Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L2₹31.9 L+₹1.4 L (4.62%)Accepted-AOC WZ 1000 B NANGAL RAYA PANKHA ROAD NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | L2 | Accepted-AOC BONAFIDE BEING LOWEST | |
| 2 | L1₹30.9 LRejected-Finance | L1 | Rejected-Finance NON BONAFIDE | |
| 3 | L3₹33.8 L+₹2.9 L (9.33%)Rejected-Finance SHOP NO 33 GOPI NATH BAZAR DELHI CANTT 10 | DELHI CANTT | NEW DELHI | DELHI | 110010 | L3 | Rejected-Finance NON BONAFIDE | |
| 4 | L4₹33.9 L+₹3.0 L (9.84%)Rejected-Finance | L4 | Rejected-Finance BEING NOT LOWEST | |
| 5 | L5₹34.3 L+₹3.4 L (11.1%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L5 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹50.0 L
EMD Value
₹1 L
Closing Date
22 May 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
ARJUN PATRO,IDSE
GE U ELECTRIC SUPPLY,DELHI CANTT-10
MANNING OPERATION INCLUINDING ROUTINE MAINTENANCE OF 33 /11 KV KHYBER GRID UNDER GE U ELECT SUPPLY DELHI CANTT 10
2021_MES_431710_1
GE ELECT/D-17/2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
GE U ELECTRIC SUPPLY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
₹1 L
Yes
16 Jun 2021
23 Apr 2021
24 May 2021
24 Apr 2021
22 May 2021
8 May 2021
60 days
Amount
Manning & Operation including routing maintenance of 33 /11 KV Khyber grid as per details as under:- (a) The installation is main receiving station and complaint centre minimume 02 electrician per shift shall be provided round the clock .The electrician shall have adequate knowledge of above maintioned job and GE/Engr-in-charge can reject the proposed electrician giving reasoned rejection.No claim shall be admissible on account of rejection of person. (b) Details of equipment:-Transformer step down 33/11 KV capacity 12/16 MVA & 16/20 MVA capacity incl marshal boxes ,accessories & control cables complete -02 Nos , Indoor type transformer stepdown 11 KV/433 Volts capacity 100 KVA -01 Nos , Outdoor type VCB , MOCB/SF-6 circuit breaker 33 KV -10 Nos, Control panel 33 KV breaker -10 Nos , 33 KV bus bar in yard incuding Isolator, CT, PT etc -02 Nos, 11 KV VCB as incomer including control panel -02 Nos , 11 KV Bus Coupler including control panel -01 No , 11 KV VCB as outgoing including control panel -21 Nos,11 KV Capacitor bank complete with control panel -01 No, LT panel -01 Nos,16 MVA/20 MVA transformer -02 Nos, batery charger -02 Nos, battery bank 50 volts DC -02 Nos, & Terminal KIOSK -10 Nos (c) The following checking/testing,supervision shall be carried out by electrician in respect of equpments mentioned at at para (b) above:- (i) Recording of all parameters of system as per indication of all equipments installed in the log sheetas directed by Engr-in-Charge round the clock on daily basis. (ii) Maintainance of fault register (iii) Maintainance of shutdown register (iv) Proper operatiion of 33 KV and 11 KV Breaker (v) Giving of Shutdown by draw out of trolley of breaker . (vi) Proper operation of 33 KV Islolator (vii) Checking of status of LED indication for breaker on , off , trip , spring charge , trip circuit healthy on daily basis. (viii) Checking of status of annunciator, hooter , indicators , meters, TNC switch , emergency trip push button , MCB for AC DC isolation, heater , thermostate on daily basis. .
(ix) Checking of status of Transformer differential relay , line differential relay , main protection numerical relay, Auxillary protection relays such as trip circuit supervision , master trip , PT fuse failure , DC supervision ,CB SF 6 gas pressure low, Main Buchholz trip ,Buchholz OLTC Trip, SPR & PRV trip, Winding temp high trip ,Oil temp high trip. Main Buchholz alarm, Winding temp High alarm, Low Oil level alarm, Oil temp high alarm, and keeping all the relays in reset condition on daily basis. (x) Cheking of Oil temprature of transformer oil as directed by Engr-in-charge. (xi) Checking of winding temprature of transformer as directed by Engr-in-Charge. (xii) Checking of oil level of transformer as directed by Engr-in-Charge. (xiii) Checking the batteries in serviceable and charged condition by checking battery, leads, battery lugs on daily basis. (xiv) Attending of all complaint of the grid. (xv) Cleaning of dust & foreign particles on and around the panel, loose connection earthing connection in the control room and yard. (xvi) Checking of condition of leakage of oil from transformer tank, bushing, radiators and other parts on weekly basis (xvii) Checking of cooling fans on weekly baisis. (xviii) Checking condition of silica gel on weekly basis (xix) Testing BDV of transformer oil as directed by Engr-in -Charge. (xx) Testing of earth resistance of all earthing as directed by Engr-in-charge. (xxi) Checking of DC voltage of system as directed by Engr -in-charge
Note : (i) The contracotor will ensure suitable repalcement of electrician while on leave/weekly holidays and Wages for the same deemed to be included in the quoted rate. (ii ) The contractor shall ensure that electricians/ operator always be present in each shift. In case of absence of any worker the penalty @ Rs 100.00 per hours per electricians/ operator shall be imposed on the contractor. (iii) The contractor shall be responsible for maintaining the complete area (i.e. inside boundary wall ) such as building , hard standing , foothpath etc in neat and clean position . All necessary T&P for cutting /cleaning of grass and vegitation will be arranged by contractor without any extra cost. (iv) The contractor shall provide uniform , raincoat, protective clothing such as hand gloves ,helmet, safety belt , first aid box and shoes etc to all persons on duty and the cost of the same is deemed to be included in quoted rate. (v) Person employed should be working experience of working on HT and LT Installation. (vi) The contractor shall provide log sheet and maintain the the same on daily basis and the cost of the same is deemed to be included in quoted rate.
Worker's wage per person per day per shift (inclusive of GST as applicable)
Employees Provident Fund as per existing rules (Prescribed Rate of EPF as applicable on (minimum wages without GST ) + GST Rate as applicable on Prescribed Rate of EPF as applicable on (minimum wages without GST )
Employees state insurance as per existing rules. (Prescribed Rate of ESI as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of ESI as applicable on (minimum wages without GST )
Contribution of Bonus as per existing rules. (Prescribed Rate of BONUS as applicable on (minimum wages without GST) + GST Rate as applicable on Prescribed Rate of BONUS as applicable on (minimum wages without GST)
Over head & profit on total of srl No 1.03 to 1.06 as applicable.
LWC as per existing rules on total of srl no 1.03 to 1.07. The bidder should note that the minmum wages including all statutory provisions as mentioned in item no 1.03 to 1.07 are exclusive of GST for calculating of labour cess. Refer Sch 'A'Note No 33 (e) on Page No 17 of Tender Document.
NOTE For Item 1 and sub items :- (a) The quoted rate against EPF, ESIC and Bonus shall be considered for payment on actual basis. Contribution towards EPF, ESIC and Bonus is payable only after submission of valid and authentic document in support of having paid the requisite amount of bonus to the workmen, ie proof of payment. (b)The rate quoted shall not be less than minimum wages as notified by Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc as applicable and also not less than applicable rates for contribution of employer towards EPF,ESIC, BONUS and LWC under respective heading /subitems. In case the rates quoted are less than the minimum wages as notified by the Government of India / State Government / Local body whichever is higher including all statutory provisions such as EPF,ESIC,Bonus,taxes etc on the last due date of bid submission. his tender will be treated as non bonafide and will not be considered for acceptance.In such case,the lowest bidder shall be determined from amongst the valid/bonafide bids only. (c) 'NIL' or 'Zero' quoting against OH & Profit will be treated as 'Non-bonafide'.
(d) Contractor is required to quote upto two digits after decimal place or otherwise it will be consdered by rounding off to two digits after decimal place in accordance with Rules for Rounding off of Numerical Values in accordance with IS:02 OF 1960(Revised 2016) of BIS. (e) Any variation in minimum wage, liability of EPF/ESIC/Bonus/LWC/GST shall be adjusted for reimbursement/recovery as under:- (i) Variation in minimum wage including other related statutory provisions shall be adjusted in terms of Condition 63 of GCC (IAFW-2249). (ii)Variation in percentage/rate of GST and LWC shall be adjusted as per instructions in Annexure XVI of MES Manual on Contracts which deals with ‘Reimbursement/Refund on Variation in Taxes Directly Related to Contract Value’
Supplying , transporting, erectiong, testing and commissioning of 36 KV, 1800MVA, 1250A, 50Hz voltage class outdoor type Vacuum Circuit Breaker for use on system voltage 33 KV. The circuit breaker and accessories shall conform to IEC-62271-100 or IS 13118 and other relevant IEC/IS standard. The circuit breaker shall be complete with terminal connection, operating mechanism, control cabinets, cable accessories like gland, terminal block, lugs, necessary steel support structure for CB and control cabinet The circuit breaker shall be required to performs as per technical parameters given below:-
(a) Installation - Outdoor, 3-pole, Vacuum Live-Tank, Porcelain Clad, Switchyard Breaker (b) Rated Voltage - 36 KV (c) Rated Current - 1250A or higher up to 2000Amps (d) Power frequency with stand voltage (KV rms)- 70 KV (e) 12/50 microsecond lighting impuls with stand voltage (KV Peak)-170 kVp (f) Rated short circuit current breaking capacity (3 Sec ) at rated voltage specified 31.5 KA (g) Control Voltage incl. trip/close coil - 50V DC (h) Spring Charging Voltage - 230VAC (j) Symmetrical interrupting capacity (KA/RMS) 31.5 KA (k) Rated short circuit Making Current (KAP)-80A (l) Out of phase breaking capacity (KA rms) as per IEC (m) Rated operating duty as per IEC(o) Temp rise over the design ambient temperature -As per IEC 62271-100 (n) Operating Mechanism -Spring (o) Creepage distance as per IEC-900mm (p) No of trip/close coil 50 V DC-02 Nos (q) Tripping system - 50 V DC Note:- (i) Cost of supply and fix of Outdoor type Terminal Kiosk (TK) having terminals/disconnecting-links for termination of CT/PT wiring including PT secondary fuses complete all as required at site are deemed to be included in the quoted rate. (ii) Cost of construction of foundation including construction material and necessary earth work as per manufacturer design for breaker & TK complete all as required at site are deemed to be included in the quoted rate.
Supplying, installation, testing and commissioning of 11 KV, 630 Amps having short circuit capacity 20kA/3-sec, Outdoor (IP54), RMU (Ring Main Unit) 5 -way comprising of 02 Nos motorized operated Load Break Switches and 03 Nos 630 Amp Fixed-Type motorized spring-charging VCBs electrolytic grade copper busbars all inside single, gas-filled, robotically welded stainless steel 304 (Non Ferrite Non Megnetic Grade) tank with minimum thickness 3+0.5 mm, IP 67 Degree of Protection, internal-arc classified 20kA/1sec, on-site-repairable with site replacable bushing/coupling/mechanism, gas refilling etc. The enclosure shall have padlockable double-door access with anti-theft hinges, fully covering the front facia and cable boxes to ensure fail-safe anti-theft protection. The unit alongwith Bus-connected, fixed-type Auxiliary Transformer shall include the following along with all necessary accessories and fittings as required at site. Location : Harbaksh Stadium
(A) 02 Nos Incoming Load Break Switches module each consisting of following accessories :- (i) Each switching-unit shall be designed as a three position switch. This three function switch combines the functions of switch-disconnector and earthing switch. (ii) 11kV, 630A Load Break Switch with interlocked line-earthing scheme both short circuit current - 20kA/3-sec, Making Capacity - 50kAp - 01 No (iii) Auxiliary contacts - 1NO + 1NC - 01 No (iv) Spring-assisted snap-action motorized mechanism with un-inhibited operating shaft for emergency manual operation with integrated earthing switch - 01 No (v) Cable terminals (site replacable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes) with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access upto 11 KV , 300 Sqmm , 3 Core , XLPE AL cable termination in live-condition : Each Set of 03 (vi) Right angle boots (push on type) : Each Set of 03 (vii) Arc proof cable covers having cable entry from bottom, front with Interlocking mechanism including earth switch - 01 No (viii) Capacitive voltage indication fixed type system as per IEC61243 with LED - 01 Set (ix) Fault Passage Indicator - It shall be provided for each incomer load break unit, FPI with LED/digital display to be added for detection of cable fault - 01 No (x) ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01 No
(B) 03 Nos. Outgoing VCB module each consisting of following accessories :- (i) Each function-unit consists of a vacuum-circuit breaker in combination with a three position-switch.The three-position-switch fulfills the operation of the disconnector-function and earthing function. (ii) 11kV, 630A Fixed-Type VCB module with series disconnector cum earthing switch of short circuit breaking current/withstand - 20kA/3-sec, Making Capacity - 50kAp-01 No (iii) Aux. contacts - 1NO+1NC-01 No (iv) Stored-energy motorized high-endurance spring charging mechanism (M1+), with inbuilt spring-charging lever and mechanically latched ON/OFF push-buttons to allow handle-less and un-inhibited operation -01 No (v) Cable terminals (site replacable Cable bushings situated not beyond 300mm from cable-cover to allow ease of access for installation/testing/replacement purposes) with double-door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access upto 11 KV , 185 Sqmm , 3 Core, XLPE AL cable termination in live-condition. Each Set of 3 (vi) Right angle boots (push on type)-Each set of 3 (vii) 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also.Relay shall record minimum 5 fault records with time stamping . Relay shall be communicable with RS 485 Port on MODBUS Protocol-01 No
(viii) Associated ring-core cast-resin insulated CTs 50/1 Amp , 2.5 VA, 10P10 for protection - Each Set of 3 (ix) Arc proof cable covers with self Interlocking mechanism with earth switch -01 No (x) Capacitive voltage indication fixed type system as per IEC61243 with LED -01 No (xi) Push button for breaker trip (xii) Shunt trip coil 24V DC - 01 (xiii) ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. (xiv) Emergency Trip Push Button - 01. (C) 01 No. Bus-connected, fixed-type Auxiliary transformer with floor-mounted compartment of matching height and depth, positioned along-side RMU to provide required aux. supply and metering consisting of following accessories :- (i) 1-Ph (11kV/rt3):230VAC, 500VA Auxiliary transformer-01 No (ii) 2x12 Volt DC battery-01 Set (iii) Battery charger-01 No (iv) HRC fuse-links for primary side isolation and AC/DC MCBs for secondary isolation-01 Set (v) Voltmeter & RYB LED Indications to confirm AC/DC supply availability-01 Set (vi) Anti-condensation space-heater-01 No (vii) CFL lamp for illumination and 3-pin socket with switch -01 No
(D) Additional equipment deliverd separately or mounted seperately :- (i) Operationg Handle for Manual Isolator/Disconnector/Earthing Operation - 02 Nos (ii) Standard Manometer - 01 No (iii) Operation and Maintenance Manual - 01 No (iv) Installation & Commissioning Manual - 01 No (v) Cable clamping provision (standard) - 01No
Note:- (i) It shall be preferable to have all feeder-switches inside single stainless steel compartment with incomer feeders at the extremities to prevent chances of failure due to plug-in coupling arrangement. (ii) Necessay interclocking arrangement shall be provided for safety and operations (iii) Above switchgear shall confirm to relevant IEC (62271-200) for design, manufacturing and internal arc compliance. Any claims towards internal arc compliance, number of mechanical/electrical/short-circuit operations, gas-leakage rates etc. shall not be accepted unless proven via type-test reports of model being offered. (iv) Cost of Provision of Plinth for RMU as per OEM drawing shall be deemed to be included in the cost inserted by the bidders.
M&L for ON load Centrifuging and dehydration including filteration and cleaning of transformer oil by dehydration machine of 33 KV transformer at site and topping up deficient transformer oil including testing of samples before and after dehydration and filteration complete all as specified and directed. Note :- Deficient quantity of Transformer oil required for top up shall be measured and paid separately under item No 2 here-in -after as supply only.
Supply only transformer oil of approved quality as per IS having dielectric strength of 45-60 KV in 2.5mm gap for filling in OLTC & for topping up in transformer as required and directed
Material and labour for topping up of / filling of SF-6 gas to achieve required gas pressure in 36 KV SF6 breaker and testing complete all as directed by Engr-in -charge.
S&F in replacement of vacuum interrupter suitable for 1250 amps, 11 KV HT VCB complete all as specified and directed.
Supply, testing and commissioning of SCR controlled float cum Boost battery charger three phase 50 Volt 40 Amp Make ; APEX and DC contribution board in common cubicle. The charger is suitable for 415V+- 10% single phase AC input and DC output for 50Volt -200 AH battery bank and supply load.
Supply, testing and commissioning of SMF VRLA battery bank 50 Volt 200 AH consisting of 25 Nos cells of 2V-200AH each capacity alongwith intercell Copper Connector, SS Nut bolt, MS Power coated stand in factory charged condition. Make Exide
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified.
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm complete all as specified..
Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1, flat size 230mmx 112mm x 75mm complete all as specified..
S&F Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified..
S&F 3.15mm dia MS wire 75x75mm mesh , made up into mattress or cages appx 2.00 mtr height and fixed with flate iron /angle by welding in position complete all as specified directed .
M & L for 2 coat of synthetic enamel painting over a coat of red oxide to steel surfaces including preparation of newly surface complete all as specified.
Dismantling of HT insulators any type, any size complete all as specified..
Dismantling of air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism complete all as specified..
Dismantling of cross-arms or M.S. channel or angle sections etc complete all as specified..
Dismantling of GI pipe 80mm/100 dia complete all as specified. .
Dismantaling of existing 4 pole structure complete all as specified..
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testing complete all as specified and directed of following sizes :-
120 Sqmm 3 Core
185 Sqmm 3 Core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm, 3 core.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size 120 Sqmm to 185 Sqmm, 3 core.
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, IS 7098 marked, suitable for LT 1100 Volt system, laid in trenches fixed to pole, including jointing & testing complete all as specified and directed of following sizes:- Note :- Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately under respective items of schedule.
240 Sqmm 3.5 core
185 Sqmm 3.5 core
Note : (i)contractor should provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge.
mayur enterprises
M/s JAIMAA ASSOCIATES
RUHI ASSOCIATES
Vijay Electricals
Buddham Builders
MV Engineers And Contractors
Rajindera Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .