Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.5 LAccepted-AOC PLOT NO 28 SANTOSHIMA COLONY WEST MARREDPALLY SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | L1 | Accepted-AOC LOWEST QUOTED BIDDER | |
| 2 | L2₹28.8 L+₹18,127 (0.63%)Rejected-Finance | L2 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER | |
| 3 | L3₹31.1 L+₹2.5 L (8.71%)Rejected-Finance HOUSE NO 2 4 136 LINGREDDY MANSION BLOCK NO IV OPP HANUMAN TEMPLE TADBUND SECUNDERABAD 500009 | SECUNDERABAD | HYDERABAD | TELANGANA | 500009 | L3 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER | |
| 4 | L4₹31.5 L+₹2.9 L (10.1%)Rejected-Finance | L4 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER | |
| 5 | L5₹31.9 L+₹3.3 L (11.6%)Rejected-Finance | L5 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
Tender Value
Refer Docs
EMD Value
₹76,000
Closing Date
14 Oct 2020, 6:00 pmClosed
CWE AIR FORCE SECUNDERABAD
CWE AIR FORCE SECUNDERABAD, BOWENPALLY - POST, SECUNDERABAD- 500 011
SPECIAL REPAIRS FOR REPLACEMENT OF BER AC PLANT AT FLYING CLOTHING STORE AT AFA HYDERABAD
2020_MES_380376_1
86627/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AFA) HYDERABAD
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE (AFA) HYDERABAD
₹76,000
Yes
16 Dec 2020
25 Sept 2020
16 Oct 2020
25 Sept 2020
14 Oct 2020
2 Oct 2020
25 Sept 2020 - 30 Sept 2020
Amount
Supply, install and commisioning of new factory made microprocessor controlled air cooled variable refrigerant flow type air conditioning system of capacity 30 TR to maintain a temparature range 22 degree +/- 2 degree Celcius consisting modular type outdoor units equipped with highly efficient full inverter scroll compressors (all compressors will have to be inverter type), special acryl precoated / blue fin heat exchanger, low noise condenser fan, The Outdoor and Indoor units shall be integrated with special super wiring system with LCD display into one common wiring circuit from the indoor control arrangement including refrigerant gas R410A and piping system, complete suitable for refrigerant R410A or equivalent non-CFC type and including all structural MS frame work PCC platforms required complete all as specified and as directed. Make- VOLTAS/BLUE STAR/LG /CARRIER/DAIKIN
Note for item 1 : (i) All external cabling, sub main wiring and refrigerant piping in between indoor and outdoor units shall be measured and paid separately. (ii) unit rate quoted shall deemed to be includes complete factory made outdoor units, special super wiring system (control wiring) all PCC work including plinth, MS angle supports etc. (iii) Indoor units, refrigerant piping, cabling etc. shall be measured and paid under separate items. (iv) The entire AC system shall be microprocessor controlled and it shall be able to operate from both inside and outside of the rooms. (v) No humidity control system and fresh air charge arrangement is required to be provided with the airconditioning system. (vi) design and drawing of complete system to be submitted to GE for approval before commencement of work
Supply and fix ceiling mounted 4 way air discharge cassette type indoor units Capacity of each indoor unit shall not be less than 3.0 TR with compact cooling, having complete accessories including front grill and cord less remote control unit and multispeed fan motor, dynamically balanced blower and designed for silent operation, including advanced air filters to keep the air clean and dust free at 20 micron level. The filter shall have to be synthetic washable media type arranged for convenient cleaning and replacement, built-in drain pump,suitable drain pan fabricated out of heavy sheet steel insulated with 6mm expanded polyethylene sheet including remote operating arrangements with board LCD display system and including suitable drain pipe connected upto the ground level outside the building through suitable route complete all as specified and as directed. Make- VOLTAS/BLUE STAR/LG /CARRIER/DAIKIN
Supply and fix wired remote control unit suitable for central room wise control for all cassette type units installed in all individual rooms together with LCD display and self daignostic features complete all as specified and directed.
Supply and installtion of refrigerant copper piping insulated with Nitrile Rubber Tubular insulation for the following sizes (outer dia) including suitable joints / branch connectors and distributers for indoor & outdoor units as required at site complete all as specified and as directed. Make: MANDEV / MAXFLOW / RAJCO
(a) 41.3 mm with 19 mm thick insulation
(b) 34.9 mm with 19 mm thick insulation
(c) 28.6 mm with 19 mm thick insulation
(d) 25.4 mm with 19 mm thick insulation
(e) 22.2 mm with 13 mm thick insulation
(f) 19.1 mm with 13 mm thick insulation
(g) 15.9 mm with 13 mm thick insulation
(h) 12.7 mm with 10 mm thick insulation
(j) 9.5 mm with 8 mm thick insulation
Supply and fix UPVC heavy class drain pipes with all fittings and necessary thermal insulation with 6mm thick Nitrile Rubber tubes for the cassette type units for the following diameters of the pipes duly fixed to wall floor with suitable MS brackets / clamps etc complete all as specified and as directed.
(a) 32mm outlet dia
(b) 40mm outer dia
Supply and fix perforated cable tray, made of 1.0mm thick plain Galvanized steel sheet, for laying of the XLPE cable, sub main Wiring, copper tubing etc including all supports, brackets, clamps, nuts & bolts etc all as specified and as directed for the following sizes :-
(a) 150mm (W) x 50mm (D)
(b) 250mm (W) x 50mm (D)
(c) 300mm (W) x 50mm (D)
Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor,1100 Volts grade of following :-
(a) 2.5 Sqmm, 2 core
(b) 2.5 Sqmm, 4 core
(c) 4.0 Sqmm, 4 core
S&F of MCB DB SPN 8 way with copper bus bar & neutral link and earth bar and having double door type to be fixed in the wall by grouting including connections and making good the disturbed surface of wall to perfectly match with the exsting wall complete all as specified and as directed.
S&F of MCB SPN 6 to 32A, 10KA rupturing capacity complete all as specified and as directed.
S&F of Fix MCB SP 6 to 32A, 10 KA rupturing capacity complete all as specified and as directed.
Material and Labour for Design, Febrication, Supply, installation, testing and commissioning control panel in door type suitable for package type air conditioner, made out of 2mm thick MS sheet duly powder coated suitable size, 3 phase 4 wire 415 Volt with angle iron frame, cubical type complete, with minimum IP 54 as per IS 13947 protection with PCC foundation (1:2:4 ) type B2 complete all as specified and directed by Engr in charge, suitable for housing and comprising the following
(a) Aluminium bas bar 400 amps - 04 Nos, supported with suitable size of heavy duty DMC/FRP stand with suitable size of stainless steel nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral.
(b) Incoming MCCB 250 Amps ,415 volt ,35 KA Breaking capacity, fixed magnetic & adjustable thermal setting 4 pole duly connected to bus bar - 01 No. (Make : LEGRAND/L&T/SCHNEIDER/ABB)
(c) MCCB 63 Amps ,415 volt ,25 KA Breaking capacity, fixed magnetic & adjustable thermal setting 4 pole duly connected to bus bar as out going for 3 nos of outdoor units and 01 for indoor units & 01 no spare - 05 No. (Make : LEGRAND/L&T/SCHNEIDER/ABB)
(d) MCCB 100 Amps ,415 volt ,25 KA Breaking capacity, fixed magnetic & adjustable thermal setting 4 pole (1 for Automatic Power Factor Controller + 1 Spare) - 02 No. (Make : LEGRAND/L&T/SCHNEIDER/ABB)
(e) LED indicating lamps with holder for main supply indication RYB- Set 01 (Make: L&T/C&S/Siemens)
(f) Instrument control MCB 3 Amps - 03 No. (Make :Legrand/L&T/Schneider)
(g) Digital voltmeter 96mm x 96mm having accuracy class 1.0, 4½ Digit. - 01 No. (Make : AE/ELMEASURE/L&T/Schneider)
(j) Digital Ammeter 96mm x 96mm having accuracy class 1.0, 4½ Digit with 3 Nos CT(600/5) - 04 Nos (Make : AE/ELMEASURE/L&T/Schneider)
(l) Digital type tamper proof Panel door mounted Energy meter - 1 No NOTE:- 1.Panel board manufacture of CPRI Approved 2. All Internal connection of MCCB from BUS Bar to made By using Aluminium busbar of suitable rated Capacity
Dismantling the existing BER AC plant approx 30TR (10TR X 3) installed in the Flying clothing store including compressors units, condensers units, GI ducting, fan motors and panel boards complete and transporting to AGE E/M stores for safe custody including fully dismantling all the plinths and finishing matching with the floor complete all as specified and as directed.
Dismantling wall and ceiling boards (fibre,pulp, insulation,etc) or insulation boards/slabs/blankets, any thickness, including cover fillets etc all as specified and as directed by Engr-in-Charge.
Dismantling timber scantlings 40Sqcm and over in section, in any position in framed work
S &F Armstrong mineral fibreaccoustical suspended ceiling system with optra (board) square edge tiles. The module size of tile is 600x600x15mm, NRC 0.90. Grid is 32x24mm; long Tee is 27x24mm 1.2m long; Cross Tee is 25x24mm 0.6m long; wall angle 3m long 19x19mm size. The grid frame is having a Galvanizing of 120 gm per sqm and passed through 500 hrs of salt test all as per manufacturer’s instructions and directed.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100volts grade, cross-sectional area 25 sq. mm 4 core complete all as specified and directed
M&L Earthing with galvanized steel earth plate 600 x 600 x 6.3 mm thick, thick buried directly in ground (Earth pit not less than 2.25 m deep below ground level) with the top edge of earth plate at a depth of not less than 1.5 mtr below normal ground level, connected to GI earth strip of size 25 x 4 mm as earthing lead upto 7.5 mtrs by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion all as specified and directed. NOTE: earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:2:4, typeB1 cover 50 MM thick with 8 mm dia TMT bar @ 140 mm C/C, GI watering pipe 20 mm bore medium grade ,funnel, wire mesh ,GI strip and 40 mm dia GI pipe light grade as in earth strip protection upto 7.5 mtr shall be deemed to be included in the quoted rate.
Supply and fix GI earth strip 25mm x 4mm fixed on the wall/ floor connecting up complete all as specified and directed
M&L for communication/ shielded cable of 1 Sqmm 3 Core for connecting of AC plants complete all as specified and directed
BRITE INDUSTRIES
omsai thermax engineers
The Deccan Engineering and Refrigeration Company
kb technologies
M/s Amit Associates
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .