Loading…
Loading…
| # | Company |
|---|---|
| 1 | 3 FINANCIAL BID OPENED ON DATE 26 10 2022 |
Tender Value
₹64.9 L
EMD Value
₹64,864
Closing Date
6 Feb 2023, 11:00 amClosed
Supply, Installation, Testing, and Commissioning of Electric Vehicle Chargers
NBCC/RBGDelhi1/NIT/VANIJYABHAWAN/2023/54
NBCC/RBGDelhi1/NIT/VANIJYABHAWAN/2023/54
Open Tender-Domestic
Electrical Work
New Delhi, Delhi
₹2,950
₹64,864
27 Feb 2023
19 Jan 2023
6 Feb 2023
6 Feb 2023
15 Feb 2023
No. Item No @18%) Scheduled) (DSR) DSR)
Part-A (Non DSR Items)
Supply, intallation,testing and commissiong of suitable 7-8 KW type -II input,
output wall / pole mounted single phase. AC Charger 230V - 240 V, 50 Hz type 2,
cable 5 mtr, socket, (with shutter), 32A with type 2 plug, LED Display with OCPP
load management / charging protocol, 1.6 or higher network interface, 4G, RFID,
1 Wifi, GSM, LTE, Ethernet, Mobile App, integrated energy metering. Protection of 8 Nos. 125033.41 1000267.25 1000267.25
charger with 30 ma ground fault detection, OC, OV, UV, surge protection short
circuit IP 54, IK-08, operating temperature -10 degree C to + 50 degree C, humidity
<95%, IEC 61851-1, IEC 61851-22, IEC61851-23 with LED status indication etc, as
complete as per requirement of site, technical data sheet & directed by EIC.
Supply, intallation,testing and commissiong of suitable 25-30 KW DC charger,
for electrical vehical CCS2 type -II input, output wall / pole mounted three phase.
Charger 415V +- 10 V, 3 phase 50 Hz type 2, cable minimum 5 mtr length, socket,
(with shutter), 40A with type 2 plug, LED Display with OCPP load management /
charging protocol, 1.6 or higher network interface, 4G, RFID, Wifi, GSM, LTE,
Ethernet, Mobile App, integrated energy metering. Protection of charger with 30 ma
ground fault detection, OC, OV, UV, surge protection short circuit IP 54, IK-08,
operating temperature -10 degree C to + 50 degree C, humidity <95%, IEC 61851-
1, IEC 61851-22, IEC61851-23 with LED status indication etc, as complete as per
requirement of site, technical data sheet & directed by EIC.
Design, Manufacturing, supplying, Installation, testing & commissioning of
Distrubution board made of 14 gauge C.R.C.A sheet, Steel dust and vermin proof ,
free standing wall mounted construction with reinforcement of sutiable size MS
base channel. 3 mm thick cable gland plate shall be provide on the top as well as
bottom of the Distribution board duly finished with chemical treatment of the
3 C.R.C.A sheet including approved shade of powder coated painting . 01 nos
earth bus shall be provided full length of board with bus bar chamber, cable alley,
cable gland plates etc. as required duly painted from inside as well as out side.
Detail of switchgear & accessiories as mentioned below vide item no-1, 2 .
(Note- The rates should comprissed along with the all material & accessories and
required switchgears as below
a) Incoming:
200 Amp, 04 pole, FP 36 KA MCCB- 1 Nos.& Spare 01 Nos
1 Set R,Y,B Indications with control MCBs as required
1 Set R,Y,B bus bar of suitable current carrying capacity including earth bus as
required
b) Outgoings:
i) 100 Amp., 04 pole MCCB 36 KA -1 Nos. & Spare 01 Nos
ii) 63 Amp. 04 pole MCCB 36 KA MCCB -01 Nos. & Spare 01 Nos
iii) 63A,2 pole isolater, 08 Nos.
Panel described as above 2 Set 648599.91 1297199.81 1297199.81
Supplying of one number PVC insulated and PVC sheated/ XLPE,
4 aluminium armoured power cable of 1.1 KV grade of following sizes
i) 4C X 10 sq. mm AI./Ar cable 50 Mtr 380.51 19025.60 19025.60
ii) 3½ X 185 sq. mm Al/Ar cable (For LT panel to Distribution Board ) 260 Mtr 2207.48 573945.26 573945.26
iii) 3½ X 70 sq. mm Al/Ar cable (Distribution Board to Charger ) 120 Mtr 949.36 113922.97 113922.97
Part-B (DSR Items 2022)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of
FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel
conduit as required
1.7.6 2 X 16 sq. mm + 1x 6 sq mm earth wire 250 Mtr 1001.63 250407.15 250407.15
Supply, intallation,testing and commissiong of 25 mm sizes of steel conduit along
5 1.20.2 with accessories in surface/ecess including painting in case of surface conduit , or 100 Metre 272.20 27220.48 27220.48
cutting the wall and making good the same in case of recessed conduit as required
Supply, intallation,testing and commissiong of 32 mm sizes of steel conduit along
6 1.20.3 with accessories in surface/ecess including painting in case of surface conduit , or 50 Metre 346.64 17331.79 17331.79
cutting the wall and making good the same in case of recessed conduit as required
Supplying and fixing following modular switch/ socket on the existing modular
plate & switch box including connections but excluding modular plate etc. as
required.
(i) 1.24.5 6 pin 15/16 amp socket outlet 8 Nos 209.47 1675.76 1675.76
Supplying and fixing following size/ modules, GI box alongwith modular base &
8 1.27 cover plate for modular switches in recess etc as required.
(i) 1.27.4 6 Module (200mmX75mm) 8 Nos 427.45 3419.57 3419.57
Supplying and installing following size of perforated painted with powder
coating M.S. cable trays with perforation not more than 17.5%, in
9 4.1 convenient sections, joined with connectors, suspended from the ceiling with
M.S. suspenders including bolts & nuts, painting suspenders etc as required.
(i) 4.1.4 300 mm width X 50 mm depth X 1.6 mm thickness 250 Mtr 826.18 206546.03 206546.03
Supplying and installing following size of perforated painted with powder
coating M.S. cable trays bends with perforation not more than 17.5%,, joined with
10 4.2 connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts,
painting suspenders etc as required.
(i) 4.2.4 300 mm width X 50 mm depth X 1.6 mm thickness 10 each 1529.03 15290.25 15290.25
Digitally signed by
DEVENDRA DEVENDRA SINGH
SINGH RAJPOOT RAJPOOT
Bill of Quantity
S. DSR Rate DSR (GST Rate (Non- Amount Amount (Non-
Description of Items Qty. Unit Amount
No. Item No @18%) Scheduled) (DSR) DSR)
Supplying and installing following size of perforated painted with powder
coating M.S. cable trays Tee with perforation not more than 17.5%, joined with
11 4.3 connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts,
painting suspenders etc as required.
(i) 4.3.4 300 mm width X 50 mm depth X 1.6 mm thickness 10 each 1816.12 18161.16 18161.16
Supply & laying of 25 mm x 5 mm G.I. strip at 0.50 metre below ground as strip
earth electrode, including connection, terminating with Nut, Bolt, Spring
12 5.9 100 Metre 153.12 15311.52 15311.52
washer etc as required. (Jointing shall be done by overlapping and with 2 sets
of G.I. nut bolt & spring washer spaced as 50 mm)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1
KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
(i) 7.5.1 Upto 35 sq. mm 50 Mtr 39.34 1967.11 1967.11
(ii) 7.5.2 Above 35 sq. mm and upto 95 sq. mm 120 Mtr 60.61 7272.97 7272.97
(iii) 7.5.3 Above 95 sq. mm and upto 185 sq. mm 260 Mtr 81.87 21287.27 21287.27
Supplying and making end termination with brass single compression gland
14 9.1 and aluminium lugs for following size of PVC insulated and PVC
sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
(i) 9.1.23 3½ X 70 sq. mm Al/Ar cable 6 set 497.62 2985.75 2985.75
(ii) 9.1.27 3½ X 185 sq. mm Al/Ar cable 4 set 930.39 3721.55 3721.55
(iii) 9.1.32 4C X 10 sq. mm AI/Ar cable 10 set 286.03 2860.28 2860.28
Total 6486356.00
Digitally signed by
DEVENDRA DEVENDRA SINGH
SINGH RAJPOOT RAJPOOT
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT.pdf
Tender Document
AC SLD Final Drawing.pdf
Tender Document
Revised BOQ.pdf
Tender Document
Technical Specifications - Revised.pdf
Tender Document
GCC for PMC Works 2022.pdf
Tender Document
SCC.pdf
Tender Document
List of Approved Makes - Revised.pdf
Tender Document
corrigendum-1302-Corr04.pdf
pdf • 0.40 MB
addendum-45df919372b5-Corrigendum 03.pdf
pdf • 0.37 MB
corrigendum-1264-Corrigendum 03.pdf
pdf • 0.37 MB
corrigendum-1263-Corrigendum 02.pdf
pdf • 0.37 MB
corrigendum-1247-Corrigendum01.pdf
pdf • 0.47 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .