable thermal & fixed magnetic setting as per sample complete all as specified and directed.
Supply only MCCB 63 Amp Four pole 415 volts Breaking Capacity 25 KA with Adjustable thermal & fixed magnetic setting as per sample complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode of size 60cm x 60cm x 6mm thick burried directly in ground vertically at a depth not less than 2.25 metre deep below normal ground level with top edge of the plate not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nuts and washers made of galvanized iron or steel and protected by light grade 15 mm dia GI pipe connected to main switch board or main control board, and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 5 of SSR Part I (1991) dismanteling of existing unserviceable erth pit, the desired value of resistance should be less than 3 Ohm. Providing a suitable size of placard at each Earthing as per sample complete all as specified and directed by Engr-in-Charge.
M&L for earthing complete with galvanized steel earth plate electrode of size 60cm x 60cm x 6mm thick burried directly in ground vertically at a depth not less than 2.25 metre deep below normal ground level with top edge of the plate not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using galvanized iron strip 25X4mm as earth lead by means of bolts, nuts, check nuts and washers made of galvanized iron or steel and protected by light grade 15 mm dia GI pipe connected to main switch board or main control board, and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 5 of SSR Part I (1991)dismanteling of esisting unserviceable erth pit, the desired value of resistance should be less than 3 Ohm. Providing a suitable size of placard at each Earthing as per sample complete all as specified and directed by Engr-in-Charge.
Material and labour for GI strip 25mm x 4mm fixing with porcelain insulators on roof and floor complete all as specified.
Material and labour for Copper strip 25mm x 3mm fixing with porcelain insulators on roof and floor complete all as specified.
Supply and fixing pre-casted RCC earth pit cover for replacing broken/ unserviceable pit cover including cleaning the surronding area (60 x60cm) complete all as specified and directed by Engr -in-Charge.
Supply and fixing funnel alongwith wire mesh in replacement of missing/ unserviceable item all as specified and directed by Engr-in-Charge.
Supply & fixing porcelain supporting insulator of existing size / adequate size fixing on wall / roof for insulating and supporting the lightning strips to protect during lightning.
Supply and fix in repair GI pipe 80mm dia, medium grade with all necessary fitting laid in trenches or with walls laid for replacement including taking out directed by Engr-in-Charge.
Supply and fix in repair GI pipe 50mm dia, medium grade with all necessary fitting laid in trenches or with walls laid for replacement including taking out directed by Engr-in-Charge.
Supply and fix in repair GI pipe 40mm dia, medium grade with all necessary fitting laid in trenches or with walls laid for replacement including taking out directed by Engr-in-Charge.
Supply and fix in repair GI pipe 25mm dia, medium grade with all necessary fitting laid in trenches or with walls laid for replacement including taking out directed by Engr-in-Charge.
Supply and fix in repair GI pipe 20mm dia, medium grade with all necessary fitting laid in trenches or with walls laid for replacement including taking out directed by Engr-in-Charge.
Supply and fix in repair GI pipe 15mm dia, medium grade with all necessary fitting laid in trenches or with walls laid for replacement including taking out directed by Engr-in-Charge.
Supply and Fixed Gun metal globe /gate/stop valve (ISI marked) with iron wheel head screwed both ends for iron pipe of 50mm dia fixed in repair all as specified and directed by EIC
Supply and Fixed Gun metal globe /gate/stop valve (ISI marked) with iron wheel head screwed both ends for iron pipe of 40mm dia fixed in repair all as specified and directed by EIC
Supply and Fixed Gun metal globe /gate/stop valve (ISI marked) with iron wheel head screwed both ends for iron pipe of 25mm dia fixed in repair all as specified and directed by EIC
Supply and Fixed Gun metal globe /gate/stop valve (ISI marked) with iron wheel head screwed both ends for iron pipe of 20mm dia fixed in repair all as specified and directed by EIC
Drilling and tapping cast iron water mains ( in position ) for branch connections of the internal dia 20 mm including S&F brass ferrule for branch connection
Supply and fix,in replacement cast iron sluice valve 100 mm dia with flanged and drilled ends any pattern ISI marked, PN 1.0 class brass spindle, including joints and jointing materials bolts, nuts washers rubber gasket complete
Material and labour, rectification of leakage in CI/DI/GI pipe line size 80 to 150 mm dia bore including filling of lead/fittings as required cocking to the existing joint making the line serviceable and functioning complete all as specified and directed Note : The rate shall be deemed to be include excavation and earth work, returning, filling and removal of soil as required.
Material and labour, rectification of leakage in GI pipe line size 20 to 50 mm dia bore including any type fittings complete as required and making the line serviceable & functioning complete all as specified and directed Note : The rate shall be deemed to be include excavation and earth work, returning, filling and removal of soil as required.
Material and labour, taking out the existing defective 20 HP motor with submersible pumping set along with column pipe of any lowering from existing position after disconnecting the electric and water supply connection and strip opening the pumping set motor complete and taking out burnt winding from motor, rewinding the same with super enamelled copper wire of existing guage, varnishing, heating including insulation material and replacement of the worn insulaftion paper, realignment of rotor, adjustment of slots re-assembling the motor complete after repairing including lowering, fixing in position and connecting the electric cable and connection, testing complete all as specified and directed. Note : The quoted rate shall be deemed to include charges taking up/lowering pumping sets, transportation, hiring of T&P, testing and electric connection and material used for jointing the cable complete
Material and labour, taking down the existing defective 20 HP motor coupled with monoblock pumping set from existing position after disconnecting the electric and water supply connection and strip opening the pumping set motor complete and taking out burnt winding from motor, rewinding the same with super enamelled copper wire of existing guage, varnishing, heating including kinsulation material and replacement of the worn insulaftion paper, realignment of rotor, adjustment of slots, re-assembling the motor after necessary rectification of pumps like replacment of bearing, repair/replacement of existing impeller as required complete after repairing, fixing in position and connecting the electric cable and connection, testing complete all as specified and directed Note : The quoted rate shall be deemed to includde charges of taking up/lowering pumping sets, transportation, hiring of T&P, testing and electric connection and material used for jointing the cable
Demolition of cement concrete ( unreinforced) of any description and in any position not otherwise specially provided for including removal of debries out of defence land complete all as specified and directed
Material and labour for 100mm thick plain cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate as in sub base floors, complete all as specified and directed.
Material and labour for 50 mm thick plain cement concrete 1:3:6 type C-2 using 40 mm graded crushed stone aggregate as in floors, finished the surface even and fair complete all as specified and directed.
Note: The Total amount shall subject to adjustment of credit for old Materials as per Schedule of Credit.
kapoor and co
M/S SIMRAN WALIA ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .