Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.8 CrAccepted-AOC | ₹30.8 Cr | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹31.8 CrRejected-Finance | ₹31.8 Cr | L2 | Rejected-Finance NOT BEING LOWEST |
| 3 | L3₹32.3 CrRejected-Finance | ₹32.3 Cr | L3 | Rejected-Finance NOT BEING LOWEST |
| 4 | L4₹33.8 CrRejected-Finance 35 B BHERU VILLAS SARDAR CLUB SCHEME AIR FORCE JODHPUR 342 011 RAJASTHAN | JODHPUR | JODHPUR | RAJASTHAN | 342011 | ₹33.8 Cr | L4 | Rejected-Finance NOT BEING LOWEST |
| 5 | L5₹34.6 CrRejected-Finance | ₹34.6 Cr | L5 | Rejected-Finance NOT BEING LOWEST |
Tender Value
₹27.1 Cr
EMD Value
₹15 L
Closing Date
4 Nov 2023, 6:00 pmClosed
Chief Engineer Navy Visakhapatnam
Chief Engineer Navy Visakhapatnam Station Road Visakhapatnam-500 004
PROVISION OF DEFICIENT MARRIED ACCOMMODATION FOR SAILORS PO and BELOW AT NAVY NAGAR CHENNAI
2023_MES_619933_1
88743
Open Tender
Civil Works
1200 days
Chennai
As per Tender
13 documents required · 13 mandatory
₹3,000
AGE I Navy Chennai
₹15 L
Chief Engineer Navy Visakhapatnam
23 Jan 2024
21 Sept 2023
6 Nov 2023
21 Sept 2023
4 Nov 2023
26 Oct 2023
7 Oct 2023
Amount
SCHEDULE 'A' PART-I (BUILDINGS & STRUCTURES):
Construction of Married Accommodation for POs and Below (S+11) including Stilt Parking in RCC framed structure complete all as specified and shown on drawings and as directed by the Engineer-in-Charge.
Construction of Substation Building (Single Storey) in RCC framed structure complete all as specified and shown on drawings and as directed by the Engineer-in-Charge.
Construction of Fire Fighting Pump House (Single Storey) in RCC framed structure complete all as specified and shown on drawings and as directed by the Engineer-in-Charge.
Construction of Fresh Water Pump House (Single Storey) in RCC framed structure complete all as specified and shown on drawings and as directed by the Engineer-in-Charge.
Construction of RCC Under Ground Sump of 1,50,000 Litres Capacity complete all as specified and shown on drawings and as directed by the Engineer-in-Charge.
Construction of RCC Under Ground Sump of 50,000 Litres Capacity complete all as specified and shown on drawings and as directed by the Engineer-in-Charge.
Notes for Item Nos.1.01 to 1.06:
(i) Cost of plinth/floor beams, pile caps, with sub base/lean concrete shall be deemed to be included in the Lump sum quoted.
(ii) Piles will be measured and paid separately as per the scope stipulated in relevant Part (s) of Schedule 'A'.
(iii) Earth work, excavation required as shown in drawings for Buildings/Structures covered under this item is deemed to be included in the Lumpsum quoted against this item.
(iv) Surplus soil obtained from excavation shall be removed from site to outside MD land.
(v) Pile main reinforcement shall be taken into pile caps as shown in drawings and the same will be measured and paid under relevant parts of Schedule 'A'.
SCHEDULE 'A' PART-II to SCHEDULE 'A' PART-XV: Note: Schedule 'A' Part-II to Part-XV are prepriced by MES. Bidders shall insert their lump sum amount in green coloured field under Column 6 only.
Lump Sum price worked out by the contractor for 'Site Clearance/Area Development/Earth Work/Excavation', as listed in Schedule 'A' Part-II.
Lump Sum price worked out by the contractor for 'Pile Foundation', as listed in Schedule 'A' Part-III.
Lump Sum price worked out by the contractor for 'Internal Water Supply', as listed in Schedule 'A' Part-IV.
Lump Sum price worked out by the contractor for 'Internal Electrification', as listed in Schedule 'A' Part-V.
Lump Sum price worked out by the contractor for 'External Water Supply', as listed in Schedule 'A' Part-VI.
Lump Sum price worked out by the contractor for 'External Electrification', as listed in Schedule 'A' Part-VII.
Lump Sum price worked out by the contractor for 'Area Drainage', as listed in Schedule 'A' Part-VIII.
Lump Sum price worked out by the contractor for 'Sewage Disposal', as listed in Schedule 'A' Part-IX.
Lump Sum price worked out by the contractor for 'Road/Path/Culvert', as listed in Schedule 'A' Part-X.
Lump Sum price worked out by the contractor for 'Rain Water Harvesting', as listed in Schedule 'A' Part-XI.
Lump Sum price worked out by the contractor for 'Fire Fighting', as listed in Schedule 'A' Part-XII.
Lump Sum price worked out by the contractor for 'Solar Water Heater', as listed in Schedule 'A' Part-XIII.
Lump Sum price worked out by the contractor for 'TV & Telephone', as listed in Schedule 'A' Part-XIV.
Lump Sum price worked out by the contractor for 'Demolition & Dismantling', as listed in Schedule 'A' Part-XV.
SCHEDULE 'A' PART-XVI: (MISCELLANEOUS ITEMS):
PILE FOUNDATION:
Boring for bored cast-in-situ piles 500mm dia. in any type of soil/clay/ soft rock except hard rock/fractured rock using DMC (Direct Mud Circulation) method of boring and getting out and disposal of spoil out side MD land complete all as specified and as shown on drawings and as directed by the Engineer-in-Charge.
Boring for 500mm dia. bored cast in situ piles in hard rock and getting out and disposal of spoil out side MD land using DMC method (Direct Mud Circulation) complete all as specified and shown on drawings and as directed by the Engineer-in-Charge.
Carrying out initial compressive load test on 500mm dia. pile as per IS 2911 Part-IV, complete all as specified and as directed.
Carrying out initial lateral load test on 500mm dia. pile as per IS 2911 Part-IV, complete all as specified and as directed.
Carrying out routine compressive load test on 500mm dia. pile as per IS 2911 Part-IV, complete all as specified and as directed.
Carrying out routine lateral load test on 500mm dia. pile as specified in IS, complete all as specified and as directed.
Carrying out low strain integrity test on cast in situ piles 500mm dia. including analysing the result as per ASTM D 5882 complete all as specified and as directed by the Engineer-in-Charge. Note fot Item Nos.18 to 22: Test results shall be approved by the CWE. The GE shall intimate CWE before commencing the load test and the test shall be carried out in presence of the authorised representative detailed by the CWE.
INTERNAL WATER SUPPLY:
S&F angular cock 15mm dia., fancy type cast copper alloy, with capstan heads, chromium plated, screwed down high pressure pipes complete all as specified and as directed by the Engineer-in-Charge.
S&F wall mounted quarter turn bath mixer 15mm dia., fancy type cast copper alloy, chromium plated, only for overhead showers & hand showers with connecting legs & wall flanges for mixing hot & cold water screwed down for pipe and fixed, of make Jaquar Cat. Part No.FLR-5215N or equilent Kohler/Hind Ware complete all as specified and as directed by the Engineer-in-Charge.
S&F CPVC fitting Female threaded adapter plastic-FAPT 15mm internal dia. complete all as specified and as directed by the Engineer-in-Charge.
S&F CPVC fitting Male threaded adapter plastic-FAPT 15mm internal dia. complete all as specified and as directed by the Engineer-in-Charge.
S&F CPVC ball valve 20mm internal dia. complete all as specified and as directed by the Engineer-in-Charge.
S&F CPVC ball valve 32mm internal dia. complete all as specified and as directed by the Engineer-in-Charge.
S&F CPVC ball valve 50mm internal dia. complete all as specified and as directed by the Engineer-in-Charge.
INTERNAL ELECTRIFICATION:
Point wiring with 1.5 Sq.mm. FRLS PVC insulated unsheathed copper conductor multi stranded 1100 Volts grade, ISI marking drawn through and including non metallic PVC rigid concealed conduit and conduit accessories medium grade, ISI marked, including modular metal flush box with and including modular white cover plate with frame for mounting modular switches/sockets/fan regulators etc. including one run of 1.5 Sq.mm. PVC insulated unsheathed copper cable for earth continuity, connected to earth dolly, for One light/bell point controlled by one no. one way switch or One fan (ceiling fan/exhaust fan/wall mounted) point controlled by one switch or one 3 pin socket outlet 5 Amps on independent board on independent board complete all as specified and as directed by the Engineer-in-Charge.
All as per item No.30 here-in-before but for One light point controlled by two nos. two way switches on independent board.
All as per item No.30 here-in-before but for one 3 pin socket outlet 5 Amps on same board.
All as per item No.30 here-in-before but for one 3 pin socket outlet 15 Amps on independent board with 2.5 Sq.mm. FRLS PVC wire and one run of 2.5 Sq.mm. copper cable for earth continuity.
All as per item No.30 here-in-before but for one 3 pin socket outlet 15 Amps on independent board with 4 Sq.mm. FRLS PVC wire and one run of 4 Sq.mm. copper cable for earth continuity.
M&L sub main wiring concealed type with PVC insulated FRLS copper conductor cable unsheathed for circuit along with earth wire including PVC rigid conduit medium grade 20mm dia. with accessories complete with two runs of 6 Sq.mm. cable and one run of 6 Sq.mm. earth wire complete with colour coding and making good the disturbed area complete all as specified and as directed by the Engineer-in-Charge. Note: Two runs of cable, one run of earth wire and one run of conduit will be measured as one unit.
S&F LED light fitting 1x18 Watt 4 feet long, 220 Volts, AC decorative box type with holders including LED tube light with inbuild driver connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed by the Engineer-in-Charge.
S&F LED light fitting 1x22 Watt 4 feet long, 220 Volts, AC decorative box type with holders including LED tube light with inbuild driver connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed by the Engineer-in-Charge.
S&F energy efficient LED mirror light fitting 2 feet long with luminare minimum 10 Watt ,230 Volts, surface mounted with necessary diffuser complete with mounting bracket etc. including connecting up with twin core twisted flexible copper conductor cable with suitable size from ceiling rose complete all as specified and as directed by the Engineer-in-Charge.
S&F LED security light fitting with tube minimum 30 Watt, new generation energy saving & environmental frindly long life versatile pressure die cast aluminium luminiare with mid power LEDs as source and HF electronic driver pre wired with 1.5 Sq.mm. copper conductor cable up to connector including 2 m long GI tubing medium grade 32mm dia. bend to shape fixing on wall with suitable MS brackets complete all as specified and as directed by the Engineer-in-Charge.
S&F LED bulb 7 Watt complete all as specified and as directed by the Engineer-in-Charge.
S&F ceiling fan complete with blades, down rods, and accessories, 230 Volts, 1200mm sweep, minimum air delivery 210 CFM with service value 6.0 BEE five star rated with brushless direct current motor (BLDC) with and including electronic regulator flexible copper wire 1 Sq.mm. form ceiling rose to connector of ceiling fan complete all as specified and as directed complete all as specified and as directed by the Engineer-in-Charge.
S&F exhaust fan made out of sturdy engineering plastic complete with louvers shutter, 230 Volt, 50 Hz, 1200 RPM copper winding of sweep 250mm, fixed on wall including making opening, fixing and making good the distrubed surfaces etc complete with and inclussive of making necessary electric connection from ceiling rose to fan through 1 Sq.mm. twin core flexible wire complete all as specified and as directed by the Engineer-in-Charge.
S&F exhaust fan AC single phase 230 Volt of size 300mm sweep, steel body with blades, and frame and louvers fixed on wall making opening, fixing and making good the distrubed surfaces etc. complete with and inclussive of making necessary electric connection from ceiling rose to fan through 1 Sq.mm. twin core flexible wire complete all as specified and as directed by the Engineer-in-Charge.
S&F smart meter single phase tro wire energy meter BIS 16444 2015 (Reaffirmed 2020) marked in existing meter board/floor panel having current range 10-60 Amps, 240 Volts, accuracy class 1.0, including suitable transperent enclosure complete all as specified and as directed by the Engineer-in-Charge. Note: The meter should be compatable with the existing software/ system/server.
Supply, install, test and commissioning of bus trunking system, sandwich type, aluminium busway (3L+N+PE), with multi layer polyster filim class-F insulation, 100% N, 50 KA for 1 Sec and 12 KV implus withstang, enclosure as integral eatrh sheet steel enclouser (C-ribbed housing in 1.5mm thick galvanised powder coated painted with RAL 7035 or as per OEM design, minium temp rise 55 degree over ambient of 40 degree rated insulation & operating voltage 1000 Volts of minimumrating 630 Amps with IP 55 protetion complete for raising mains of building having S+11 floors complete all as specified and as directed by the Engineer-in-Charge. Notes: 1. Rate inclusive of all bends, seperators, flexible joints, tap off boxes, end feed units, earthng strip/connection to bus bar, angle iron supports etc. and all other necessary accessories required for installation and commissioning with TPN DB complete. 2. The contractor shall submit drawings/specification for approval of CWE through GE before placement of order. 3. The rate quoted shall be deemed to include (i) Tap off bozes with MCB/MCCB 63 Amps and 16 Sq.mm. size cable for connecting from tap off box to TPN DB at each floor, (ii) End cover at top floor and (iii) Suitable arrangement for connecting the UG cable from panel to bus bar trunking system.
EXTERNAL WATER SUPPLY:
M&L laying of ductile iron pipe 100mm dia. with spigot and socket end centrifugally (spun) cast class K-9 conforming to IS-8329 including provision of specials, such as tees, elbows, bends reducers, taper pieces (measure separately), including testing and commissioning complete all as specified and as directed by the Engineer-in-Charge.
M&L brick masonry valve chamber of size 900x900x900mm comprising of 50mm thick PCC for valve including excavation and earth work in any type of soil and 200mm thick PCC 1:4:8 type D2 foundation, brick work in CM 1:6, plastring internal surface 15mm tick in CM 1:4, PCC 1:3:6 type C1 couping, 50x50x6mm angle iron, 3mm thick MS plate cover complete with locking arrangement painting to steel and iron surface with two coat of synthetic enamel paint over one coat of zinc chrome primer complete all as specified and as directed by the Engineer-in-Charge.
Supply, install, testing and commissioning of pump sets, centrigfugal, electric driven supplied and installed complete minimum 50m head, minimum 950 LPM discharge inclusive of sheet enclosure type starter motor rating AC3 415 Volts, 3 Phase and PCC foundation complete all as specified and as directed by the Engineer-in-Charge.
M&L for cutting existing GI pipe 100mm dia. for alterations or additions necessarily done in position with out taking down complete all as specified and as directed by the Engineer-in-Charge.
EXTERNAL ELECTRIFICATION:
Supply, installation and Testing of 11 KV Compact Sub Station consisting of the following specifications: complete all as specified and as directed by the Engineer-in-Charge. (I) HT Switchgear: (a) 11kV 630Amps 21KA/3 sec. Non-Extensible Ring Main Unit Compact switchgear with Copper bus bar (DV) consisting of One No. Fixed Manual Load Break switch and One No. Fixed Manual Vacuum Circuit Breaker in robotically welded having IP67 in SF6 encapsulated stainless steel enclosure of thickness 2.5mm having IP-67. with series trip, self-powered microprocessor based numerical over current and earth fault relay protection. (b) Relay shall be ( 50,50N,51,51N)-1NO (c) Protection CT shall be 40/1A 2.5VA 5P10.-3Nos (d) Manometer-1No (e) Voltage Presence Indicator (L1, L2, L3) for each Module-2Nos (f) Mechanical indications for breaker ON / OFF / TRIP -1 set (g) Operating Handle-1No (II) Transformer: 200 KVA 11KV/433V DYn11 Copper Wounded Cast Resin Dry Type Transformer with off load tap links of +5% to -5% @2.5% with WTI scanner. Class of Insulation: F, Temperature rise 90 degree C. Losses (Subject to IS 2026 Toll)-NLL-1200W and FLL-4200W and Impedance of 4.5% (Subject to IS Tol) with Surge Arrester & WTI scanner-1No (III) LVS PANEL: (a) 500AMPS ALUMINUM BUSBAR (100% FOR PHASE & 50% FOR NEUTRAL, CURRENT DENSITY- 1 AMP/SQMM including insulation with heat sleeve with colour code RYB)
(b) INCOMER FROM TRANSFORMER: (i) 400 Amps 433V 50KA 4P Fixed Manual Moulded Case Circuit breaker (MCCB) with microprocessor based release for over current, short circuit and earth fault protection-1No. (ii) RYB Indications-1set (iii) Digital Multifunction meter of Class 1.0 Accuracy with RS485 port-1No. (c) OUTGOING: (i) 400 Amps 433 Volts 50 KA 4P Fixed Manual Moulded Case Circuit breaker (MCCB) with microprocessor based release for over current, short circuit fault protection-1No. (ii) 250 Amps 433 Volts 25 KA 4P Fixed Manual Moulded Case Circuit breaker (MCCB) with microprocessor based release for over current, short circuit fault protection-3Nos. (d) Outdoor Enclosure: Outdoor type enclosure having construction of galvanised sheet steel with combination of 3.15mm thickness for load bearing member and 1.5mm with non load bearing member with 4mm HRCA base frame. The enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP23 degree of protection for transformer compartment. The enclosure shall be powder coated (Colour light gray & dark gray). Each compartment will be provided with the door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided for MV & LV compartment. Separate switch operated bulket lap + hooter in transformer compartment.-1 set door interlock to trip HT breaker on opening of transformer compartment door
(e) Interconnection and earthing interconnection between HT switchgear & transformer using 1Cx3x95 Sq.mm. XLPE single core aluminium cable & interconnection between transformer & LT switchgear using aluminum bus bars. Internal earthing connections by using 50x6mm GI strips including transformer neutral-1set
(g) Bus bar connection switch 630 a copper bus bar, Earth connections- type tested for 21 KA STC (h) Enclosure CRCA suitable for outdoor (IP54) installation with the provision for receiving I/C, O/G cables through front and bottom entry, excluding termination kits and glands. 2mm CRCA sheet for inside sheets and covers, 3mm thick CRCA sheet for outer load encl. (j) Load break switch: 11 KV, 630A, 21 KA/ 3 SEC ,Horizontal type draw-out with measuring CT and HT protetion fuse including indication lamps RYB, ammeter, voltmeter with Mechanical interlock all as specified and directed.
S&F LED street light fitting 60 Watt, 230 Volts, AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete all as specified and as directed by the Engineer-in-Charge.
S&F LT panel out door type for street light comprising of astronomical time switches 230 Volt Single Phase 20 Amps MCBs, 20 Amps contactor complete all as specified and as directed by the Engineer-in-Charge.
Supply, install, testing & commissioning of Automatic Power Factor Correction (APFC) Panel for 3 Phase, 415 Volts, 50 Hz system of capacity 100 KVAR complete all as specified and as directed by the Engineer-in-Charge.
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes complete all as specified and as directed by the Engineer-in-Charge;
3½ core 400 Sq.mm.
3½ core 95 Sq.mm.
3½ core 50 Sq.mm.
2 core 10 Sq.mm.
Supply laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 Volts grade, of sixe 3 core 95 Sq.mm. complete all as specified and as directedby the Engineer-in-Charge.
S&F for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sq.mm. complete all as specified and as directed by the Engineer-in-Charge.
S&F for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sq.mm. complete all as specified and as directed by the Engineer-in-Charge.
M&L earth continuity conductor or main earthing lead made of galvanised iron strip 25x4mm size, fixed to wall on batten or recess or chases or burried in ground or fixed to poles or any other indicated situation including drawing through GI pipe for earthing etc. complete all as specified and as directed by the Engineer-in-Charge.
M&L underground drainage double wall corrugated (DWC) HDPE pipe 50mm dia. SN4 confirming to IS-16098 (Part-II) single socketed in any length laid in trenches or floors etc. complete all as specified and as directed by the Engineer-in-Charge.
M&L underground drainage double wall corrugated (DWC) HDPE pipe 100mm dia. SN4 confirming to IS-16098 (Part-II) single socketed in any length laid in trenches or floors etc. complete all as specified and as directed by the Engineer-in-Charge.
AREA DRAINAGE:
M&L pre-cast cement concrete block masonry with solid PCC blocks of grade C5 conforming to IS-2185 Part-I, in CM 1:6, exc. 10cm in width and setting in mortar complete all as specified and as directed by the Engineer-in-Charge.
M&L pre-cast RCC M-30 as in factory made cover slabs, set in cement mortar (1:4) including use and waste of form work complete all as specified and as directed by the Engineer-in-Charge.
SEWAGE DISPOSAL:
M&L pre-cast cement concrete block masonry with solid PCC blocks of grade C5 conforming to IS-2185 Part-I, in CM 1:6, exc. 10cm in width and setting in mortar complete all as specified and as directed by the Engineer-in-Charge.
M&L pre-cast factory made SFRC manhole cover slabs of size 900mmx 450mmx75mm including reinforcemnt, conforming to IS 12592-2002, set in cement mortar (1:4) including use and waste of form work complete all as specified and as directed by the Engineer-in-Charge.
M&L M&L for 300 user of RCC septic tank of conventional designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-30 Design Mix in walls, base slab, baffle walls and roof slab including beams etc. with vent shaft, manhole openings with cover connection etc. complete with effective depth of 1.5 meter and overall depth of 3 meter complete all as specified and as directed by the Engineer-in-Charge.
M&L M&L for soakage wells excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M-25 concrete including intercepting chamber and screen chamber made of brick masonry in CM 1:4, RCC cover slab in M-25/SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats, of size 3.6m dia.x3.0m effective depth complete all as specified and as directed by the Engineer-in-Charge.
ROAD/PATH/CULVERT:
M&L pre-cast cement concrete block masonry with solid PCC blocks of grade C5 conforming to IS-2185 Part-I, in CM 1:6, exc. 10cm in width and setting in mortar complete all as specified and as directed by the Engineer-in-Charge.
M&L granular sub base (GSB) with grading V of 200mm thick compacted thickness (Laid in two layers of 75mm each, compacted seperately) confirming to grading as specified, spread, rolled & consolidated to required gradient and camber complete using necessary mechanical paver/grader & vibratory soil compacter of capacity 8-10 Ton complete all as specified and as directed by the Engineer-in-Charge. Notes: 1. Pavement shall be made for solid quantity arrived after consolidation. 2. Compaction of granular sub base filling shall be carried out under optimum moisture condition to achieve 98.50% modified density. 3. Curing shall be carried out as per IRC recommendations. 4. Before execution of this item the approved material obtained from outside MD land shall be tested/Checked for suitability to use. 5. Contractor shall use vibratory earth compactor in lieu of power roller to achieve 98.50% MDD at OMC without any extra cost and the method of compaction to be adopted as per recommendation of agency reporting MDD at OMC. 6. GSB shall be as per MORTH specification as detailed in particular specification.
RAIN WATER HARVESTING:
M&L pre-cast cement concrete block masonry with solid PCC blocks of grade C5 conforming to IS-2185 Part-I, in CM 1:6, exc. 10cm in width and setting in mortar complete all as specified and as directed by the Engineer-in-Charge.
M&L pre-cast RCC M-30 as in factory made cover slabs, set in cement mortar (1:4) including use and waste of form work complete all as specified and as directed by the Engineer-in-Charge.
FIRE FIGHTING SYSTEM:
M&L laying of ductile iron pipe 150mm dia. with spigot and socket end centrifugally (spun) cast class K-9 conforming to IS-8329 including provision of specials, such as tees, elbows, bends reducers, taper pieces (measure separately), including testing and commissioning complete all as specified and as directed by the Engineer-in-Charge.
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 4 core 10 Sq.mm. complete all as specified and as directed by the Engineer-in-Charge;
S&F perforated GI cable tray of size 100x50x1.6mm thickness including mounting accessories and paint two coat of primer over one coat of red oxide as required at site complete all as specified and as directed by the Engineer-in-Charge.
S&F air release valve 25mm dia. bore, single air outlets conforming to IS-14845 fixed on the top of wet riser complete all as specified and as directed by the Engineer-in-Charge.
S&F star delta fully automatic starter up to 25 HP pumps complete all as specified and as directed by the Engineer-in-Charge.
S&F star delta fully automatic starter up to 12.5 HP pumps complete all as specified and as directed by the Engineer-in-Charge.
M&L for 2 runs of 1.5 Sq.mm. unarmoured FRLS cable through steel conduit heavy duty including mounting with all accessories complete all as specified and as directed by the Engineer-in-Charge.
M&L earth continuity conductor or main earthing lead made of galvanised iron strip 25x4mm size, fixed to wall on batten or recess or chases or burried in ground or fixed to poles or any other indicated situation including drawing through GI pipe for earthing etc. complete all as specified and as directed by the Engineer-in-Charge.
M&L for cutting existing GI/DI/MS pipe 150mm dia. for alterations or additions necessarily done in position with out taking down complete all as specified and as directed by the Engineer-in-Charge.
S&F 6 Kg fire extinguisher dry chemical powder ABC type complete all as specified and as directed by the Engineer-in-Charge.
S&F 4.5 Kg fire extinguisher Co2 type complete all as specified and as directed by the Engineer-in-Charge.
S&F 9 Kg/litre fire extinguisher water stored pressure type complete all as specified and as directed by the Engineer-in-Charge.
S&F fire bucket stands complete all as specified and as directed by the Engineer-in-Charge.
S&F mechanical foam fire extinguisher 9 litre capacity complete all as specified and as directed by the Engineer-in-Charge.
LIGHTNING PROTECTION:
S&F single pointed air terminal aluminium rod 12mm dia. 300mm long with aluminium box plate of size of 125x125x10mm fixed over porcelain insulator and fixed on roof top complete including 40mm dia. medium grade MS pipe 300mm long and including necessary fasteners fixed for lighting protection with necessary connections to earthing etc. complete all as specified and as directed by the Engineer-in-Charge.
S&F horizontal roof conductor and down conductor of size 25x3.15mm aluminium strip fixed to walls/columns/projections/roof including porcelain blocks/DMC insulator spaced at 1m interval complete all as specified and as directed by the Engineer-in-Charge.
S&F test point terminal block made out of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia. 25mm long hexagonal head screws etc. complete all as specified and as directed by the Engineer-in-Charge.
S&F galvanised iron strip of 25x4mm size with saddles and fixing screws etc. for wall conductors connected with equipment and above ground (Proper insulation should be provided between the strip and walls) complete all as specified and as directed by the Engineer-in-Charge.
M&L underground drainage double wall corrugated (DWC) HDPE pipe 50mm dia. SN4 confirming to IS-16098 (Part-II) single socketed in any length laid in trenches or floors etc. complete all as specified and as directed by the Engineer-in-Charge.
AVIATION LIGHT:
M&L for LED aviation obstruction lights not less than 30 Watt including fixing accessories such as clamp, lock nuts, saddles etc. complete all as specified and as directed by the Engineer-in-Charge.
S&F LT panel out door type for street light comprising of astronomical time switches, 230 Volts, Single Phase, 20 Amps MCBs, 20 Amps contactor etc. complete all as specified and as directed by the Engineer-in-Charge.
M&L for cable with copper conductor PVC round sheathed (flexible) industrial cable 4 Sq.mm. with rigid non-metallic PVC conduit 20mm dia. exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. complete all as specified and as directed by the Engineer-in-Charge.
HOT WATER SUPPLY:
S&F electric water heater, storage type, steel body with copper inner tank and heating element upto 2 KW capacity 25 Litres, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece branded with ISI mark etc. complete all as specified and as directed by the Engineer-in-Charge.
TV & TELEPHONE:
S&F TV socket type RJ 11 including GI box, inner and modular cover plates complete all as specified and as directed by the Engineer-in-Charge.
S&F telephone socket including GI box, inner and modular cover plates complete all as specified and as directed by the Engineer-in-Charge.
DG SET:
Supply, installation, testing and commissioning of silent Diesel Engine driven generating set 100 KVA, 415 Volts, 3 Phase, 4 wire with multifunctional panel having overload/short circuit/low oil/engine over speed/water/oil temperature indicator and alarm system and AMF panel with on load auto changeover of load, engine and alternator as per IS complete with relay panel and switch gears for automatic starting on main failure, control panel having meter and sound proof canopy as per CPCB norms, including retrofitted emission control devices and foundation as specified by OEM and comprising of the following components complete all as specified and as directed by the Engineer-in-Charge. (a) 12 Volts battery along with copper connecting lead. (b) Fuel storage tank with fuel pipe (c) Multi-functional panel having the following safety features from over load/short circuit over/ under voltage, low lube oil/engine over speed/water and oil temperature with indication & alarm system: (i) Digital Volt Meter (0 to 500 Volts), (ii) Ammeter (0 to 400 Amps), (iii) Frequency Meter, (iv) RPM Indicator, (v) KWH Meter & (vi) Hour Meter (d) Factory made acoustic canopy as per ISI as the enclosure of DG set. Notes: (i) The rate includes the cost of foundation and all necessary civil works as per manufacturer’s drawing. (ii) The rate includes the cost for 12 hours load all test as specified including provision of diesel and load for testing. (iii) The contractor shall hand over the user manual, tools kit, test certificate of the manufacturer.
LIFTS:
Design, supply, install, testing and commissioning of passenger lift, with capacity of 8 Nos. passengers, speed 1.5 metre/sec, lift with single speed motor 415 Volts, 3 Phase, AC 50 Hz supply conforming to IS-14665, suitable to serve G+11 floors with AC variable voltage and variable frequency drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (Electric motor driven mechanism), sliding stainless steel doors, Automatic Rescue Device (ARD) system with+/-5mm with suitable dry maintenance free battery, automatic power operated centre opening & sliding stainless door of 16 gauge with 3D infrared sensor in full height of door and built-in announcing system without hand set (03 Nos., one each in car, machine room and near ground floor landing door) complete all as specified including necessary joists for mounting machine in machine room and all civil works required with erection of lift including auto fan, LED lights, emergency lights etc. along with the following components complete all as specified and as directed by the Engineer-in-Charge: (a) Alarm speaker for alarm system to be fixed), stop button in car with rechargeable arrangement for battery (b) Four sleek circular LED lights fitting in false ceiling (c) Overload warning indicator both audio and visual type with tripping system having relay etc. (d) Set of three Nos. limit switches at the bottom and top most position of lift. (e) Display indicating panel, power control cables (f) Mirror of 6mm thickness of suitable size on one wall inside the car
Design, supply, install, testing and commissioning of passenger lift, with capacity of 13 Nos. passengers, speed 1.5 metre/sec, lift with single speed motor 415 Volts, 3 Phase, AC 50 Hz supply conforming to IS-14665, suitable to serve G+11 floors with AC variable voltage and variable frequency drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (Electric motor driven mechanism), sliding stainless steel doors, Automatic Rescue Device (ARD) system with+/-5mm with suitable dry maintenance free battery, automatic power operated centre opening & sliding stainless door of 16 gauge with 3D infrared sensor in full height of door and built-in announcing system without hand set (03 Nos., one each in car, machine room and near ground floor landing door) complete all as specified including necessary joists for mounting machine in machine room and all civil works required with erection of lift including auto fan, LED lights, emergency lights etc. along with the following components complete all as specified and as directed by the Engineer-in-Charge: (a) Alarm speaker for alarm system to be fixed), stop button in car with rechargeable arrangement for battery (b) Four sleek circular LED lights fitting in false ceiling (c) Overload warning indicator both audio and visual type with tripping system having relay etc. (d) Set of three Nos. limit switches at the bottom and top most position of lift. (e) Display indicating panel, power control cables (f) Mirror of 6mm thickness of suitable size on one wall inside the car
Supply, installation, testing and commissioning of indoor panel CPRI approved , IP 42, made out of CRCA sheet 2mm thick vermin proof factory made with 40x40x6mm MS angle/channel duly painted with two coats of synthetic enamel powder coated paint over a coat of metal primer with bus bar chamber comprising of high conductivity copper bus bar of capacity 200 Amps three phase and half the capacity for neutral including internal wiring with 6 Sq.mm. copper conductor (FRLS) including PCC foundation suitable to accommodate the following complete all as specified and as directed by the Engineer-in-Charge: INCOMING: (a) MCCB 415 Volts, 100 Amps, 4 Pole with electronic release electronic earth leakage module with over load, short circuit and earth fault protection with earth module breaking capacity 16 KA-01 No. (b) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp complete and all as per standard practice -1 No. OUTGOING: (a) MCCB 40 Amps, 415 Volts, 4 Pole with electronic earth leakage module, over load short circuit protection, breaking capacity 16 KA electronic release-02 Nos. (b) MCB 32 Amps, 415 Volts, 4 Pole with electronic earth leakage module, over load short circuit protection, breaking capacity 16 KA electronic release-03 Nos.
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes complete all as specified and as directed by the Engineer-in-Charge;
3½ core 70 Sq.mm.
4 core 25 Sq.mm.
S&F 40mm bore light grade GI tubes with all fitting, laid in trenches for protection of GI strip complete all as specified and as directed by the Engineer-in-Charge.
M&L earth continuity conductor or main earthing lead made of galvanised iron strip 25x4mm size, fixed to wall on batten or recess or chases or burried in ground or fixed to poles or any other indicated situation including drawing through GI pipe for earthing etc. complete all as specified and as directed by the Engineer-in-Charge.
Supply, install, test and commissioning of solar panel powered inverter (Single wave) with battery backup of capacity 14 KW (Single phase, 230 Volts, 50 Hz, AC supply) using tubular battery of 12 V, 150 AH of sufficient quality complete, off grid type, with and inclusive of aal the electrical and mechanical accessories like manual changeover switch 20 Amps single phase 240 Volts, DB SPN 2 way with 20 Amps with MCB SPN 20 Amps, copper wires etc. including stand for the inverter & batteries complete all as specified and as directed by the Engineer-in-Charge. Notes: 1. Solar panel of specification 320 WP (Minimum) polycrytaline type to be provided. 2. The contractor shall submit the wiring diagram to the Engineer-in-Charge before commencement of the work for approval.
SCHEDULE 'A' PART-XVII: Outsourcing Services for Operation of Lifts for the First Year of the two year Defect Liability Period:
Outsourcing of services for operaion of passenger lifts (2 Nos. i.e. 8 passengers & 13 passengers 01 each) any type and make to serve S+11 floors, during First Year of the two year Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts).
SCHEDULE 'A' PART-XVIII: Outsourcing Services for Operation of Lifts for the Second Year of the two year Defect Liability Period:
Outsourcing of services for operaion of passenger lifts (2 Nos. i.e. 8 passengers & 13 passengers 01 each) any type and make to serve S+11 floors, during Second Year of the two year Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts).
SCHEDULE 'A' PART-XIX: Outsourcing Services for Operation of Lifts and Comprehensive maintenance of Lifts for the First Year after Defect Liability Period:
Outsourcing of services for operaion of passenger lifts (2 Nos. i.e. 8 passengers & 13 passengers 01 each) any type and make to serve S+11 floors, during First Year after expiry of Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts).
Comprehensive mainenance of passenger lift, with capacity of 8 Nos. passengers to serve S+11 floors complete including ARD and all connected components of lift during First Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
Comprehensive mainenance of passenger lift, with capacity of 13 Nos. passengers to serve S+11 floors complete including ARD and all connected components of lift during First Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
SCHEDULE 'A' PART-XX: Outsourcing Services for Operation of Lifts and Comprehensive maintenance of Lifts for the Second Year after Defect Liability Period:
Outsourcing of services for operaion of passenger lifts (2 Nos. i.e. 8 passengers & 13 passengers 01 each) any type and make to serve S+11 floors, during Second Year after expiry of Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts).
Comprehensive mainenance of passenger lift, with capacity of 8 Nos. passengers to serve S+11 floors complete including ARD and all connected components of lift during Second Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
Comprehensive mainenance of passenger lift, with capacity of 13 Nos. passengers to serve S+11 floors complete including ARD and all connected components of lift during Second Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
SCHEDULE 'A' PART-XXI: Outsourcing Services for Operation of Lifts and Comprehensive maintenance of Lifts for the Third Year after Defect Liability Period:
Outsourcing of services for operaion of passenger lifts (2 Nos. i.e. 8 passengers & 13 passengers 01 each) any type and make to serve S+11 floors, during Third Year after expiry of Defect Liability Period by providing services of One Lift Operator (Semi Skilled) in 02 shifts on all the days including sunday & holidays including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfication of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-charge (Shift Details: 365 Days x 1 Building x 2 Shifts=730 Shifts).
Comprehensive mainenance of passenger lift, with capacity of 8 Nos. passengers to serve S+11 floors complete including ARD and all connected components of lift during Third Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
Comprehensive mainenance of passenger lift, with capacity of 13 Nos. passengers to serve S+11 floors complete including ARD and all connected components of lift during Third Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
Notes for Outsourcing Services Items: (i) The lift shall be operated daily in two shifts as directed by the Engineer-in-Charge. (ii) The timings for two shifts of 8 hours each daily i.e. First shift shall be from 0630 hours to 1430 Hours and Second Shift shall be from 1430 Hours to 2230 Hours. (iii) In case of non-function of passenger lift, the Goods Lift installed in the same building shall be operated as directed. (iv) The work shall be supervised by adequately qualified supervisor with relevant experience of minimum 5 years items under BoQ shall be deemed to be including the same. (v) The unit rate is deemed to include for maintaining log books, record of repair/replacement of perished/unserviceable, minor adjustments, minor repairs of all accessories, cleaning/up keeping of lift and surrounding area as directed by the Engineer-in-Charge. (vi) One emergency light and necessary tools shall be available in a tool box with the operator in the shift for smooth functioning of lifts. (vii) Conveyance and communication system like mobile phone etc. shall be provided by the Bidders/Service providers to all Lift Attendants/Supervisors. (viii) The Bidders shall ensure house keeping, environmental cleanliness of area all round the lift and the area shall be kept absolutely neat and clean. The lift attendant shall clean the Lift car cabin, all landing floors and tiles all round lift doors with necessary cleaning material such as cotton cloth and cleaning solution etc.
(ix) The Bidders shall abide by the latest Labour rules and minimum wages Act. Wages paid by the bidders to the persons employed shall not be less than the minimum wages fixed by the state/central government from time to time whichever is higher. The Bidders shall also insure the workmen employed on the job. (x) The Bidders is responsible for insurance, EPF, ESI, Bonus, Labour welfare cess et., as applicable and shall be paid to the workmen as per existing Labour rules/ Acts/ regulations and rate quoted shall be deemed to be included for the same. (xi) Dress Code: The bidders shall provide the workmen with Dark Blue Colour uniform {formal pant & T-shirt} with labels showing/ printed i.e. “Name of the firm and designation” on front and on the back of the T-shirt along with protective clothing/gear. The bidders shall also provide shoes to the workers and the persons shall not be allowed to enter the work site without wearing shoes. (xii) INSURANCE: The Bidders shall be responsible for all Accidents/Injuries happening to the workmen. Any accident causing minor/fatal injury, partial disability due to any untoward incident or non-adherence to safety and IE regulations or fault in maintaining of internal electric supply system or on account of any mishandling/ wrong operation/ lack of knowledge of safety precautions or on account of any circumstances beyond his/ their control, the bidders shall be solely responsible for settling all claims of compensation to the deceased, falling which department will have a right to recover any sum indicated/ claimed by Labour commissioner/court authorities. No claim whatsoever will be entertained in this regard. No compensation is payable by the department on this account. Bidders shall provide first aid boxes to meet any emergency situations.
(xiii) The rate quoted by the bidders shall be deemed to be including Basic rate (Minimum Wages as notified by Government of India/State Government/Local body, whichever is higher), employers contribution towards Employees Provident Fund (EPF) liability, contribution towards Employees State Insurance Corporation (ESIC), contribution towards Bonus. Overhead and profit and labour welfare cess (LWC) as applicable depending upon the manpower requirement. This will create onus on the Bidders to applicable depending upon the man power requirement. This will create onus on the bidders to ascertain the relevant rates and quote accordingly. The rates quoted shall be inclusive of all taxes, cess, levies are applicable including GST. Note: The Manpower deployed shall be changed for every 11 months period. The rate quoted deemed to be inclusive for the same.
(viii) The tenderer shall submit MoU from the original manufacturer of the lift for comprehensive maintenance to undertake comprehensive maintenance during and after Defects Liability Period directly or through their nearest authorized/accredited agencies service personnel. The MoU shall be submitted at least 06 months prior to issue of completion certificate of main contract as per Work Order No I.
G R M CONSTRUCTIONS
LUMOS INFRA PVT LTD
RAGHUSONS INFRA ENGINEERING PVT. LTD
DES RAJ AND SONS BUILDERS PVT LTD
SHRI GURMUKHDAS CONTRACTORS PVT. LTD.
S.S.NATARAJAN AND CO
DHARIWAL TRADERS PRIVATE LIMITED
Bidder Name
LUMOS INFRA PVT LTD
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid