| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.9 LAccepted-AOC | L1 | Accepted-AOC Reasonable lowest tenderer | |
| 2 | L2₹17.2 L+₹82,510.80 (5.04%)Rejected-Finance 0 3 SHASTRI STREET FEROZEPUR CITY PB PIN 152002 | FEROZEPUR CITY | FEROZEPUR | PUNJAB | 152002 | L2 | Rejected-Finance Not Lowest tenderer | |
| 3 | L3₹18.2 L+₹1.8 L (11.0%)Rejected-Finance OLD PULL MADIYA JAIRAMPUR AZAMGARH AZAMGARH UTTAR PRADESH 276001 | AZAMGARH | UTTAR PRADESH | 276001 | L3 | Rejected-Finance Not Lowest tenderer | |
| 4 | L4₹18.3 L+₹1.9 L (11.8%)Rejected-Finance | L4 | Rejected-Finance Not Lowest tenderer | |
| 5 | L5₹18.7 L+₹2.3 L (14.2%)Rejected-Finance | L5 | Rejected-Finance Not Lowest tenderer |
Tender Value
₹14.8 L
EMD Value
₹29,500
Closing Date
20 Jul 2022, 6:00 pmClosed
GE (East) Ferozepur Cantt
GE (East) Ferozepur Cantt
Spl Repair/ Replacement of LT Panels and connecting items at New MES IB and MES Installation under GE (East) Ferozepur Cantt
2022_MES_505710_5
8156/GE/E/FZR/21-22/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (East) Ferozepur Cantt
Please refer Tender Documents
8 documents required · 8 mandatory
₹500
Yes
GE (East) Ferozepur Cantt
₹29,500
Yes
12 Aug 2022
2 Jul 2022
22 Jul 2022
2 Jul 2022
20 Jul 2022
13 Jul 2022
Amount
Excavation in trenches not exceeding 1.5 Mtrs. wide and not exceeding 1.5 Mtrs. in depth for foundation, laying of cablesetc and getting out in hard/dense soil complete all as specified.
Removing excavated material (Soil) n.exc 50 m and depositing where directed at a level n. exc 1.5 Mtrs. above the starting point complete all as specified.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exc. 25cm depth in soil, complete all as Specified.
M& L for Sand cushioning to under ground cable in trenches/existing cable trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable complete all as specified and directed Note:- The punned down thickness shall be measured and paid.
Supply and lay bricks of sub class 'B' type for protection of U/G cable in trenches all as specified and directed.
Supply, laying , jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 185 Sqmm 3.5 core confirming to IS : 7098-1985 laid in trenches or passing through pipes/ducts or fixed to walls/poles complete all as specified and directed.
Supply, laying , jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 95 Sqmm 3.5 core confirming to IS : 7098-1985 laid in trenches or passing through pipes/ducts or fixed to walls/poles complete all as specified and directed.
Supply, laying , jointing and testing of cable XLPE insulated, screened, PVC bedded ,galvanized steel strip or wire armoured heavy duty electric cable with multistranded aluminium conductor, 1100 volts grade, laid in trenches or duct or passing through pipe or fixed to poles walls of size 70 Sqmm 3.5 core confirming to IS : 7098-1985 laid in trenches or passing through pipes/ducts or fixed to walls/poles complete all as specified and directed.
M&L for Sprey painting of LT Panel complete with two coats of synthetic Enamel paints ( Off Whote Color or as per existing color) over a coat of red oxide and other necessary fabrication work like replacement of hinges ,locking Knobs, bending and welding work required for hinges etc as per required at site complete all as Specified and directed by Engr -in- Charge
Supply and fixing in replacement Aluminium Bus Bar/extended strips of MCCBs, of suitable rating as per required size at site complete all as Specified and directed
M&L for repair of Outdoor type LT Panel/Feeder pillar by relacement of Front & Rear doors/ shutters,Made out of CRCA Sheet 3.15 mm thickness with necessary fabrication work like replacement of hinges,locking knob Bending,welding and paining with two coats of Enamel paints over a coat of red oxide Matching with existing panel color as required at site complete all as specified and directed by Engr -in- Charge.
Supply and fixing in replacement single run FRLS PVC insulated multicore standard shealthed cooper conductor cable of 25 Sqmm single core for internal wiring inside the LT Panel as per standered color coding for three phase and neutral including thimbling of suitable size with nut bolts and insulated from common bus bar to outgoing MCCB complete all as specified.
S&F of MCCB of capacity 400 Amps, 4 pole, 415volt, 50Hz,Adjustable type rupturing capacity 36 KA (minimum) or higher, AC, 50 C/S, fixed in repairs, complete all as specified & directed.
All as per Item No. 15 but 250 A 36 KA, complete all as Specified.
All as per Item No. 15 but 200 A 36 KA, complete all as Specified.
All as per Item No. 15 but 160 A 25 KA, complete all as Specified.
Boring of holes under road, pavement, hard standing for laying pipe for crossing cable including getting out, disposal of rubbish off to a distance upto 50 Mtrs including 100 mm GI pipe medium grade, complete all as Specified.
Boring of holes under road, pavement, hard standing for laying pipe for crossing cable including getting out, disposal of rubbish off to a distance upto 50 Mtrs including 80 mm GI pipe medium grade, complete all as Specified.
Boring of holes under road, pavement, hard standing for laying pipe for crossing cable including getting out, disposal of rubbish off to a distance upto 50 Mtrs including 50 mm GI pipe medium grade, complete all as Specified.
Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (Preferably in vertical position) earth pit not less than 2.25 metre below normal ground level with top edge of the earth plate not less 1.5 metre (BGL) connected to galvanized iron earth strip 32 x6 mm by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 50mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 50 mm bore “light grade” galvanized iron protection pipe for earth strip 32 x6 mm upto 5m length, charcoal, common salt, complete all as shown in EP No 1 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion, complete all as specified and directed. Note : GI earthstrip 32 x6 mm more than 7.5 m will be measured and paid separatly.
Marwaha Builders
ABHISHEK AND COMPANY
A N CONSTRUCTION CO
S.R. Kaura and Company
DHAWAN CONSTRUCTION COMPANY
Supreme Constructions
M/S Sandhu Const.Co.
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .