Executive Engineer
Assistant Executive Engineer-in-charge, AC Division, Works Department, IIT Delhi, Hauz Khas, New Delhi - 110016
Replacement of Solar Inverter of ITEC Bldg, Sonipat Campus
2025_IIT_885944_1
IITD/WORKS (SP-5173)/2025
Open Tender
Miscellaneous Works
Works
30 days
IIT Delhi Hauz Khas
As per tender documents
14 documents required · 14 mandatory
₹0
₹23,883
5 Jan 2026
18 Nov 2025
26 Nov 2025
18 Nov 2025
25 Nov 2025
18 Nov 2025
Select, Excess (+), Less (-)
Tender Inviting Authority: INDIAN INSTITUTE OF TECHNOLOGY
Name of Work: Replacement of Solar Inverter of ITEC Building, Sonipat Campus.
Contract No: IITD/WORKS(SP-5173)/2025
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Item Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency Rate (as per Clause 8 of Commercial and Additional Conditions) (INR) Excise Duty Amount in INR Rs. P GST Amount in INR Rs. P Freight Charges ( Unloading & Stacking) in Rs. P Any Other Taxes in Rs. P Any Other Duties/Levies in Rs. P IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes col (13) = (4) x (7) in Rs. P TOTAL AMOUNT TOTAL AMOUNT In Words
1 Providing, installation, testing and commissioning of 50 kW capacity On Grid power conditioning unit (PCU)/Inverter of 350 - 800 V dc input voltage range and 415 V ac, three phase, 4 wire, 50 Hz ± 2.5 Hz output voltage suitable to generate ac with a variation of 10% at nominal voltage. Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degC, minimum IP-65, built-in meter and data logger, MPPT, switching devices IGBT/MOSFETs and controller Microprocessor / DSP. PCU / inverter shall be capable of complete automatic operation including wake-up, synchronisation & shutdown. The PCU shall be able to withstand unbalanced load conforming to IEC standard with shutdown/standby mode. it must be provided with grid islanding along with manual disconnect pole isolation switch besides automatic disconnection. Minimum protections: Mains under / over voltage, over current, over/under grid frequency, over temperature, surge voltage induced at output due to external source, short circuit, lightning, anti-islanding (for grid sync mode) and other protections as per applicable standards. LCD/LED display of minimum parameters: dc input voltage, dc current, ac voltage and current (all 3 phases), instantaneous and cumulative ac output power, daily dc energy produced and other parameters as per applicable standard. Communication interface compatibility shall be RS 485 / RS 232. Including disconnecting and removing the faulty inverter in place and reconnecting with new inverter/PCU unit etc. complete as required. (Acceptable make: SMA / KACO / Refusol / Delta /Thea / Danfoss ) item3 4 Each 0 Excess(+) Full Conversion INR 1.01 Supplying, Conveying and fixing spls. Including eart item1 123.223 Nos
Total in Figures 4 Construction of chamber for 100mm sluice plates item5 10 Nos
Quoted Rate in Figures Select %
Quoted Rate in Words
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.71 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.59 MB
BOQ_931223.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .