Loading…
Loading…
Tender Value
₹3.3 L
Closing Date
19 Aug 2026, 3:00 pm
Superintending Engineer
Office of Superintending Engineer Construction and Maintenance Unit
Electrical wiring for the connection to the Laboratory tables in the EI lab 304 in the Department of ECE at NIT Warangal
2026_NITW_919751_1
10/NITW/EMPANELED/ELECT/26-27
Limited
Electrical Works
Works
45 days
NIT Warangal
Please refer Tender documents.
1 document required · 1 mandatory
₹0
Exempted
29 Jul 2026
29 Jul 2026
20 Aug 2026
29 Jul 2026
19 Aug 2026
29 Jul 2026
29 Jul 2026 - 12 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying and fixing of 25 mm size of FRLS (ISI) PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. | 100 | Mtrs | 168 | ₹16,800 |
| 2 | Supplying and fixing of 32 mm size of FRLS (ISI) PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. | 50 | Mtrs | 209 | ₹10,450 |
| 3 | Supply and fixing of 32mmX12.5 UPVC Mini Trunking along with External Angle/Flat Angle/Internal Angle/T Joints/End Caps and Fasteners in complete as required including Labour charges etc., | 75 | Mtrs | 252.44 | ₹18,933 |
| 4 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. ( 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire ) | 5 | Each | 1,704 | ₹8,520 |
| 5 | Supplying and drawing 2 X 2.5 sq.mm +1 X 2.5sq.mm sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. | 25 | Mtrs | 148 | ₹3,700 |
| 6 | Supplying and drawing 2 X 4.0 sq.mm + 1 X 4.0 sq.mm sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. | 350 | Mtrs | 222 | ₹77,700 |
| 7 | Wiring for circuit/ submain wiring along with earth wire with the 4 X 6 sq. mm + 2 X 6 sq. mm earth wire sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. | 75 | Mtrs | 813 | ₹60,975 |
| 8 | Supplying, installation, Testing & Commissioning of 36 watt Panel light 2x2 ft., of CRCA Sheet Body (Thickness ≥ 0.50 mm) and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. (System lumen efficacy ≥120 <135 lm/Watt . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted.Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C)-Compatitable for both false ceiling and surface Lighting | 15 | Each | 2,225 | ₹33,375 |
| 9 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required | 55 | Each | 545 | ₹29,975 |
| 10 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. | 75 | Each | 659 | ₹49,425 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.34 MB
Tendernotice_2.pdf
PDF • 0.28 MB
BOQ_966552.xls
BOQ • 0.29 MB
tenderdocument.pdf
Tender Documents • 1.33 MB
niet.pdf
Additional Documents • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].