Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.8 LAccepted-AOC 23 3RD FLOOR BNCCI HOUSE R N MUKHERJEE ROAD WEST BENGAL KOLKATA 700001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹24.5 L+₹2.7 L (12.4%)Rejected-Finance 23 2 PANCHANANTOLA ROAD KOLKATA 700041 | KOLKATA | HOWRAH | WEST BENGAL | 700041 | L2 | Rejected-Finance L2 | |
| 3 | L3₹27.4 L+₹5.6 L (25.9%)Rejected-Finance GR 8 ADDA 1 FLOOR CITY CENTRE DURGAPUR 713216 | DURGAPUR | PASCHIM BARDHAMAN | WEST BENGAL | 713216 | L3 | Rejected-Finance L3 | |
| 4 | L4₹28.4 L+₹6.6 L (30.4%)Rejected-Finance 0 KALIKAPUR KALIKA PUR CHAMPAHATI SOUTH 24 PARGANAS WEST BENGAL 743330 | 24 PARAGANAS SOUTH | WEST BENGAL | 743330 | L4 | Rejected-Finance L4 |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
17 Jul 2021, 9:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE AED PWD
Office of the Executive Engineer,Asansol Electrical Division,PWD
Arrangement of necessary Power Supply DG Back-up and Oxyzen Connection for operation of PSA Plants of Asansol District Hospital Paschim Bardhaman Power Back Up of 250KVA DG for PSA of Asansol District Hospita
2021_WBPWD_336257_1
WBPWD/EE/AED /Short bid eNIQ-21/2021-22
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
Near Polo Ground, Asansol
Please refer Tender documents.
4 documents required · 4 mandatory
₹50,000
5 Jul 2022
12 Jul 2021
19 Jul 2021
12 Jul 2021
17 Jul 2021
13 Jul 2021
180 days
Amount
(1)- Supply, Delivery, Testing & Commissioning of 250 KVA/ 200 KVA Silent Diesel Generator Set ( Enginee BHP 330) with microprocessor based genset controller suitable for solo application & alternator both mounted on a common base plate with fuel tank, residential silencer, AVM Pads with its leads, first fill of lube oil & CPCB approved Acoustic Enclosure having approx. size ( L-4800mm, W - 1500 mm, H - 2025 mm) subject to observation of Pollution Norms and comfirming to least BIS code with capacity of 10% over loading for one hour in twelve hours duration having following main items and accessories
ENGINE
(Make- Cummins(Jakson)/Greaves/Kirloskar/Ashok Leyland) DG set will be provided as per choice of EIC
Engine Type : 4 Stroke Diesel Engine
Rated Output : 330 ВНР
Duty : PRIME
Cooling : Water cooled with radiator
Cylinder : 6
Aspiration : Turbo Charged CHANGED AIR COOLED
Type of Govemer : Electronic
Fuel Tank Capacity : Minimum capacity 100 as per manufacturer's standard Ltrs.
Fuel Consumption at 75% rated Load with Radiator or Fan : As per Manufacturer's standard Ltr./ Hr. or Less
Fuel Consumption at 100% rated Load with Radiator or Fan : - As per Manufacturer's standard Ltr./ Hr. or Less
Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp, warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
Exhaust system -Provided with turbo charger and residential exhaust silencer with manifold flexible bellow and companion flanges. Coupling and fly wheel -Coupling, fly wheel and flywheel housing. Lubricating system -Provided with oil pan, engine mounted lube oil pump and full flow lube oil filter, lube oil bypass filter along with first fill of lube oil. Fuel system -Comprising of fuel pump with Electronic / Mechanical Governor, fuel injector, 12 V solenoid coil and replaceable fuel filter. Starting system -12 V D.C electric starter and 12 V Battery charging alternator. Safety control -Comprising of protection against – low lube oil pressure trip, High water temperature trip High/Low DC voltage trip, weak battery trip and over speed trip
Starting system: 24V DC Electric starter motor,24V DC battery charging alternator
Battery : 2x12V, 150 AH Dry type Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
(1.03)- Integrated Control System :
(1.04)- (a) Physical Construction - 128 x 64 mm LCD alphanumeric display with 8 membrane key inter face, Non metallic enclosure, LED Display - Fault warning and generator set status , Key switch for OFF/RUN/START.
(b)- Governor & Speed / Frequency regulator - Integrated electronic Governing ( adjustable up to 5%)
© - Operator Interface - Manual Stop/Starter Remote Satrt/Stop Cyclic cracking, Alpha numeric screen, Alternator trim adjustment.
(d) AC Instruments - 3 phase AC Ammeter, 3-Ph AC Voltmeter, KW meter, KVA meter, PF meter, Frequency meter.
(e)- Measurements/ Instruction - Lube oil pressure, Coolant Temperature, Engine speed, Hours run, battery voltage.
(f) EngineProtection - High coolant temperature 9 warning & shutdown) Low lube oil pressure ( Warning & Shitdown), Fail to crank ( Shutdown), Overspeed ( Shutdown),Low/ High battery Voltage ( Warning), Low Coolant level shutdown.
(g)- AC Protection - Over Frequency ( shutdown), Under Frequency ( warning) , Over Voltage ( Shutdown), Over Current ( Shutdown), Under Voltage (warning).
(1.05)- (h)- Other Accessories - Operating temperature range 0-60°C, common fault alarm, common shutdown, date and time stamp for alarm. Diamension ( in mm) are 267x378x157.
(i) Additional features - Speed bias or raise / lower inputs are provided for paralleling, remote monitoring capability through seprate interface modules. Engineering tool/ manufacturing tool compatible with existing tools, 6 configurable discrete Output, 2 Configurable discreate Inputs, Fault Indication on front panel display using fault LEDs, Smooth transition to rated speed, Programmable fault threshold, Controlled ramping to restricted startup smoke.
(j) Other - vibration damper, Fly wheel with housing.
(B). ALTERNATOR: Make - Make : Stamford/Crompton Greaves /Kirloskar/ Ashok Ley Powerrating - 250 KVA , 08 pf ( Lag)] Type of laternator - Permanent Lubricating Single Bearing, Brushless, self excited and self regulated through an AVR. Protection - IP 23 protections with class H insulation. Overlaod - Permissible over laod of 10% for one hour in 12 hours of operation. (a) ± 0.5%Voltage regulation (Max.) in static (b) IP : 23 protection with class "H"© permanent lubricating nearing
(d) permissible over laod of 10% for one hour in 12 hours of operation.
(1.08)- Silent Feature of Acoustic Enclosure ( 250 KVA) :
(1.09)- (a) The enclosure is of moduler construction with the provision to assemble and dismantle easily at site.
(b)- The Sheet metal component are NINE TANK pre treated before powder coating.
© The enclosure is power coated ( inside as well as outside) with special pure polyestar base powder. All nut an bolts / external hardware are made from stainess steel.
(d) The doors handle are looking type.
(e) The door handle are lockable type.
(f) The sound proof of the enclosure is done with quality Rock wool/Mineral wool confirming IS: 8183. the rock wool is further covered with fiber glass tissure and perforated sheet.
(g) Special design attenuators are provided to control sound at air entry and exit points.
(h) Temperature of enclosure does not exceed beyond 7-10°C of ambient temperature.
(i)- There is a provision of emergency shut down from out side the enclosure.
(j)- noise level is <75 dB ( A) at 1 mtr. Distance under free field condition, i.e as per CPCB norms.
(k) Door hinges are made of anti corrosive special alloy.
(l) Viewing window is fitted with toughed glass instead of acrylic sheet.
(1.10)-(H)- Documentation :
1 Set of following documentation should be with each set.
(a) O&M Manual of Diesel Engine.
(b) Spare parts list of Diesel Engine.
© Test Certificate of Diesel Engine.
(d) Test certificate of Alternator
(e) Test certificate of D.G. set
(f) Warranty card of DG set
(1.11) Supply , Installtion, Testing & Commissioning of Wall / Floor mounted AMF Control Panel fabricated from 14 SWG CRCA sheet and powder coated after 7 ( Seven) tank treatment process. The panel comprises with following items :
(a)- 415V, 400A MCCB with O/L , S/C & E/F Release ( Mk. L & T / Siemens/ ABB)
(b)- 400A, 4 Pole Power Contractor with 2NO + 2NC Aux. Contact block coil voltage 230V AC -2 Nos. (1 No. for DG & 1 No. for Mains) ( Schneider / Siemens / ABB)
©- Indicating Lamps ( with series resistance) red, Yellow, green ( Mk. Siemens0.
(d) Other items are as follows.
(1.12) 1. Emergency Stop push button Red.
2. battery Charger I/P - 230V AC, O/P - 24 V DC with Trickle / Boost Slector Switch arrangement.
4. Microprocessor Based AMF Relay ( 3ph Voltage monitering relay)
5. Hooter (96 sqmm)
6. Cranking Relay
7. 4 Aux Relay card.
8. Aux. Contactor with 1 No. Time Delay 0-60 sec. Timer Block unit.
9. Resistance unit.
10. Control Fuse Links with base.
11. Terminal Block
12. Current Transformer
13. Load Monitor ( For V,A,KW,KVA,KVAr, Frequency & PF metering). ( Silent DG Mk. Jakson Cummins ( Engine Model : QSL 9G 16) (ENGINE : CUMMINS & ALTERNATOR : Satmford / Catterpiller)
ACOUSTIC ENCLOSURE
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustict enclosure must be certified as per CPCB-II norms.
BASE FRAME
Base frame -Common iron channel fabricated base frame containing the engine and alternator mounted through AVM Pads. Fuel Tank -Capacity 170 Lts. Made of 14 SWG sheet metal built inside base fame complete with drain valve, air vent, inlet and out let connection, fuel gauge. Acoustic enclosure -High quality Sound proof, weather proof environmental friendly acoustic encloser fabricated from 14/16 SWG sheet Steel & powder coated specially design to meet up CPCB - II standards to maintain the noise level 75 dB (A) at distance of 1 meter from acquistic encloser under free field condition with hinged gasketted doors with suitable locking arrangement.
TERMS & CONDITIONS
(i) Rate should be quoted inclusive of all applicable taxes and Duty etc.
(ii) All materials, equipments & accessories must conform to relevant IS /IЕС specifications. The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer.
(iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to submit in triplicate copy during delivery of the equipment.
(iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from competent Authority (As per CPCB-II).
(v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer / OEM.
(vi) The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier.
DG Installation
Supply & laying 4 core 240 sq. mm. XLPE/PVC Al armoured cable ( make- polycab/Havells/Gloster) from DG Amf panel to DG , Main Panel to DG and Main panel to site panel a) through existing RCC /Hume/GI pipe/ open masonary trench for single,2,3,3.5.4 core
Supply & Fixing Compression Type gland and finishing end 4 core 240 sqmm
Supply & laying 1 x 50sq. mm. single core cu unarmoured cable ( make- polycab) from neutral busbar to neutral point of DG a) through existing RCC /Hume/GI pipe/ open masonary trench for single,2,3,3.5.4 core
Supply, transporation & pouring of HSD Oil.
Supply, transporation & pouring of HSD Mobil.
S&D of 205 ltr Capacity heavy gauge M.S. sheet barrel at site.
S&D of best quality oil hand pump with 1" dia PVC flexiable pipe (12 ft app.)
S & F exhaust pipe of 150 mm. dia MS black pipe (Thickness 4 mm) including connection with the existing silencer attached with the flexible coupler and S&F flange,bend, nuts, bolts & washers etc. & necessary fixing materials etc. as required from DG set to nearest building (horizontal/Vertical Run) with suitable high temperature painting.
Making insulation by 2" glass wool including netting arrangement and covered with aluminium clading as per direction of the EIC.a) 150mm dia
S&F special type MS angle iron bracket support made of 40x40x5 mm. MS angle with flat iron clamp with nuts, bolts & washers etc. for 150 mm. dia (Vertical Run)
S&F rain protection canopy.
Supply & fixing GI flat with black PVC heat shrink sleeve for covering the 50 x 6 mm.
Hiring charges for scaffolding by bamboo, coir rope by square type arrangement for smooth working and lifting of MS black pipe for vertical installation including dismantling after completion of work.
S &laying of 10core 2.5sqmm copper armour cable a) through UG
b) through GI pipe
c)on wall with saddling as per GS
S/F compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry & S/F socketing with finishing the end of XLPE/PVC armoured cables of 10core 2.5sqmm copper armour cable
Finishing the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc. including supplying sockets, tapes for a) 10core 2.5sqmm copper armour cable
S&F 2 Kg capacity Gas pressure (ABC/DCP) fire extinguisher on wall by suitable size of iron bracket (Make - surex/Fireshield)
S&F 9 ltr. Capacity round fire bucket with iron hook and duly filled up by sand.
S & F EI danger board. (size : 20 cm. x 30 cm.)
Finishing the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc. including supplying sockets, tapes for 50 sq.mm from neutral bus-bar to DG neutral
Earthing with 65 mm dia GI pipe( TATA -Medium) x 3.0 mtr long 1 no. 50x6 mm galvanized( hot dip) steel strip ( 4 mtr long) 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S& F 65 mm dia GI pipe ( ISI-medium)protection (3 mtr long) to be filled with bitumen partly under the ground level and partly above ground level to an avg depth of 3.65 mtrs
Earthing with 50mm. dia GI pipe (ISI-Medium) x 3.64 mm thick x 3.04 mtr. Long & 1 x 4 SWG GI (Hot dip) wire (4 mtrs. Long) with nuts, bolts & washers etc. as per GS (2 nos. for DG set ) as per GS
Excavation of soil for installation of Earth Electrode and filling & ramming
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe
Extra for treatment of soil by using salt & charcoal or coke for plate electrode
JAYBEECO
DURGAPUR POWER
GHOSH ENTERPRISE
technical_641440.pdf
PDF • 0.31 MB
techsummary_641440.pdf
PDF • 0.31 MB
finance_641440.pdf
PDF • 0.32 MB
BOQ Comparative Chart
xlsx • 0.02 MB
finsummary_641440.pdf
PDF • 0.32 MB
21finalorder.pdf
PDF • 0.59 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .