| 1 | L1₹56.7 LAccepted-Finance 1 128 A SECOND FLOOR MOHAMMADPUR NEAR BHIKAJCAMA PLACE NEW DELHI 110066 | NEW DELHI | NEW DELHI | DELHI | 110066 | ₹56.7 L | L1 | Accepted-Finance 1st Lowest |
| 2 | L2₹57 L+₹34,585 (0.61%)Rejected-Finance V P O SAROTARI TEHSIL BAROH DISTRICT KANGRA PIN 176037 HP | KANGRA | HIMACHAL PRADESH | 176037 | ₹57 L+₹34,585 (0.61%) | L2 | Rejected-Finance 2nd Lowest |
| 3 | L3₹57.1 L+₹39,635 (0.70%)Rejected-Finance | ₹57.1 L+₹39,635 (0.70%) | L3 | Rejected-Finance 3rd Lowest |
| 4 | L4₹62.8 L+₹6.1 L (10.8%)Rejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | ₹62.8 L+₹6.1 L (10.8%) | L4 | Rejected-Finance 4th Lowest |
| Sl No | Description | Qty | Unit | Electromech Engineers L2 | Auto Traders L3 | Vijaypower Generators Limited L4 | M/s Dhapola Elevator and Engineering L1 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation , commissioning and testing of diesel engine driven Gen with sound proof acousri cenclosure(canopy CRCA sheet of 2mm thickness and noise level below 75 decible/M) and provision of exhaust fan insise the canopy to control the noise level as per limit of central pollution control board (CPCB IV+) 500 KVA 3 phase 415 volt 1500 RPM, 4 wire 50 cycle and power factor 0.8 complete all as specified including complete with foundation (using 100 mm thick PCC 1:4:8 type D-2 as in lean concrete, flyash brick masonry in CM 1:6, the top of the plinth shall consist of 100 mm thick PCC 1:2:4 type B-1 over 75 mm thick PCC 1:4:8 type D-2 over compacted moorum filling, 10 mm thick rendering in CM 1:4 on brick surface) and comprising of the following with set of tools and two years maintaince spares as recommended by the manufacturer complete all as specified and directed :- (Make :Greaves power,Kirlosker Cummins India Ltd) | 1 | Each Job | 53,20,000 ₹53,20,000 | 54,49,760 ₹54,49,760 | 58,32,000 ₹58,32,000 | 49,50,000 ₹49,50,000 Lowest |
| 1.01(a) Prime mover :- Suitable for driving 500 KVA alternator, water cooled, battery start diesel engine of adequate BHP conforming to BSS frame pedestal support with anti vibration pad rated for continuous running capable of taking 10 % over load for one hour in any 12 hrs operation with the following standard activities:- (i) Fly wheel to match with the flexible coupling (ii) Flexible coupling with guard (iii) Air cleaner oil bath type / dry type (iv) Lubricating oil filter paper element type (v) Fuel pump (vi) Blower type fan and radiator (vii) Governor for class 'A' governing as per IS -1601 of ELEC/G3 (viii) Starter , motor for electric start complete with dynamic alternate , lead acid batterie of 02 nos heavy duty of capacity 12 V 180 AH each or adeqaute size and length of cable not less than 2m long including battery box all as directed. (ix) Hour meter and RPM indicator (x) Exhaust pipe brought outside the bud and lagging of entire exhaust pipe with 12 mm dia arrestor rope (xi) Instrument panel duly wired compromising of the followiing:- (a) Lub oil temp gauge (b) Lube oil pressure gauge (c) High/ Low temp gauge (d) Starting switch with key (e) Fuel tank | |||||||
| 1.02(b) ALTERNATOR :- 500 KVA at 0.8 PF brush less self excited, self regulated 3 phaser , 50 HZ 415 V 1500 RPM 4 wire screen protected drip proof enclosure free from stimulation problem continuous rating conforming to BS 2613 IS 4722 complete with automatic voltage regulator between +5% of set voltage from no load to full load. (c) Automatic Main Failure Panel :- Supply, installation , commissioning and testing of AMF panel for 500 KVA DG Set fabricated out of MS sheet (factory made) suitable for floor mounted higned from panel for easy accessibility with suitable rated bus bar internal wiring and with provision for connecting incoming/ out going leads with the following accessories as per the manufacturing DG Set :- (i) MCCBs of suitable rating (For DG Set & main incoming) (ii) Auxiliary contactor with timer (on delay) (iii) Current transformer (iv) Voltmeter digital type with selector switch (v) Ammeter digital type with selector switch (vi) Frequency meter digital type (vii) Power factor digital type (viii) KWH meter electronic type (ix) One set of indicator lamps (Red, Yelllow, Blue) (x) Push button start and stop (xi) One set of lamps for indicating " load on set" "load on mains" "set fails to start" "low oil pressure " "high cylinder temperature" " Battery low" | |||||||
| 1.03(xii) Battery charger connected to main supply side to charge batteries compromising of the following :- (xiii) Transformer of adequate capacity with quto cut facilities. (xiv) Recitifier (xv) DC ammeter and DC Voltmeter (xvi) Indicator lamp for battery (xvii) Charge rate selection for tickle or high charge. (xviii) Set of easily to accessible control fuses (xi) Set of relays auto start the DG Set on main failure and low voltage (xx) Over/under voltage relay (xxi) Change over switch open execution type of suitable capacity with HRC fuse (xxii) Reverse power relay (xxiii) Emergency stop (A) Genset specification ↓ 1. Genset rating - Prime 2. Genset output (kVA/kWe) - 500 / 400 3. Genset model - GPWII-PIV-500M 4. Gross engine Power (kWm) - 444 5. Gross engine Power (HP) - 604.1 6. Engine model - 12V14TAG31 7. Aspiration / Cooling - TCAC 8. No. of Cylinders / Arrangement - 12 / V-Type 9. Displacement (L) - 16.8 10. Bore x Stroke (mm) - 115 X 135 11. Compression ratio - 16.8 12. Rated RPM - 1500 13. Overspeed trip (RPM) - 1650 14. Governor type / DG Perfomance Class - Elec / G3 15. Frequency Regulation - Isochronous 16. Air cleaner type / Qty - Dry / 02 | |||||||
| 1.04(B) Exhaust system:- 1. Max allowable backpressure (kPa) - 15 2. Exhaust temperature ( Deg C) - 550 3. Silencer type - NA 4. Aftertreatment System - DOC+SCR+ASC (C) Engine electrical system:- 1. Charging alternator VDC / Amps - 24 V / 44 A 2. Starter motor rated voltage (DC) - 24 3. Battery voltage (DC) / Capacity (AH) - 12V / 180 AH X 2 (D) Fuel System:- 1. Recommended fuel - IS 1460, HSD 2. Fuel tank capacity (L) - 740 (E) Fuel Consumption @ % load (LPH)(Including radiator fan + other accessories):- 1. LPH @ 100% - 105.00 2. LPH @ 75% - 79.00 (F) Lubricating Oil System:- 1. Lube oil sump capacity (L) - 50 2. Lube oil change period (Hrs) - 500 3. Lube oil consumption (% of SFC) - ≤0.06% 4. Lube oil filter type / Qty - Spin on / 02 5. Recommended lube oil grade - 15W40, API CI4+ 6. Recommended lube oil - Greaves Maxtherm | |||||||
| 1.05(G) Alternator Specification:- 1. Alternator Make - LS 2. Voltage (3P) - 415 3. Frequency (Hz) - 50 4. Current (3P) (Amps) - 695.6 5. Type - 4P, rotating field 6. Voltage regulator - Automatic 7. Voltage regulation -% - ±1% 8. Insulation class - H 9. Temperature rise (Deg C) - 125 10. Bearing (Qty / type) - 1, sealed 11. Coupling - Flex disc 12. Unbalanced load capability - 25% of rated amps (H) Cooling System:- 1. Max ambient capability (Deg C) - 50 2. Coolant capacity (Eng + Rad) (L) - 120 (I) Controller:- 1. Controller Model - DSE 6120 MKIII (J) DEF System:- 1. Recommended fuel - ISO 22241, DIN-70070 2 DEF Tank Capacity (L) - 60 (K) DEF Consumption:- 1. LPH @ 100% - 5.3 2. LPH @ 75% - 4.0 (L) Genset Outer Dimensions:- 1. Length(L) X Width(W) X Height(H) (mm) - 5615 X 2000 X 2965 2. Dry Weight (Approx.) (kg) - 5650 | |||||||
| 1.06Disclaimer:- 1. Ref.: ⁽1⁾Fuel consumptioin @ 0.85 Specific Gravity with 5% Tolerance, DEF consumption : 5% of FC 2. PRIME POWER RATING as per ISO 8528 3. Conformance standards: Engine - BS 5514, ISO 3046, Alternator - IS 13364 (Part - II), Genset - SO 8528 and Tolerances as applicable. Note :- (i) Any fitting /fixture are deemed to be included above which are required for its proper functioning (ii) Necessary foundation for installaiton of DG Set shall be provided as per manufacturer recommendatios and cpost deemed inclusive of the rates quoted above. (iii) DG Set should automatically start when AC main fails and load should also transfer on DG set automatically and also switch off while main AC ON. (iv) The contractor shall provide Engine operation/ maintenance and spare parts alternator warranty certificate and Engine test certificate. | |||||||
| 2.00 | S & F in replacement XLPE insulated and PVC armoured heavy duty electric cables with aluminum conductor, 1100 volt grade of size 400 sqmm, 4.0 core, in trenches/through pipes/ducts or on poles/walls jointing to O/H conductor, LT panels, main switch with suitable size aluminum lugs and testing complete all as specified & directed for the following sizes:-
Note : (a) Excavation shall be measured and paid seperately under respective items of Sch 'A' .
(b) All required lugs of suitable sizes according to laying of cable & Connection deemed to be including in quoted rate. | 98 | RM | 3,160 ₹3,09,680 | 2,150 ₹2,10,700 Lowest | 3,801 ₹3,72,498 | 5,500 ₹5,39,000 |
| 3.00 | Excavating in trenches, in any type of soil not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, etc or not exceeding 10 Sqm on plan and not exceeding 1.5m in depth for shafts, cesspits, manholes, pier holes, etc and getting out in any type of soil complete all as specified and directed. | 55 | CUM | 210 ₹11,550 | 110 ₹6,050 Lowest | 300 ₹16,500 | 850 ₹46,750 |
| 4.00 | Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed. | 35 | CUM | 50 ₹1,750 | 40 ₹1,400 | 21 ₹735 Lowest | 1,250 ₹43,750 |
Tender Value
₹53 L
EMD Value
₹1.0 L
Closing Date
15 Jun 2026, 6:00 pmClosed
CWE MHOW
HQ CWE MHOW, MHOW CANTT, MHOW (M.P)-453441
PROVN OF REPLACEMENT OF DG SET OF CAPACITY 500 KVA ALONGWITH AMF PANEL AGAINST BER AT FILTRATION PLANT UNDER GE MIS MHOW
2026_MES_766163_1
CWE/MHOW/91(T) OF 2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
HQ CWE MHOW
Please refer Tender docs
8 documents required · 8 mandatory
₹1,000
Yes
GE (M) Inf School Mhow
₹1.0 L
7 Sept 2026
18 May 2026
17 Jun 2026
18 May 2026
15 Jun 2026
2 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation , commissioning and testing of diesel engine driven Gen with sound proof acousri cenclosure(canopy CRCA sheet of 2mm thickness and noise level below 75 decible/M) and provision of exhaust fan insise the canopy to control the noise level as per limit of central pollution control board (CPCB IV+) 500 KVA 3 phase 415 volt 1500 RPM, 4 wire 50 cycle and power factor 0.8 complete all as specified including complete with foundation (using 100 mm thick PCC 1:4:8 type D-2 as in lean concrete, flyash brick masonry in CM 1:6, the top of the plinth shall consist of 100 mm thick PCC 1:2:4 type B-1 over 75 mm thick PCC 1:4:8 type D-2 over compacted moorum filling, 10 mm thick rendering in CM 1:4 on brick surface) and comprising of the following with set of tools and two years maintaince spares as recommended by the manufacturer complete all as specified and directed :- (Make :Greaves power,Kirlosker Cummins India Ltd) | 1 | Each Job | - | - |
| 1.01 | (a) Prime mover :- Suitable for driving 500 KVA alternator, water cooled, battery start diesel engine of adequate BHP conforming to BSS frame pedestal support with anti vibration pad rated for continuous running capable of taking 10 % over load for one hour in any 12 hrs operation with the following standard activities:- (i) Fly wheel to match with the flexible coupling
(ii) Flexible coupling with guard
(iii) Air cleaner oil bath type / dry type
(iv) Lubricating oil filter paper element type
(v) Fuel pump
(vi) Blower type fan and radiator
(vii) Governor for class 'A' governing as per IS -1601 of ELEC/G3
(viii) Starter , motor for electric start complete with dynamic alternate , lead acid batterie of 02 nos heavy duty of capacity 12 V 180 AH each or adeqaute size and length of cable not less than 2m long including battery box all as directed.
(ix) Hour meter and RPM indicator
(x) Exhaust pipe brought outside the bud and lagging of entire exhaust pipe with 12 mm dia arrestor rope
(xi) Instrument panel duly wired compromising of the followiing:-
(a) Lub oil temp gauge
(b) Lube oil pressure gauge
(c) High/ Low temp gauge
(d) Starting switch with key
(e) Fuel tank | - | - | - | - |
| 1.02 | (b) ALTERNATOR :- 500 KVA at 0.8 PF brush less self excited, self regulated 3 phaser , 50 HZ 415 V 1500 RPM 4 wire screen protected drip proof enclosure free from stimulation problem continuous rating conforming to BS 2613 IS 4722 complete with automatic voltage regulator between +5% of set voltage from no load to full load. (c) Automatic Main Failure Panel :- Supply, installation , commissioning and testing of AMF panel for 500 KVA DG Set fabricated out of MS sheet (factory made) suitable for floor mounted higned from panel for easy accessibility with suitable rated bus bar internal wiring and with provision for connecting incoming/ out going leads with the following accessories as per the manufacturing DG Set :- (i) MCCBs of suitable rating (For DG Set & main incoming)
(ii) Auxiliary contactor with timer (on delay)
(iii) Current transformer
(iv) Voltmeter digital type with selector switch
(v) Ammeter digital type with selector switch
(vi) Frequency meter digital type
(vii) Power factor digital type
(viii) KWH meter electronic type
(ix) One set of indicator lamps (Red, Yelllow, Blue)
(x) Push button start and stop
(xi) One set of lamps for indicating " load on set" "load on mains" "set fails to start" "low oil pressure " "high cylinder temperature" " Battery low" | - | - | - | - |
| 1.03 | (xii) Battery charger connected to main supply side to charge batteries compromising of the following :-
(xiii) Transformer of adequate capacity with quto cut facilities.
(xiv) Recitifier
(xv) DC ammeter and DC Voltmeter
(xvi) Indicator lamp for battery
(xvii) Charge rate selection for tickle or high charge.
(xviii) Set of easily to accessible control fuses
(xi) Set of relays auto start the DG Set on main failure and low voltage
(xx) Over/under voltage relay
(xxi) Change over switch open execution type of suitable capacity with HRC fuse
(xxii) Reverse power relay
(xxiii) Emergency stop (A) Genset specification ↓
1. Genset rating - Prime
2. Genset output (kVA/kWe) - 500 / 400
3. Genset model - GPWII-PIV-500M
4. Gross engine Power (kWm) - 444
5. Gross engine Power (HP) - 604.1
6. Engine model - 12V14TAG31
7. Aspiration / Cooling - TCAC
8. No. of Cylinders / Arrangement - 12 / V-Type
9. Displacement (L) - 16.8
10. Bore x Stroke (mm) - 115 X 135
11. Compression ratio - 16.8
12. Rated RPM - 1500
13. Overspeed trip (RPM) - 1650
14. Governor type / DG Perfomance Class - Elec / G3
15. Frequency Regulation - Isochronous
16. Air cleaner type / Qty - Dry / 02 | - | - | - | - |
| 1.04 | (B) Exhaust system:-
1. Max allowable backpressure (kPa) - 15
2. Exhaust temperature ( Deg C) - 550
3. Silencer type - NA
4. Aftertreatment System - DOC+SCR+ASC
(C) Engine electrical system:-
1. Charging alternator VDC / Amps - 24 V / 44 A
2. Starter motor rated voltage (DC) - 24
3. Battery voltage (DC) / Capacity (AH) - 12V / 180 AH X 2
(D) Fuel System:-
1. Recommended fuel - IS 1460, HSD
2. Fuel tank capacity (L) - 740
(E) Fuel Consumption @ % load (LPH)(Including radiator fan + other accessories):-
1. LPH @ 100% - 105.00
2. LPH @ 75% - 79.00
(F) Lubricating Oil System:-
1. Lube oil sump capacity (L) - 50
2. Lube oil change period (Hrs) - 500
3. Lube oil consumption (% of SFC) - ≤0.06%
4. Lube oil filter type / Qty - Spin on / 02
5. Recommended lube oil grade - 15W40, API CI4+
6. Recommended lube oil - Greaves Maxtherm | - | - | - | - |
| 1.05 | (G) Alternator Specification:-
1. Alternator Make - LS
2. Voltage (3P) - 415
3. Frequency (Hz) - 50
4. Current (3P) (Amps) - 695.6
5. Type - 4P, rotating field
6. Voltage regulator - Automatic
7. Voltage regulation -% - ±1%
8. Insulation class - H
9. Temperature rise (Deg C) - 125
10. Bearing (Qty / type) - 1, sealed
11. Coupling - Flex disc
12. Unbalanced load capability - 25% of rated amps (H) Cooling System:-
1. Max ambient capability (Deg C) - 50
2. Coolant capacity (Eng + Rad) (L) - 120
(I) Controller:-
1. Controller Model - DSE 6120 MKIII
(J) DEF System:-
1. Recommended fuel - ISO 22241, DIN-70070
2 DEF Tank Capacity (L) - 60
(K) DEF Consumption:-
1. LPH @ 100% - 5.3
2. LPH @ 75% - 4.0
(L) Genset Outer Dimensions:-
1. Length(L) X Width(W) X Height(H) (mm) - 5615 X 2000 X 2965
2. Dry Weight (Approx.) (kg) - 5650 | - | - | - | - |
| 1.06 | Disclaimer:-
1. Ref.: ⁽1⁾Fuel consumptioin @ 0.85 Specific Gravity with 5% Tolerance,
DEF consumption : 5% of FC
2. PRIME POWER RATING as per ISO 8528
3. Conformance standards: Engine - BS 5514, ISO 3046, Alternator - IS 13364 (Part - II), Genset - SO 8528 and Tolerances as applicable. Note :- (i) Any fitting /fixture are deemed to be included above which are required for its proper functioning
(ii) Necessary foundation for installaiton of DG Set shall be provided as per manufacturer recommendatios and cpost deemed inclusive of the rates quoted above.
(iii) DG Set should automatically start when AC main fails and load should also transfer on DG set automatically and also switch off while main AC ON.
(iv) The contractor shall provide Engine operation/ maintenance and spare parts alternator warranty certificate and Engine test certificate. | - | - | - | - |
| 2 | S & F in replacement XLPE insulated and PVC armoured heavy duty electric cables with aluminum conductor, 1100 volt grade of size 400 sqmm, 4.0 core, in trenches/through pipes/ducts or on poles/walls jointing to O/H conductor, LT panels, main switch with suitable size aluminum lugs and testing complete all as specified & directed for the following sizes:-
Note : (a) Excavation shall be measured and paid seperately under respective items of Sch 'A' .
(b) All required lugs of suitable sizes according to laying of cable & Connection deemed to be including in quoted rate. | 98 | RM | - | - |
| 3 | Excavating in trenches, in any type of soil not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, etc or not exceeding 10 Sqm on plan and not exceeding 1.5m in depth for shafts, cesspits, manholes, pier holes, etc and getting out in any type of soil complete all as specified and directed. | 55 | CUM | - | - |
| 4 | Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed. | 35 | CUM | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.24 MB
BOQ_858069.xls
BOQ • 1.87 MB
PS91T.pdf
Tender Documents • 0.44 MB
SpecialCondition91T.pdf
Tender Documents • 0.22 MB
GenralPagesAndConditions91T.pdf
Tender Documents • 0.64 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .