Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.5 LAccepted-AOC 852 EKTA VIHAR 1 C NEAR ANAND NAGAR 9 B PATIALA 147001 | PATIALA | PATIALA | PUNJAB | 147001 | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹35.0 L+₹1.1 L (3.34%)Rejected-Finance 300 PREM BASTI 10 SANGRUR SANGRUR PUNJAB 148001 | SANGRUR | PUNJAB | 148001 | L2 | Rejected-Finance NOT BEING LOWEST | |
| 3 | L3₹35.5 L+₹1.6 L (4.79%)Rejected-Finance | L3 | Rejected-Finance NOT BEING LOWEST | |
| 4 | L4₹40.8 L+₹6.9 L (20.4%)Rejected-Finance H NO 597 SEONA ROAD RANJIT NAGAR PATIALA PB 147001 | PATIALA | PATIALA | PUNJAB | 147001 | L4 | Rejected-Finance NOT BEING LOWEST |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
21 Oct 2024, 6:00 pmClosed
LT COL SANDEEP KUMAR
AS PER TENDER DOCUMENTS
REPAIR AND MAINTANANCE OF INTERNAL WIRING, FITTINGS AND FIXTURES AS WELL AS ATTEND MAINTANANCE PROGRAMME MD ACCN AND OTM AREA AT OLD CANTT AREA UNDER GE (N) PATIALA AT MIL STN PATIALA
2024_MES_675879_1
GE (N)/TOKEN-57/2024-2025
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
PATIALA
AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
GE NORTH PATIALA
₹90,000
Yes
28 Nov 2024
21 Sept 2024
23 Oct 2024
21 Sept 2024
21 Oct 2024
7 Oct 2024
Amount
Taking down carefully existing points wiring on surface conduit/concealed conduit for light/ fan/socket /power/ bell from wall & roof along with fitting and fixtures such as switches, sockets, ceiling roses, batten holders, unserviceable light fittings, piece of wires,gutties, conduit, wooden boards etc and making good the disturbed portion of all floor, ceiling etc all as specified and directed.
M & L for point wiring with 1.5 sqmm PVC insulated and unsheathed FRLSH(FLAME RETARDANT LOW SMOKE AND HALOGEN) single core multi-stranded copper conductor for one light/fan and including PVC rigid concealed conduit medium grade 19/20 mm dia including, chasing and cementing work terminated in pressed steel terminal boxes with top cover plate including 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper earth continuity conductor controlled by one switch and/or one regulator including repairing the surfaces in CM 1:3 and finishing the surface as per existing treatment required for fitting of flush and junction boxes all as specified and directed Note: (i)Switches and regulators shall be measured and paid for separately. (ii) Wiring shall be done as per colour code in IS for phase, neutral and earth ((iii) In case of Modular: Modular cover plate and metal flush boxes are included in Point wiring
All as per Sl item No 2 above herein before but one 5Amp socket point on independent board but with other switches complete all as specified and directed.
All as per Sl item No 2 above herein before but one socket out let 5 pins 5 Amp on the same board but with other switches complete all as specified and directed.
All as per Sl item No 2 above herein before but one socket out let 3 pin 15 Amp Independent with 2.5 sqmm wire including 2.5 sqmm PVC insulated and unsheathed FRLS single core multi stranded copper earth continuity conductor complete all as specified and directed.
M & L for point wiring with 1.5 sqmm PVC insulated and unsheathed FRLSH(FLAME RETARDANT LOW SMOKE AND HALOGEN) single core multi-stranded copper conductor for one light/fan in existing conduit to be terminated in pressed steel terminal boxes with top cover plate including 1.5 sqmm PVC insulated and unsheathed FRLSH single core multi-stranded copper earth continuity conductor controlled by one switch and/or one regulator complete including repairing the surfaces in CM 1:3 and finishing the surface as per existing treatment all as specified and directed. Note: (i)Switches and regulators shall be measured and paid for separately. (ii)Wiring shall be done as per colour code in IS for phase, neutral and earth (iii)In case of Modular: Modular cover plate and metal flush boxes are incl in Point wiring). NOTE:-1.The contractor must produce certificate of FRLSH wire as well as on site testing of FRLSH wire. .
All as per Sl item No 6 above herein before but one 5Amp socket point on independent board but with other switches complete all as specified and directed.
All as per Sl item No 6 above herein before but one socket out let 5 pins 5 Amp on the same board but with other switches complete all as specified and directed.
All as per Sl item No 6 above herein before but one socket out let 3 pin 15 Amp Independent with 2.5 sqmm wire including 1.5 sqmm PVC insulated and unsheathed FRLS single core stranded copper earth continuity conductor complete all as specified and directed.
S& F Modular switch 1 way, 6 Amps, 1 module complete all as specified and directed.
S & F Modular switch 1 way, 16 Amps, 1 module with indicator lamp complete all as specified and directed.
S & F Modular socket 5 pin 6 Amps, 2 module complete all as specified and directed.
S & F Modular socket 5 pin 6/16 Amps, combination type 2 module complete all as specified and directed.
S & F fan regulator modular type 2 module 6 step complete all as specified and directed.
S&F ceiling rose surface bakelite surface 65 x 50mm 3 terminals all as specified & directed.
S& F Modular Bell switch 1 way, 6 Amps, 1 module complete all as specified.
Suppy and fix bell ding dong type AC 230 volts complete all as specified and directed.
S&F incl taking down 20 watt wall mounted, new generation LED batten fitting 4 feet with polycarbonate diffuser andextruded thermoplastic body > 90 lumen/watt having correleted color temperature(CCT) of Emitting light 6500/3000 K with CRI of LED >90 . including all fixing accessories & connecting up with PVC insulated twin core flexible copper conductor cable of suitable size complete all as specified and directed.
Supply and fix incl taking down 36 watt recessed mounted LED luminaire suitable for armstrong/grid ceiling with super bright LED fittings minimum 100 lumen/watt with connector block etc with short circuit protection , open protection , reverse polarity protection , high voltage protection complete with all accessories pre wired having correleted color temperature(CCR) of Emitting light 6500 OR 3000 K(According to requirement) with CRI of LED >90. and including cconnection with twin core twisted flexible copper conductor cable .75X2 Sqmm complete all as specified and directed.
Supply and fix incl taking down Led Stellar Square/round recessed Mounted slim and and Elegant Downlight /Panel for indoor application with high aesthetic appeal of capacity 12 watt, minimum 100 lumen/watt having correleted color temperature(CCR) of Emitting light 6500 OR 3000 K(According to requirement) with CRI of LED >90.complete with all electrical connection up with PVC insulated twin core flexible copper conductor cable of suitable size complete all as specified and directed.
S&F MCB DB double door 240 volts with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting type, drilling holes for incoming and out going cables complete suitable for 8 ways with IP43 protection complete all as specefied and directed. (Note: MCB should be B or C curve as directed by engineer in charge)
S&F MCB , SPN, 240 Volt , 40 amp for fixing in DBs of including proper thimble connections complete all as specified and directed. (Note: MCB should be B or C curve as directed by engineer in charge).
S&F MCB, single pole 240 volts 6 to 32 Amp capacity fixing in DB’s including proper thimble connections complete all as specified and directed. (Note: MCB should be B or C curve as directed by engineer in charge)
S&F MCB, single pole 240 volts 40 to 63 Amp capacity fixing in DB’s including proper thimble connections complete all as specified and directed. (Note: MCB should be B or C curve as directed by engineer in charge)
S&F MCCB DB VTPN 4 WAYdouble door 240 volts with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting type, drilling holes for incoming and out going cables complete suitable for ways with IP54 protection complete all as specefied and directed. (Note: MCCB should be B or C curve as directed by engineer in charge)
S&F MCCB DB VTPN 4 WAYdouble door 240 volts with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting type, drilling holes for incoming and out going cables complete suitable for ways with IP43 protection complete all as specefied and directed. (Note: MCCB should be B or C curve as directed by engineer in charge)
Supply and fix metal clad Box of single phase 220V with built in socket and plug of capacity 20 amp complete all as specified and directed.
S&F MCCB , TPN, 240 Volt , 125 amp for fixing in DBs of including proper thimble connections complete all as specified and directed. (Note: MCCB should be B or C curve as directed by engineer in charge)
S&F MCCB , TPN, 240 Volt , 63 to 100 amp for fixing in DBs of including proper thimble connections complete all as specified and directed. (Note: MCCB should be B or C curve as directed by engineer in charge)
Earthing complete with galvanised steel earth plate electrode, 600x600 x 6.0mm thick buried directly in ground(earth pit not less than 2.25m deep below normal level) connected to galvanised earth lead wire 4.0mm dia by means of nuts, bolts, & washers of GI as shown in electrical plate No 3 of SSR Part I. Connected to earthing test point testing complete including necessary earth pit chamber in PCC 1: 3: 6 type C1, and 50mm thick RCC 1 : 2: 4 of chamber cover and with 8mm dia mild steel re-enforcement of 15Cm C/C spacing both ways with a handle made of 8 mm bar for fitting, galvanised iron funnel, wire mash watering pipe GI 20 mm dia light grade, and protection to earth lead shall be provided with GI pipe light grade 15mm dia up to 7.5m from the earth plate electrode, excavation, charcoal and common salt mixed refilling of soil etc complete all as directed. Test Sheet having Earth resistance value less than 3 ohm will be submitted by contractor complete all as specified and directed.
M & L for Sub main wiring with four single core 10.0 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 10 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 4 Runs of 10.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 2 Run of 10 Sqm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring.
M & L for Sub main wiring with two single core 10.0 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 10 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 10.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 10 Sqm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring.
M & L for Sub main wiring with two single core 6.0 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 6 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 6.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 6 Sqm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring.
M & L for Sub main wiring with two single core 4.0 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 4 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 4.00 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 4 Sqm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring.
M & L for Sub main wiring with two single core 2.5 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 2.5 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 2.50 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 2.5 Sqm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring.
M & L for Sub main wiring with two single core 1.5 Sqmm PVC insulated and unsheathed FRLSH ,stranded copper conductor cable drawn through PVC concealed conduit 25 mm dia including 1.5 Sqmm PVC insulated unsheathed FRLSH stranded copper conductor cable as earth wire all as specified and directed by Engineer-in-charge. Note 1:- 2 Runs of 1.50 Sqmm Copper conductor cable, 1 Run of PVC conduit & 1 Run of 1.5 Sqm Copper conductor Earth wire shall be measured as one unit) Note 2 : Rate quoted for this items shall be inclusive of the cost of (i) Rigid non-metallic PVC conduit of 25 mm dia with tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (ii) Cutting chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to match the existing surfaces, cutting not exc. 10 cm girth . (iii) Taking out/down existing unserviceable sub main wiring.
Supply and fix incl taking down new generation energy saving 9/10 watt LED bulk head (porch light fitting) made of plasitic housing with opal diffuser With IP 65. having correleted color temperature(CCR) of Emmiting light 6500/3000 K with CRI of LED >90. connection with PVC insulated twin core flexible copper conductor cable of suitable size.complete all as specified and directed.
M&L switch piano flush type single pole, one way 6amp complete all as specified and directed.
M&L switch piano flush type single pole, one way 15 amp complete all as specified and directed.
M&L socket outlet piano flush type 2 in 1 3 pin 5 amp complete all as specified and directed.
M&L socket outlet piano flush type 3 pin 15 amp complete all as specified and directed.
S/fix fan regulator electronic socket type complete all as specified and directed.
S&F modular white/grey cover plate with frame, 1 module/2 module complete all as specified and directed.
S&F modular white/grey cover plate with frame, 3/4module complete all as specified and directed.
S&F modular white/grey cover plate with frame, 6 module complete all as specified and directed.
S&F modular white/grey cover plate with frame, 8 module complete all as specified and directed.
S&F Metal Flush boxes 1/2 module complete all as specified and directed.
S&F Metal Flush boxes 3/4 module complete all as specified and directed.
S&F Metal Flush boxes 6 module complete all as specified and directed.
S&F Metal Flush boxes 8 module complete all as specified and directed.
M&L modular switch 1 way 6 A, 1 module complete all as specified and directed.
M&L modular socket, 6A-2/3 pin combined, 2 module complete all as specified and directed. Make :(as per existing fitment)
M&L modular switch 16 Amps, 1 module with indicator complete all as specified and directed.Make :(as per existing fitment)
M&L modular socket 16 Amps, 6 pin, 2 module complete all as specified and directed. Make :(as per existing fitment)
S&F modular fan step regulator, 120W - 1 module 6 steps complete all as specified and directed. Make :(as per existing fitment)
S&F BUZZER DING DONG AC 230Volts single pole complete all as specified and directed.
S& F Modular switch 1 way, 6 Amps, 2 module with indicator lamp complete all as specified and directed.
S & F Modular switch 1 way, 16 Amps, 2 module with indicator lamp complete all as specified and directed.
Supply and fix batten holder including flexible wire complete all as specified and directed.
S&F incl taking down 12 watt LED Bulb with base cap B22/E27 type minimum 90 lumen/watt having correleted color temperature(CCT) of Emitting light 6500 /3000 K with CRI of LED >90 complete all as specified and directed.
S/Fix in replacement of old MCB DB TPN 4 Way with 200Amp standerd bus bar factory made IP 43 protection class metal double door with Shrouded Neutral Bar & Pan assembly with connecting link complete including Provision for fixing one MCB TPN upto 125A complete all as specified and directed. (MCB TPN will be measured and paid separately under respective items of sch A)
S&F MCB TPN 240 volts 63 to 100 Amp capacity fixing in DB’s including proper thimble connections complete all as specified and directed. (Note: TPN should be B or C curve as directed by engineer in charge)
S & F INDUSTRIAL HIGH BAY LED light of capacity 120 W ,The LED make must be of minimum 100 lumen/watt .The driver must be power factor > 0.95 with short circuit protection , open circuit protection , reverse polarity protection , high voltage protection. the luminaire must have secondary optics with perfectly matched lens for better light control with CMRI approved correleted color temperature(CCT) of Emitting light 5700 K with with die cast aluminium housing with heat resistant toughened glass IP 66 protection comlete with control gear box and all accessories require to fix the light on wall/structure/pole like clamps nus, bolts et cwith suitable size and including connecting up with twin core twisted flexible copper conductor cable 1.5x2 sqmm with proper clamps. complete all as specified and directed by Engr in Charge.
S&F incl taking down 20 watt wall mounted, new generation alluminium BATTEN SUITABLE FOR LED T-8 Retro fit for multipuspose application with 20 Watt LED Rod 4 feet > 90 lumen/watt , made from extruded aluminium housing,polycarbonate diffuser having correleted color temperature(CCT) of Emitting light 6500/3000 with CRI of LED >90. including all fixing accessories & connecting up with PVC insulated twin core flexible copper conductor cable of suitable size complete all as specified and directed.
S&F incl taking down 18 Watt LED tube Rod 4 feet T-8 Retro fit >90 lumen/watt made from polycarbonate diffuser and polycarboneted body having correleted color temperature(CCT) of Emitting light 6500/3000 K with CRI of LED >90. complete all as specified and directed.
Supply and fix incl taking down Led Stellar Square/round SURFACE Mounted Asthetically designed energy saving LED LIGHT for indoor application of capacity 10 watt having correleted color temperature(CCR) of Emitting light 6500 OR 3000 K(According to requirement) with CRI of LED >90.complete with all electrical connection with PVC insulated twin core flexible copper conductor cable 0.75X2 Sqmm with proper clamps.complete all as specified and directed.
Supply and fix incl taking down outdoor decorative LED Post top lantern with spun aluminium die cast Housing cum heat sink PMMA diffuser in IP65 fitted LED lightf of capacity 40 watt. complete all as specified and directed.
Supply and fix incl taking down outdoor decorative LED Post top lantern with spun aluminium die cast Housing cum heat sink PMMA diffuser in IP65 fitted LED lightf of capacity 20 watt. complete all as specified and directed.
Supply and fix incl taking down LED garden light fitting with LED bulb upto 20 watt E27/B22 base cap fitted on the piller with the help of GI pipe/PCC up to 550 mm height nut bolts and in stainless steel housing with clear acrylic cover in top section with IP 65 protection class ,connection with 1.5 sqmm 3 core copper cable upto 1.5 RM including making suitable PCC foundation and all electrical connection complete all as directed.
Supply and fix LED active power factor correction (APFC) electronic gear (electronic driver) suitable for 25 watt LED light fitting O/P current upto .6A output voltage 23-36V power factor >.90 complete all as directed.
S&F PVC insulated copper conductor 3 core 1.5sqmm passing through flexible PVC conduit and fixed with clamp. complete all as specified and directed. NOTE:-cable and flexible conduit both included in quoted rates.
S&F Alluminium armoured cable 2 core 6 sqmm with PVC insulated.fixed with clamps complete all as specified and directed.
XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core supplied & laid in replacement complete all as specified& directed by Engineer-in-Charge.
XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core supplied & laid in replacement complete all as specified& directed by Engineer-in-Charge.
XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core supplied & laid in replacement complete all as specified& directed by Engineer-in-Charge.
XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core supplied & laid in replacement complete all as specified& directed by Engineer-in-Charge.
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cables including getting out in any kind of soil complete all as specified and directed.
Returning filling in including spreading, levelling, and well ramming, in layers not exceeding 25 cm each layer of any kind of soil.
Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting point.
Material and labour for sand cushioning for cables 8 cm below the cable and 15 cm above with dry river sand in trenches for cushioning of underground cable line including spreading, leveling, well ramming completed all as specified and directed.
Supplying & laying factory made unreinforced Precast concrete cable covers class LV type 1, flat, Size 250x150x40mm laid in trenches as protection to cables complete all as directed by Engr-in-Charge
Cutting of hardstanding floor/wall for laying of cable including matching with suface by using cement concrete 1:2:4 type B-1 all as specified and directed.
Material and labour for replacement of GI tubing light grade 40 mm bore for passing through cables under the floor ,along the wall or along the pole complete all as specified and directed.
M&L for Boring of holes under road, pavement, hard standing by trench-less technology using ultrasound technique and necessary machine suitable to pass through 40 to 80 mm bore GI tubing /cable etc complete all as specified and directed. Note: GI pipe shall be measured and paid seperately under relevant item.
Supply and fix in replacement of 9/12 watt LED light fitting decorative type wall mounting fixture including LED lamp compact and energy efficient epoxy powder coated luminaire, white metal swing Arm Wall lamp with Bulb and connecting with copper conductor flexible cable from ceiling rose to conector of the light complete all as specified and directed by Engr-in-charge.
AGGARWAL & CO (BID ID -3138525)
m/s s.n. builders (BID ID -3138770)
Jawandha Enterprises (BID ID -3138952)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .