CWE FEROZEPUR
HQ CWE FEROZEPUR CANTT PIN 152001
REPAIR/MAINTENANCE OF VCB HT PANEL AND CONNECTED ITEMS AT MRS AND OTHER HT SUB STATIONS HT OH/UG DISTRIBUTION SYSTEM AT EAST and WEST OF JHOKE ROAD AND TRANSFORMERS UNDER GE (EAST) FEROZEPUR CANTT
2026_MES_798858_1
CWE/FZR-89/2026-27
Open Tender
Civil Works
Item Rate
365 days
FEROZEPUR CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE (East) Ferozepur
₹2.0 L
Yes
16 Nov 2026
16 Nov 2026
19 Dec 2026
16 Nov 2026
12 Dec 2026
7 Dec 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Disconnection all electrical connection HT/LT from the bushings/terminal box of the unserviceable distribution transformer of capacity 400 to 500 KVA, of any make and specifications, indoor/outdoor type from existing position i.e. 2/4 poles structure or PCC foundation; dismantling, taking down and opening the transformer for repair by transporting the transformer to authorized Workshop (100 KM), opening of top cover including conservator, breather and allied items, inspecting the same to assess the repairs required, carryout the repairs. Cleaning, greasing and overhauling including taking out and replacement of unserviceable/worn out parts with new parts, fixing parts by draining out transformer oil complete all as required to make the transformer serviceable. Refilling transformer oil duly charged upto min BDV 60 KV, assembling, removing of the burnt parts i.e tape, paper insulating strings etc gently and carefully, washing of the dust, rust and dirt from all parts incluiding taking out HT/LT leg coil core tank and cooling tubes, painting the inner side tank by zinc chromate paint and preparing the same for re-assembling after carrying out required repairs, replacement, overhauling, commissioning and testing at workshop and bringing back to the original location after repairs and overhauling where the transformer was originally installed; fixing and installing in original position, making all electrical/mechanical connections, commissioning and testing to the entire satisfaction of Engineer-in-Charge complete all as specified and as directed.
Note :
(i) Unit rate quoted by the contractor shall be deemed to include for taking out and reinstalling after repair of transformer with the help of crane, including transportation to workshop and back incluiding handling, loading and unloading etc..
(ii) Unserviceable wornout items/spare required shall be measured and paid separately under respective items of BoQ. (iii) Refilling in dehyrated transformer oil shall be deemed to be included in the unit rates qouted by the contractor. Fresh/New tranformer oil shall be measured and paid for separately under respective item of BoQ. But tranformer oil shall be sold to the contractor. (iv) New copper winding of the tranformer shall be measured and paid for sepataely | 8 | Each Job | - | - |
| 2 | All as per item No 1 here-in-before but 150 KVA to 315 KVA. | 8 | Each Job | - | - |
| 3 | All as per item No 1 here-in-before but 75 KVA to 125 KVA. | 4 | Each Job | - | - |
| 4 | Supply only HT/ LT coil DPC aluminium wire /strip of existing size(gauge),grade and in weight complete with insulating material for transformers of capacity 75 KVA to 500 KVA complete all as specified and directed. | 460 | Kg | - | - |
| 5 | Supply only HT/LT coil DPC copper winding strip of existing size (gauge), grade and in weight complete with insulating material for transformers of capacity 75 KVA to 500 KVA, complete all as specified and directed. | 2,300 | Kg | - | - |
| 6 | Supply only HT brass spindles including, heat resistance gasket, nuts, bolts, washers for transformers of capacity 75 KVA to 125 KVA as per existing type, dia and length complete all as specified and directed. | 8 | Each set | - | - |
| 7 | All as per item No 6 here-in-before but for transformers of capacity 150 KVA to 315 KVA . | 8 | Each set | - | - |
| 8 | All as per item No 6 here-in-before but for transformers of capacity 400 KVA to 500 KVA. | 8 | Each set | - | - |
| 9 | Supply only HT porcelain bushing for transformers of capacity 75 KVA to 500KVA complete all as specified and directed. | 10 | Each | - | - |
| 10 | Supply only LT brass spindle including heat resistance gasket, nuts, bolts, washers for transformers of capacity 75 KVA to 125KVA complete all as specified and directed. | 5 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
BOQ_896201.xls
BOQ • 1.60 MB
Tender89.pdf
Tender Documents • 1.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .