Karnataka Power Corporation Limited
ARAVIND B K
Up gradation of 2.2/4.6kV to 2.2/11kV Distribution System for Colony power supply at Shimsha HES
KPCL/2026-27/EL/WORK_INDENT4869
KPCL/2026-27/EL/WORK_INDENT4869
Open
Electrical
Two Tender Document System(Two Cover)
KPCL Executive Engineer O AND M Office SVP ShivanaSamudra
14 documents required · 14 mandatory
The intending Bidder shall be have successfully carried out Supply, erection & commissioning of HT line/Transformer of 11KV system /erection & commissioning of Transformer of 11KV & above system in any Central or State Govt. or PSUs or any reputed private organizations. In this regard, the intending bidder shall have successfully carried out the said work as Prime Contractor in a single Work done of value not less than Rs.27.74 lakhs in Central or State Govt. or PSUs or any reputed private organizations in last preceding five financial years and shall furnish copy of the related Work order and Work done/work completion certificate issued by the competent authority as documentary evidence. Cost of completed works of previous years will be given 10 percent of simple weightage per year to bring them to current year price level
The Successful Bidder shall have Class-I or above (for Karnataka State)/ Class-A or above (other than Karnataka State) Electrical Contractor License. In this regard, the bidder shall furnish an undertaking as per KPCL format enclosed in the Tender document)
The intending bidder in his name shall have achieved in at least two financial years an average annual turnover of Rs.55.48 lakhs in the last preceding five years and furnish annual turnover certificate OR Profit & Loss statements duly certified by the Chartered Accountant. Financial Turnover of previous years will be given 10 percent of simple weightage per year to bring them to current year price level
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
₹1,390
₹1.1 L
12 Oct 2026
12 Oct 2026
3 Nov 2026
30 Oct 2026
Up gradation of 2.2/4.6kV to 2.2/11kV Distribution System for Colony power supply at Shimsha HES
Supply, erection, installation, Testing and commissioning of 300KVA, 2.2KV/11KV 3phase , Oil Natural cooled, Outdoor type Distribution Transformer Power:300kVA,Phases:3Primary Voltage:2200+ or - 5%V S...
Supply, erection, installation, Testing and commissioning of 300KVA, 2.2KV/433V 3phase , Oil Natural cooled, Outdoor type Auxilary Transformer Power: 300 kVA Phases: 3 Primary Voltage: 2200 + or -5%V ...
Supply, erection, installation, Testing and commissioning of 125KVA, 11KV/433V 3phase , Oil Natuaral cooled, Outdoor type Auxilary Transformer Power: 125 kVA Phases:3 Primary Voltage: 11000+ or -5%V S...
Supply, Erection, Testing & Commissioning of Distribution Transformer - 3 Phase, 11kV/433V - Stacked Core with Oil - A. OPEN BUSHING TYPE 63kVA, Aluminum Wdg, Star 1 (4 Star).
Double Pole Transformer Structure complete with cross arms, braces, clamps, bolts & nuts and washers including 2 No of Poles For 25/63/100 kVA 4/5 Star Rated Transformer on PSCC Pole - 9 Mtr Long, 300...
Providing 2 Pole Structure at the Tapping Point Using RCC Pole complete with cross arms, Polymeric Insulator, Guy Set, Spiral Earth Electrod, Caution/Danger Board, Anti Climbing Device, 11 kV, 400 Amp...
Supply of 11 kV, 3 Core, HTUG Cable for insulations High-quality clean XLPE compound shall be used (Free from micro voids, Moisture content, ambers and contaminations) with pressure extruded, inner sh...
Laying of cable in Existing Trench/GI pipe/ Stone Ware/RCC Hume pipe using Wooden/ Aluminum Rollers as directed by the departmental staff 3x95 to 3x240 Sqmm
Supply of 1.1 kV, XLPE or Heat-resistant PVC insulated, PVC extruded Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armoring strip thickness and resistivity as per IS-3975-...
Supply of Straight Through Jointing Kits HS Type suitable for 3Cx95 Sqmm Cable
Making of Straight Through Jointing Kits HS Type suitable for 3Cx95 Sqmm Cable
Supply of 11kV XLPE UG Cable Termination Kit Outdoor HS Type Suitable for 3Cx95 Sqmm
Making of 11kV XLPE UG Cable Termination Kit Outdoor HS Type Suitable for 3Cx95 Sqmm Cable
Supply of 11kV XLPE UG Cable Termination Kit Indoor HS Type Suitable for 3Cx95 Sqmm
Making of 11kV XLPE UG Cable Termination Kit Indoor HS Type Suitable for 3Cx95 Sqmm Cable
Providing 2 Pole Structure at the Tapping Point Using RCC Pole including 9 Mtr RCC Pole, 11 kV, 400 Amps Double Break GOS, 11 kV, 400 Amps Double Break GOS, etc.
Supply & Erection of Lightning Arrester a) 9 kV, 5 kA Metal Oxide Ceramic Type with ground disconnector
Transformer grounding - GI Grounding pipe, B - Class, 42 mm dia, 2.5 Mtr long, 3.2 mm thick with bolts nuts, GI Strips and washers Per complete Minimum Weight of GI Pipe: 7.3 Kgs
Providing Concreting with Material & Labour Base concreting CC 1:4:8 For 9 Mtr Square Pole 650x650x150 mm for DP Structure.
Providing Pole concreting CC 1:2:4 (without coping) For 9 Mtr Square Pole for DP Structure
Labour charges for Ground mat for Grounding of equipment with various sizes, 50x6mm G.I. Flat and connecting Equipment to the earth mat/ground pit. Each point of earthing with all formation works like...
Supply of Earth Flat of 25mm (25x3, 6)
Digging of Pit for providing GI Pipe type Earthing in Ordinary/ Hard Soil.
Supply of Grounding Material Pipe Grounding GI Grounding pipe, B - Class, 42 mm dia, 281674 No 592 626 2.5 Mtr long, 3.2 mm thick with bolt, nut, GI Strips and washer complete Minimum Weight of GI Pip...
Supply of Good Quality well burnt Charcoal for grounding 600095 No 412 600 purposes packed in non-returnable gunny bag of 30 Kg each
Supply of Good Quality Salt for grounding purposes 607054 Bag 275 275 packed in 50 Kg gunny bag
Supply, erection & commissioning of 11KV VCB Panel- Comprises of - 12kV 26.3KA for 3Sec. 630A, 3P Rated Voltage: 12 kV Rated Current: 630 A Short-Circuit Breaking Capacity: 25 kA for 3 sec Frequency: ...
Earth Excavation for RMU Foundation Work - Earth Excavation for RMU Foundation Depositing of earth on Bank up to a lead of 50 Mtr and with a lift up to 1.5 Mtr in Ordinary Soi/ Hard Soil.
KSRB 2-4 Refilling the RMU foundation with the approved new earth with initial lead of 50 Mtr including watering and tamping layers of 15 cm thick etc., complete.
Transporting RMU (Compact) unit from store to work spot including loading, unloading. (No separate crane charges 1 Panel
Fixing foundation frame of channels and angle iron welding fixing in concrete aligning the RMU on foundation bed, assembly of units, connecting Bus Bars from panel to panel initial filling of oil etc....
Lettering the RMU with enamel paint and also writing single line diagram of each panel, caution Board, Danger Board etc., Per including cost of Paint, Brush etc.
Dismantling of 100kVA, 2.2/4.6kV, 1 Phase Power Transformer - same as erection
Dismantling of 50kVA, 4.6/0.415kV, 1 Phase Power Transformer - same as erection
Dismantling of 100kVA, 4.6/0.415kV, 1 Phase Power Transformer - same as erection
Dismantling of 1Cx95Sqmm 6.6kV Cable - 75% of erection charges.
Dismantling of RCC/PSCC Pole of 9 to 10 Mtr long in a pit of 1.8 Mtr depth 1 - 75% of erection charges.
Providing chain link fencing 50 mm size of 8 guage properly stretched between square Poles of size 50*50*3 and fixed with suitable bolts & nuts, the free ends shall be welded to the Pole and block pip...
Supplying and Spreading of Jelly 200mm thick with 40mm jelly with all lead and lifts.
Construction of platform with size stone, cement concert for erection of 500 kVA Transformer/Metering cubicle/Heavy Equipment. Construction of platform (1.5x1.5x1.2) Mtr in size stone, for erection of...
Supplying & Laying cable trays including welding, fixing of supports, Cable tray of 300 mm width (suitable for cable ducts of A, B & C type)
Supply Caution/Danger Board Using 1.6 mm Thick 300*250mm -MS HT 11000 Volts with Reflecting SE Paint as per IS standards
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
TENDER DOCUMENT-UPGRADATION OF COLONY POWER SUPPLY - R2-09-10-2026.pdf
Tender Document • 2.00 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .