Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹44.3 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹47.0 L+₹2.7 L (6.17%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹48.8 L+₹4.5 L (10.2%)Rejected-AOC | L3 | Rejected-AOC L3 |
Tender Value
₹49.1 L
EMD Value
₹98,200
Closing Date
4 Jul 2024, 3:00 pmClosed
Chief Engineer, CEG, GSO
Room No. 306, GSO Annex building, Kalpakkam - 603102
Maintenance of Earth Pits
2024_GSO_810487_1
GSO/CTC/ESD/23/2024
Open Tender
Electrical Works
Item Rate
365 days
Kalpakkam Township
As stipulated in NIT/tender
8 documents required · 8 mandatory
₹0
₹98,200
16 May 2025
11 Jun 2024
5 Jul 2024
11 Jun 2024
4 Jul 2024
28 Jun 2024
12 Jun 2024 - 25 Jun 2024
Amount
Supply, installation and testing of GI Pipe Earth Electrode as per IS: 3043 including RCC Chamber and RCC cover slab as per Drawing Nos. IGC/ESD/5060/1007/1 & IGC/ESD/5060/1008/1 are enclosed. (50 Kg. Each Bentonite & Charcoal shall be provided for each earth pit). (Refer Sec VI, Clause No.12.4).
Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats including excavation and refilling as per the detailed specification and as directed by the Engineer in Charge. No cutting or drilling permitted after galvanisation.(Refer Sec VI, Clause No.12.9)
25 x 3 mm GI flat
Supply, fabrication and installation of the following size of Hot dip Galvanised GI Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. No cutting or drilling permitted after galvanisation. (Refer Sec VI, Clause No.12.9).
25 x 3 mm GI flat
Maintenance of Earth Pits (Including supply of Sodium Bentonite) and measurement of Earth Pit Resistance as per the specification.
Maintenance of Earth Pits (Excluding supply of Sodium Bentonite) and measurement of Earth Pit Resistance as per the specification
Supply and replacing following earth pit chamber parts after removing and disposing off old/damaged part as per drawing No. IGC/ESD/5060/1008/1 and as directed by the Engineer in Charge.
RCC Top cover alone
RCC Ring with cover
Supply and installation of 150 mm Dia. 2 Mtrs Long, NP 2 Class Hume Pipes Direct in ground at a depth of 1200 mm including supply of collars and fixing them with 1:1 Cement mortar and curing, including excavation in all types of soil, backfilling complete as directed by Engineer-in-Charge (Refer Sec VI, Clause No.8.1).
Supply and installation of 150 mm Dia. 2 Mtrs Long, NP 2 Class Hume Pipes across the road at a depth of 1200 mm including supply of collars and fixing them with 1:1 Cement mortar and curing, including cutting for crossing of existing road and excavation of all types of soil, backfilling, normalisation of road etc complete as directed by Engineer-in-Charge. (Refer Sec. VI. Clause No. 8.2).
Excavation of soil including refilling with excavated earth an disposing surplus earth at places as directed within a lead of 10 Mtrs. and initial lift up to 1.5 mtrs. including neat banking as per detailed specification at Kalpakkam Township. (Ref Sec VI, Clause No. 2).
Excavation in hard soil including refilling with excavated earth and disposing surplus earth at places as directed within a lead of 10 Mtrs. and initial lift up to 1.5 Mtrs. including neat banking as per detailed specification at Anupuram Township.(Ref Sec VI, Clause No. 2).
Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of One number PVC / HRPVC / XLPE insulated and PVC sheathed stranded aluminium / copper conductor power cable of 1.1 KV grade of following sizes direct in ground including excavation, sand cushioning, protective covering with chamber burnt/cement bricks on sides & top, refilling the trench and providing RCC route indicator etc as required (Note: Cable will be issued at free of cost by department), (Ref. sec VI, Clause No. 3)
3 / 3.5 / 4 Core up to 25 Sq. mm
3 / 3.5 / 4 Core x above 25 Sq. mm to 3 / 3.5 / 4 Core x up to 120 Sq. mm
3 / 3.5 / 4 Core x above 120 Sq. mm but not exceeding 3 / 3.5 / 4 Core x 240 Sq. mm
3 / 3.5 / 4 Core x above 240 Sq. mm to 3 / 3.5 / 4 Core 400 Sq. mm
Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC / HRPVC / XLPE insulated, Stranded Aluminium / Copper conductor cables of following sizes in built-in -trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued at free of cost by department). (Ref Sec. VI, Clause No. 3)
3 / 3.5 / 4 Core up to 25 Sq. mm
3 / 3.5 / 4 Core x above 25 Sq. mm to 3 / 3.5 / 4 Core x up to 120 Sq. mm
3 / 3.5 / 4 Core x above 120 Sq. mm but not exceeding 3 / 3.5 / 4 Core x 240 Sq. mm
3 / 3.5 / 4 Core x above 240 Sq. mm to 3 / 3.5 / 4 Core 400 Sq. mm
Retrieval of the existing One number PVC / HRPVC / XLPE insulated and PVC sheathed power cable of 1.1 kV grade of following sizes laid direct in ground including Removal of end termination, excavation of trenches, retrieving of bricks and back filling as per the detailed specification.(Refer Sec.VI. Clause No. 5)
3 / 3.5 / 4 Core up to 25 Sq. mm
3 / 3.5 / 4 Core above 25 Sq. mm and up to 120 Sq. mm
3 / 3.5 / 4 Core above 120 Sq. mm and up to 240 Sq. mm
3 / 3.5 / 4 Core above 240 Sq. mm and upto 400 Sq. mm
Retrieval of the already laid One number 1100 Volts Grade XLPE / HRPVC insulated, Stranded Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of end termination GI spacer, clamps etc as per the detailed specification.(Ref. Sec. VI, Clause No.5)
3 / 3.5 / 4 Core up to 25 Sq. mm
3 / 3.5 / 4 Core above 25 Sq. mm and up to 120 Sq. mm
3 / 3.5 / 4 Core above 120 Sq. mm and up to 240 Sq. mm
3 / 3.5 / 4 Core above 240 Sq. mm and upto 400 Sq. mm
Relaying of one number PVC/HRPVC/XLPE insulated and PVC sheathed power cable of grade 1.1 KV of following sizes direct in ground including transportation of cables, excavation and backfilling of soil, supply of sand etc as per the detailed specification. (Note: Cable & Brick will be issued at free of cost by department) (Refer Sec VI, Clause No.6)
3 / 3.5 / 4 Core up to 25 Sq. mm
3 / 3.5 / 4 Core above 25 Sq. mm and up to 120 Sq. mm
3 / 3.5 / 4 Core above 120 Sq. mm and up to 240 Sq. mm
3 / 3.5 / 4 Core above 240 Sq. mm and upto 400 Sq. mm
Relaying of one number 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of following sizes in built-in trenches on walls, poles and through embedded pipes using the retrieved spacer & clamps as per the detailed specification. (Note: Cable will be issued at free of cost by department) (Refer Sec VI, Clause No.6)
3 / 3.5 / 4 Core up to 25 Sq. mm
3 / 3.5 / 4 Core above 25 Sq. mm and up to 120 Sq. mm
3 / 3.5 / 4 Core above 120 Sq. mm and up to 240 Sq. mm
3 / 3.5 / 4 Core above 240 Sq. mm and upto 400 Sq. mm
Retrieval of the existing One number PVC / HRPVC / XLPE insulated, PVC sheathed armoured Power cable of grade exceeding 1.1 kV but not exceeding 11 kV grade, following sizes laid direct in ground including Removal of end termination, excavation of trenches, retrieving of bricks, slabs & back filling as per the detailed specification. (Refer Sec VI. Clause No. 5)
3 Core upto 120 Sq. mm
3 Core above 120 Sq. mm and Upto 240 Sq. mm
Retrieval of the already laid One number 11 kV (E), 3 Core, Aluminium Conductor, XLPE insulated Power cable of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of end termination GI spacer, clamps etc as per the detailed specification. (Refer Sec VI, Clause No. 5)
3 Core upto 120 Sq. mm
3 Core above 120 Sq. mm and Upto 240 Sq. mm
Relaying of one number PVC/HRPVC/XLPE insulated and PVC sheathed power cable of grade exceeding 1.1 KV but not exceeding 11kV grade of following sizes laid direct in ground including transportation of cables, excavation and backfilling of soil, supply of sand etc as per the detailed specification. (Note:-Cable, Brick & Slab will be issued at free of cost by department). (Refer Sec VI, Clause No.6)
3 Core upto 120 Sq. mm
3 Core above 120 Sq. mm and Upto 240 Sq. mm
Relaying of one number PVC/HRPVC/XLPE insulated and PVC sheathed power cable of grade exceeding 1.1 KV but not exceeding 11kV grade of following sizes in built-in trenches on walls, poles and through embedded pipes using the retrieved spacer & clamps as per the detailed specification. (Note: Cable will be issued at free of cost by department),(Refer Sec VI, Clause No.6)
3 Core Upto 120 Sq. mm
3 Core above 120 & Upto 240 Sq. mm
Supply and Installation of MS Brackets, Supports, Frame work, Clamps, Base Channels,etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting/galvanising as follows including supply of required, fasteners, nuts, washers, etc.(ReferSec VI, Clause No.11).
MS Fabrication 1 Coat of primer and Two coats of Synthetic Enamel Paint.
Supply and Painting One coat on metallic surfaces of Electrical equipments and other required surface at all level with following paint (Asian or Approved brand, colour and manufacturer) to give and even shade including preparation of the surfaces, scaffolding complete all as per specifications and as directed by the Engineer - in - Charge.
Synthetic Enamel Paint
End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No. 10.1).
4 Core x 10 Sq. mm UG cable
4 Core x 16 Sq. mm UG cable
3.5 / 4 Core x 25 Sq. mm UG cable
3.5 / 4 Core x 35 Sq. mm UG cable
3.5 / 4 Core x 50 / 70 Sq. mm UG cable
3.5 / 4 Core x 95 / 120 Sq. mm UG cable
3.5 / 4 Core x 185 Sq. mm UG cable
3.5 / 4 Core x 240 Sq. mm UG cable
3.5 / 4 Core x 400 Sq. mm UG cable
Clearing light jungle area, bulb weeds, grass including removal all unwanted plants, branches, twigs, wild growth etc.complete, and disposing the same 100 meters away manually or burning them without disturbing other areas etc., complete all as directed by the Engineer-in-Charge. Contractor must inform the Engineer-in-charge and prior permission shall be obtained from him for burning the wild growth.
Supply, installation, testing and commissioning of the following Raychem make Heat Shrinkable Cable Straight Through Jointing Kits (Crimping type) for 3.5 Core Aluminium Conductor, 1.1 kV (E), PVC/XLPE insulated cables of following sizes as specified. Excavation will be measured separately
Straight Through Joint (Crimping type) for 3.5 Core 120- 185 Sq. mm
Straight Through Joint (Crimping type) for 3.5 Core 240 Sq. mm
Straight Through Joint (Crimping type) for 3.5 Core x 400 Sq. mm
Straight Through Joint (Crimping type) for 3.5 Core, 25- 50 Sq. mm
Straight Through Joint (Crimping type) for 3.5 Core, 70-95 Sq. mm
Conveyance of tools and equipments between Townships Kalpakkam and Anupuram to carry out emergency works during monsoon, cyclone, electrical breakdown, etc. as and when required including cost of vehicle hire charges, fuel, driver wages, etc, as per specification and as directed by Engineer In Charge. Note. One operation means to carry out the operation mentioned above for a net working time of 8(eight) hours per day
GPK ELECTRICALS
SRI VINAYAGA ENTERPRISES
Bidder Name
SRI VINAYAGA ENTERPRISES
EC Enterprises
GPK ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .