Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.3 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹9.5 L+₹14,571.90 (1.56%)Rejected-Finance INDEX NO E 29 CWE JRC 352 3 GURU NANAK PURA EAST JALANDHAR CITY PIN 144001 | JALANDHAR CITY | JALANDHAR | PUNJAB | 144001 | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹9.5 L+₹15,388.95 (1.65%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹9.7 L+₹38,441.40 (4.11%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST | |
| 5 | L5₹9.9 L+₹58,781 (6.29%)Rejected-Finance 7TH MILE UPPER SHILLONG P O NONGLYER SHILLONG MEGHALAYA | EAST KHASI HILLS | MEGHALAYA | 793009 | L5 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
23 Oct 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
AGE (I) AF STATION AMRITSAR
ASST. GARRISON ENGINEER (I) AIR FORCE STATION AMRITSAR - 143001
REPAIR TO LT DISTRIBUTION NETWORK AT AIR FORCE STATION AMRITSAR
2024_MES_675007_1
AGE (I) AF/ASR/T-11/2024-2025
Open Tender
Electrical and Maintenance Works
Item Rate
210 days
AGE (I) AF STATION AMRITSAR
Class E and Category b(i)
8 documents required · 8 mandatory
₹500
Yes
AGE (I) AF STATION AMRITSAR
₹20,000
Yes
28 Nov 2024
18 Sept 2024
30 Oct 2024
18 Sept 2024
23 Oct 2024
9 Oct 2024
Amount
Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep for laying of cables and foundation of poles etc by mechanically and getting out complete all as spceified and directed by Engr-in-charge.
Returning, filling in trenches (soil) including spreading levelling and well ramming in layers not exc 25 cm thick complete all as spceified and directed by Engr-in-charge.
Removal of surplus excavation soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as spceified and directed by Engr-in-charge.
M&L sand cushioning with a layer of dry river sand 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts. complete all as spceified and directed by Engr-in-charge. Note: Punned down thickness (overall 18cm), shall be considered for measurement and payment.
M&L, locally available , sub class 'B' bricks (old size) laid flat and dry in trenches over the cable for protection prependicular to the direction of cable adjacent to each other complete all as spceified and directed by Engr-in-charge.
M&L, GI pipe light grade 80 mm dia bore for cable protection fixed to pole or under road/ pavement, complete including MS clamps, nuts, bolts etc complete all as spceified and directed by Engr-in-charge.
M&L, GI pipe light grade 40mm dia bore for cable protection fixed to pole or under road/ pavement, complete including MS clamps, nuts, bolts etccomplete all as spceified and directed by Engr-in-charge.
Supply, Laying, jointing and commissioning, LT under gound cables XLPE insulated screened PVC bedded galvanized steel strip armoured electric powder cable (heavy duty) with alumininum conductor cross sectional are 120 Sqmm 3.5 core LT, 1100 volts grade , laid in trenches , along poles or passing with through pipe or laid under floor or through/ on walls etc, complete all as spceified and directed by Engr-in-charge. Make : KEI/Polycab/Havells
Supply, Laying, jointing and commissioning, LT under gound cables XLPE insulated screened PVC bedded galvanized steel strip armoured electric powder cable (heavy duty) with alumininum conductor cross sectional are 95 Sqmm 3.5 core LT, 1100 volts grade , laid in trenches , along poles or passing with through pipe or laid under floor or through/ on walls etc, complete all as spceified and directed by Engr-in-charge. Make : KEI/Polycab/Havells
Supply, Laying, jointing and commissioning, LT under gound cables XLPE insulated screened PVC bedded galvanized steel strip armoured electric powder cable (heavy duty) with alumininum conductor cross sectional are 16 Sqmm 4 core LT, 1100 volts grade , laid in trenches , along poles or passing with through pipe or laid under floor or through/ on walls etc, complete all as spceified and directed by Engr-in-charge. Make : KEI/Polycab/Havells
Supply, Laying, jointing and commissioning, LT under gound cables XLPE insulated screened PVC bedded galvanized steel strip armoured electric powder cable (heavy duty) with alumininum conductor cross sectional are 50 Sqmm 3.5 core LT, 1100 volts grade , laid in trenches , along poles or passing with through pipe or laid under floor or through/ on walls etc, complete all as spceified and directed by Engr-in-charge. Make : KEI/Polycab/Havells
Supply, Laying, jointing and commissioning, LT under gound cables XLPE insulated screened PVC bedded galvanized steel strip armoured electric powder cable (heavy duty) with alumininum conductor cross sectional are 10 Sqmm 2 core LT, 1100 volts grade , laid in trenches , along poles or passing with through pipe or laid under floor or through/ on walls etc, complete all as spceified and directed by Engr-in-charge. Make : KEI/Polycab/Havells
Supply and fixing Three phase Voltmeter Digital type class 0.5 incl of Make AE/L&T. complete all as spceified and directed by Engr-in-charge.
Supply and fixing Three phase Ammeter Digital type class 0.5 of Make AE/L&T complete all as spceified and directed by Engr-in-charge.
Supply & Fixing MCCB 630 Amp Four pole 415 volts Breaking Capacity 50 KA with Adjustable thermal & fixed magnetic setting as per existing fixed on site, complete all as spceified and directed by Engr-in-charge. Make : Havells/Legrnd/C&S/Indo asian
M&L for earthing complete with galvanized steel earth plate electrode of size 60cm x 60cm x 6mm thick burried directly in ground vertically at a depth not less than 2.25 metre deep below normal ground level with top edge of the plate not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using galvanized iron strip 25X4mm as earth lead by means of bolts, nuts, check nuts and washers made of galvanized iron or steel and protected by light grade 40 mm dia GI pipe light grade connected to main switch board or main control board, and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 5 of SSR Part I (1991)dismanteling of existingunserviceable erth pit, the desired value of resistance should be less than 3 Ohm. Providing a suitable size of Placard at each Earthing as per sample complete all as specified and directed by Engr-in-Charge.
Material and labour for GI strip 25mm x 4mm fixing with porcelain insulators on roof and floor, complete all as spceified and directed by Engr-in-charge.
Supply and fixing pre-casted RCC earth pit cover for replacing broken/ unserviceable pit cover including cleaning the surronding area (60 x60 cm), complete all as spceified and directed by Engr-in-charge.
Supply and fixing funnel alongwith wire mesh in replacement of missing/ unserviceable item, complete all as spceified and directed by Engr-in-charge.
Supply & fixing porcelain supporting insulator of existing size / adequate size fixing on wall / roof for insulating and supporting the lightning strips to protect during lightning, complete all as spceified and directed by Engr-in-charge.
Material and labour Painting to Steel tublar poles 9 m long with one coat of Synthetic enamel paint black/yellow from ground level /copping remaining Job portion painting with one coat of aluminium paint including preparation of old painted surfaces and painting the pole terminal etc. all as specified and as directed.
Material and labour for painting of LT feeder pillar box external/internal surfaces indoor/outdoor type of any size with two coat of synthetic enamel paint of approved quality and colour after cleaning and removing the rusted area using sand paper complete all as specified and directed
Supply and fixing street light junction box insulated and made out of environment friendly, recyclable, UV resistant, halogen & silicon free,polycarbonate with glass fiber reinforced of size in mm should be not less then 205 X 255 X 112. The box shall be rated for Degree of Ingress Protection IP 66/67 including all fixing material as required all as specified and directed. Make: cat. Part no KF2525 of Hensel or equivalent in Siemens/GE Power/Rittal.
Supply and replace danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for HT 25x20cm size all as directed.
Supply and replace in repair of the following in existing panel of Make : Havells/Legrnd/C&S/Indo asian
(a ) MCCB 4 Pole, 415 V, with Microprocessor release 160 Amps with breaking capacity 36 KA
(b ) MCCB 4 Pole, 415 V, with Microprocessor release 250 Amps with breaking capacity 36 KA
(c ) MCCB 4 Pole, 415 V, with Microprocessor release 400 Amps with breaking capacity 36 KA
Supply and fixing Anti suicide fan down rod for ceilling fans in various accomodation (MD & OTM) having minimum length 200mm or as required as per site condition , consisting of MS & pipe good qulity material colour white or brown . The work also consist taking down fan if required, installation of anti suicide rod by removing old rod, inclusive of flexiable copper wire size 23/0.75 and refixing at same place after cleaning of fan and accessories as directed by Engineer - in - charge.
S&F Bracket made out of GI pipe light grade 25 mm dia 1.50 mtr long duly welded with MS pipe capacity of 100mm dia ,30 cm long with holes ,nuts ,bolts and fixing on the top of pole complete all as specified.
Bracket made out of GI pipe light grade 40 mm dia 1.50 mtr long duly welded with MS pipe capacity of 100mm dia ,30 cm long with holes ,nuts ,bolts and fixing on the top of pole complete all as specified.
Demolition of cement concrete ( unreinforced) of any description and in any position not otherwise specially provided for including removal of debries out of defence land complete all as specified and directed
Material and labour for 100 mm thick plain cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate as in sub base of floors, complete all as specified and directed.
Material and labour for 75 mm thick plain cement concrete 1:3:6 type C-2 using 40 mm graded crushed stone aggregate as in floors, finished the surface even and fair, complete all as specified and directed.
Supply and fixing of Battery 12 volt, 60 AH , Make – Exide/ Su-kam/Amco/Luminous/Instapower complete all as directed.
Supply and fixing of Solar panel suitable for 60 watt complete all as specified and directed by Engr-in- Charge
Note: The Total amount shall subject to adjustment of credit for old Materials as per Schedule of Credit.
Northern cable fault locatoers (BID ID -3141167)
B S TRADERS (BID ID -3140825)
BHARAT ENGINEERS (BID ID -3141149)
kapoor and co (BID ID -3148226)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .