Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹65 L
EMD Value
₹1.2 L
Closing Date
18 Nov 2026, 6:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
CWE (A) Jaisalmer
HQ CWE (A) JAISALMER
MAINTENANCE AND REPAIRS TO VARIOUS 33 AND 11 KV SUB STATIONS AND OH, UG NETWORK OF TCP 01 MRS AT ZONE -I AT JAISALMER MIL STN UNDER GE(A) JAISALMER
2026_MES_794965_1
84496/C/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JAISALMER
AS PER NIT
8 documents required · 8 mandatory
₹1,000
GE (A) JAISALMER
₹1.2 L
Yes
21 Oct 2026
21 Oct 2026
19 Nov 2026
21 Oct 2026
18 Nov 2026
11 Nov 2026
21 Oct 2026 - 28 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for Caliberation/Servicing/Overhauling & testing and commissioning of factory manufactured VCB/RMU, HT 12 KV Phase 3 wire 50 C/S upto 800 Amps, 18.4 KA or suitable amps single panel switch board, vertical isolation and horizontal draw out type vaccum circuit breaker (VCB) confirming to IS-13118, EIC-56 totally enclosed, single busbar floor mounting metal clad indoor extendible fully interlock complete comprising the following :-
(a) CTs primary current injection test .
(b) IR values of CTs
(c) Ratio test of PTs and IR value
(d) Protection relays testing through secondary current injection kit
(e) Voltmeter, ammeter functional tesing
(f) Breaker tesing for tripping time, closing time, contact resistance values and physically healthyness of Vaccum interuptor.
Note:- 1. Wiring of Control Panels of VCBs, wiring of WTI, OTI, CTs, PTs will be including quoted rate if found defective.
2. Contractor will be responsible for arranging the expert for checking and rectification/Alteration of control wiring of safety relays through primary and secondary injection kit alongwith necessary tools & plants.
3. Relay calibration report shall be submitted to the department. | 11 | Each Job | 99 | ₹1,089 |
| 2 | S&F in repair annunciator relay box consisting of 4/6 block 18 to 90 volts DC complete in existing VCB 11/12 KV of CG make and including taking down old relay box of any size complete all as specified & directed by Engr-in-Charge. | 3 | Each | 100 | ₹300 |
| 3 | S&F in repair master trip relay 24 Volts DC complete in existing VCB 33 or 12 KV of CG make and including taking down old unsv relay complete all as specified & directed by Engr-in-charge. | 1 | Each | 100 | ₹100 |
| 4 | S&F in repair master trip relay 110 Volts DC complete in existing VCB 33 or 12 KV of CG make and including taking down old unsv relay complete all as specified & directed by Engr-in-charge. | 3 | Each | 100 | ₹300 |
| 5 | S&F in replacement of earth fault over current relay 24 Volts DC complete in existing VCB 33 or 12 KV of CG make and including taking down old unsv relay complete all as specified & directed by Engr-in-charge. | 1 | Each | 100 | ₹100 |
| 6 | S&F in replacement of earth fault over current relay 110 Volts DC complete in existing VCB 33 or 12 KV of CG make and including taking down old unsv relay complete all as specified & directed by Engr-in-charge. | 3 | Each | 100 | ₹300 |
| 7 | S&F in replacement of auxilary relay 110 Volts DC complete in existing VCB 33 or 12 KV and including taking down old unsv relay complete all as specified & directed by Engr-in-Charge. | 4 | Each | 100 | ₹400 |
| 8 | S&F in replacement of auxilary relay 24 Volts DC complete in existing VCB 33 or 12 KV and including taking down old unsv relay complete all as specified & directed by Engr-in-Charge. | 2 | Each | 100 | ₹200 |
| 9 | S&F in replacement of TCS relay 110/24 Volts DC complete in existing VCB 33 or 12 KV and including taking down old unsv relay complete all as specified & directed by Engr-in-Charge. | 4 | Each | 100 | ₹400 |
| 10 | Supply and fixing in replacement of over current and earth fault IDMT protection relay (digital relay) type CGI 14 N,75/250 Volts complete necessary connection and testing in existing VCB 33 or 12 KV of CG make and including taking down old unsv IDMT protection relay completeall as specified and directed by Engr-in-charge. | 2 | Each | 100 | ₹200 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
TENDER1.pdf
Tender Documents • 2.61 MB
BOQ_891588.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .