Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L2₹4.9 CrAccepted-AOC PL NO 17 18 RUTUJA RESIDENCY SNO 120 MODERN COLONY KOTHRUD C M E PUNE CITY PUNE MAHARASHTRA INDIA 411029 | PUNE | PUNE | MAHARASHTRA | 411029 | ₹4.9 Cr | L2 | Accepted-AOC After negotiation the bidder reduce the rate |
| 2 | L1₹4.9 CrRejected-Finance SCF 15 HUDA COMPLEX 184 NEW IDC 124001 | ROHTAK | HARYANA | 124001 | ₹4.9 Cr | L1 | Rejected-Finance Bidder denied the work. |
| 3 | L3₹6.5 CrRejected-Finance | ₹6.5 Cr | L3 | Rejected-Finance L-3 |
| 4 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| Sl No | Description | Qty | Unit | Highlight Associates and Contractors L1 | UNIVASTU BOOTES INFRA LLP L2 | M/s S S Sathe L3 |
|---|---|---|---|---|---|---|
| 1.00 | SITC of HT Panel with one Incomer and 2 O/G make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 15,75,000 ₹15.8 L | 31,40,435 ₹31.4 L | 35,82,657 ₹35.8 L |
| 2.00 | MAIN LT PANEL as per IEC 61439 PTTA as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid.
SECTION-01
INCOMER :
2000A TP+NL 50kA ACB x 2Nos.,
1600A TP+NL 50kA ACB x 1 No.
BUS BAR : 2000 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.
BUS COUPLER : 1 x 1500A 4P 50kA ACB
OUT GOINGS : 800 A 4P 50kA ACB x 1 No.,
630A FP 25kA MCCB x 2 No.,
400A FP 25kA MCCB x 1 No.,
250A FP 25kA MCCB x 3 Nos.,
160A FP 25kA MCCB x 1 Nos.,
100A FP 25kA MCCB x 4 Nos.,
40A FP 25kA MCCB x 1 No.,
25A FP 25kA MCCB x 1 No.,
make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 34,00,000 ₹34 L | 41,20,845 ₹41.2 L | 35,55,824 ₹35.6 L |
| 3.00 | DG Panel (DG Synchronizationl Panel) as per IEC 61439 PTTA
as per technical specifications below :
Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid.
INCOMER : 1600A, & 800A 50kA Air Circuit Breaker
BUS BAR : 2500 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.
BUS COUPLER : 1 x 2500A 50kA 4P ACB
OUT GOINGS : 3 X 1600 AMP 4P 50kA ACB
make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 29,85,000 ₹29.9 L | 40,01,400 ₹40.0 L | 35,69,875 ₹35.7 L |
| 4.00 | UPS Panel (UPS feeder Panel)
as per technical specifications below :
Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
INCOMER : 800 AMP TP+NL ACB x 1 No., 630 AMP TP+NL MCCB x 1 No.,
BUS BAR : 800 AMP, 500 Volts, 3 phase 50 HZ TP+2N high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.
OUTGOING : 400 AMP 4P MCCB 15kA 5 Nos. WITH INDICATION LAMPS
All Items complete as above make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 8,50,000 ₹8.5 L | 8,59,673 ₹8.6 L | 9,25,462 ₹9.3 L |
| 5.00 | A-MDB-LG ( RAW Panel Block-A )
as per technical specifications below :
Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid.
INCOMER : 250 AMP 15kA TP+NL MCCB with Thermal Magnetic protection, Indication lamps
BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.
OUT GOINGS :
63 AMP 4P 15kA MCCB 1 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS
40 AMP 4P 15kA MCCB 13 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS
16 AMP DP MCB 15kA 2 Nos.
complete panel as above make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 3,00,000 ₹3 L | 3,72,879 ₹3.7 L | 3,22,845 ₹3.2 L |
| 6.00 | B-UMDB-BL
as per technical specifications below :
Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
INCOMER : 400 AMP TP+NL 15kA MCCB X 4 Nos.
BUS BAR : 1500 AMP, 500 Volts, 3 phase 50 HZ TP+2N high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.
OUTGOING :
400 AMP 4P 15kA MCCB x 1 No. WITH INDICATION LAMPS
250 AMP 4P 15kA MCCB x 2 Nos. WITH INDICATION LAMPS
200 AMP 4P 20kA MCCB x 1 No. WITH INDICATION LAMPS
160 AMP 4P 20kA MCCB x 1 No. WITH INDICATION LAMPS
100 AMP 4P 20kA MCCB x 3 Nos. WITH INDICATION LAMPS
All Items complete as above make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 6,50,000 ₹6.5 L | 6,73,723 ₹6.7 L | 8,54,851 ₹8.5 L |
| 7.00 | A-USMDB-LG ( UPS Panel Block-A )
as per technical specifications below :
Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid.
INCOMER : 400 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps
BUS BAR : 400 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.
OUT GOINGS :
100 AMP 4P 15kA MCCB 1 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS
63 AMP 4P 15kA MCCB 12 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS
40 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS
complete panel as above make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 3,00,000 ₹3 L | 3,77,074 ₹3.8 L | 3,55,621 ₹3.6 L |
| 8.00 | B-USMDB-BL ( UPS Panel Block-B )
as per technical specifications below :
Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid.
INCOMER : 250 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps
BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.
OUT GOINGS :
80 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS
63 AMP 4P 15kA MCCB 7 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 1,70,000 ₹1.7 L | 1,91,779 ₹1.9 L | 1,14,568 ₹1.1 L |
| 9.00 | C-USMDB-BL ( UPS Panel Block-C )
as per technical specifications below :
Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid.
INCOMER : 250 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps
BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.
OUT GOINGS :
63 AMP 4P 15kA MCCB 6 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS
80 AMP 4P 15kA MCCB 2 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS
complete panel as above make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 1,70,000 ₹1.7 L | 1,91,779 ₹1.9 L | 1,55,784 ₹1.6 L |
| 10.00 | D-USMDB-GF ( UPS Panel Block-D )
as per technical specifications below :
Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid.
INCOMER : 200 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps
BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.
OUT GOINGS :
63 AMP 4P 15kA MCCB 7 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS
complete panel as above make adlec, vidhut control & tricolite complete in all respect. | 1 | Each Set | 1,70,000 ₹1.7 L | 1,86,998 ₹1.9 L | 1,45,987 ₹1.5 L |
Tender Value
₹5.5 Cr
EMD Value
₹11.0 L
Closing Date
27 Mar 2024, 10:00 amClosed
GAUTAM KUMAR
Executive Engineer Office (Faridabad)
Development of Theme Park site at Jyotisar Kurukshetra ( Electrical, AHU, Cables and Insulation )
2024_HBC_370074_1
2024E2466BF8 BF18 462A 9CE9 58EB36B4BF8B1270HTC
Open Tender
Civil Works
45 days
Kurukshetra (Thanesar)
2 documents required · 2 mandatory
₹23,600
₹11.0 L
Yes
29 Apr 2026
16 Mar 2024
27 Mar 2024
16 Mar 2024
27 Mar 2024
16 Mar 2024
Amount
SITC of HT Panel with one Incomer and 2 O/G make adlec, vidhut control & tricolite complete in all respect.
MAIN LT PANEL as per IEC 61439 PTTA as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. SECTION-01 INCOMER : 2000A TP+NL 50kA ACB x 2Nos., 1600A TP+NL 50kA ACB x 1 No. BUS BAR : 2000 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. BUS COUPLER : 1 x 1500A 4P 50kA ACB OUT GOINGS : 800 A 4P 50kA ACB x 1 No., 630A FP 25kA MCCB x 2 No., 400A FP 25kA MCCB x 1 No., 250A FP 25kA MCCB x 3 Nos., 160A FP 25kA MCCB x 1 Nos., 100A FP 25kA MCCB x 4 Nos., 40A FP 25kA MCCB x 1 No., 25A FP 25kA MCCB x 1 No., make adlec, vidhut control & tricolite complete in all respect.
DG Panel (DG Synchronizationl Panel) as per IEC 61439 PTTA as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 1600A, & 800A 50kA Air Circuit Breaker BUS BAR : 2500 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. BUS COUPLER : 1 x 2500A 50kA 4P ACB OUT GOINGS : 3 X 1600 AMP 4P 50kA ACB make adlec, vidhut control & tricolite complete in all respect.
UPS Panel (UPS feeder Panel) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 800 AMP TP+NL ACB x 1 No., 630 AMP TP+NL MCCB x 1 No., BUS BAR : 800 AMP, 500 Volts, 3 phase 50 HZ TP+2N high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUTGOING : 400 AMP 4P MCCB 15kA 5 Nos. WITH INDICATION LAMPS All Items complete as above make adlec, vidhut control & tricolite complete in all respect.
A-MDB-LG ( RAW Panel Block-A ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 250 AMP 15kA TP+NL MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 63 AMP 4P 15kA MCCB 1 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 40 AMP 4P 15kA MCCB 13 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 16 AMP DP MCB 15kA 2 Nos. complete panel as above make adlec, vidhut control & tricolite complete in all respect.
B-UMDB-BL as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. INCOMER : 400 AMP TP+NL 15kA MCCB X 4 Nos. BUS BAR : 1500 AMP, 500 Volts, 3 phase 50 HZ TP+2N high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUTGOING : 400 AMP 4P 15kA MCCB x 1 No. WITH INDICATION LAMPS 250 AMP 4P 15kA MCCB x 2 Nos. WITH INDICATION LAMPS 200 AMP 4P 20kA MCCB x 1 No. WITH INDICATION LAMPS 160 AMP 4P 20kA MCCB x 1 No. WITH INDICATION LAMPS 100 AMP 4P 20kA MCCB x 3 Nos. WITH INDICATION LAMPS All Items complete as above make adlec, vidhut control & tricolite complete in all respect.
A-USMDB-LG ( UPS Panel Block-A ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 400 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 400 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 100 AMP 4P 15kA MCCB 1 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 63 AMP 4P 15kA MCCB 12 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 40 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
B-USMDB-BL ( UPS Panel Block-B ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 250 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 80 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 63 AMP 4P 15kA MCCB 7 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
C-USMDB-BL ( UPS Panel Block-C ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 250 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 63 AMP 4P 15kA MCCB 6 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 80 AMP 4P 15kA MCCB 2 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
D-USMDB-GF ( UPS Panel Block-D ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 200 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 200 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 63 AMP 4P 15kA MCCB 7 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
E-USMDB-GF ( UPS Panel Block-E ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 160 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 63 AMP 4P 15kA MCCB 5 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
G-USMDB-GF ( UPS Panel Block-G ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 100 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 100 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 63 AMP 4P 15kA MCCB 6 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
A-ESMDB-GF ( Emergency Panel Block-A) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 80 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 80 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 40 AMP 4P 15kA MCCB 5 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 20 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
B-ESMDB-BL ( Emergency Panel Block-B) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 100 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 100 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 40 AMP 4P 15kA MCCB 6 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 20 AMP 4P 15kA MCCB 2 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
C-ESMDB-BL ( Emergency Panel Block-C) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 250 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 160 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 63 AMP 4P 15kA MCCB 4 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 40 AMP 4P 15kA MCCB 2 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 32 AMP 4P 15kA MCCB 3 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 20 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
D-ESMDB-GF ( Emergency Panel Block-D) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 100 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 100 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 40 AMP 4P 15kA MCCB 6 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
B-MDB-LG ( RAW Panel Block-B ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 250 AMP 15kA TP+NL MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 250 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 63 AMP 4P 15kA MCCB 2 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 40 AMP 4P 15kA MCCB 12 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
C-MDB-LG ( RAW Panel Block-C ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 160 AMP 15kA TP+NL MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 40 AMP 4P 15kA MCCB 14 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 32 AMP 4P 15kA MCCB 2 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
D-MDB-GF ( RAW Panel Block-D ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 160 AMP 15kA TP+NL MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 80 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 40 AMP 4P 15kA MCCB 9 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
E-MDB-GF ( RAW Panel Block-E ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 100 AMP 15kA TP+NL MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 100 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 40 AMP 4P 15kA MCCB 6No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 32 AMP 4P 15kA MCCB 4Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
G-MDB-GF ( RAW Panel Block-G ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 400 AMP 15kA TP+NL MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 400 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 40 AMP 4P 15kA MCCB 10 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 32 AMP 4P 15kA MCCB 4 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 63 AMP 4P 15kA MCCB 4 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
E-ESMDB-GF ( Emergency Panel Block-E) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 100 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 100 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 40 AMP 4P 15kA MCCB 6 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
G-ESMDB-GF ( Emergency Panel Block-G) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 100 AMP TP+NL 15kA MCCB with Thermal Magnetic protection, Indication lamps BUS BAR : 100 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 40 AMP 4P 15kA MCCB 7 Nos. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 32 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS 20 AMP 4P 15kA MCCB 1 No. WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
P-PVDB ( Solar Feeder Panel Parking) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 250 AMP FP 20kA MCCB 2 Nos. with Thermal Magnetic protection, Indication lamps 200 AMP FP 20kA MCCB 1 No. with Thermal Magnetic protection, Indication lamps 100 AMP FP 20kA MCCB 1 No. with Thermal Magnetic protection, Indication lamps BUS BAR : 1000 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 800 AMP 4P 20kA MCCB WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
B-PVDB-BL ( Solar Feeder Panel Blook- B) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 200 AMP FP 20kA MCCB 1 No. with Thermal Magnetic protection, Indication lamps 125 AMP FP 20kA MCCB 2 Nos. with Thermal Magnetic protection, Indication lamps 80 AMP FP 20kA MCCB 1 No. with Thermal Magnetic protection, Indication lamps BUS BAR : 630 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 400 AMP 4P 20kA MCCB WITH THERMAL MAGNETIC PROTECTION AND INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
SS-PVMDB ( Solar Feeder Panel Substation ) as per technical specifications below : Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchboard suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing, SPD Provision which connected to the nearest earth grid. INCOMER : 800 AMP FP 15kA MCCB 2 Nos. with Thermal Magnetic protection, Indication lamps 400 AMP FP 15kA MCCB 2 Nos. with Thermal Magnetic protection, Indication lamps 160 AMP FP 15kA MCCB 1 No. with Thermal Magnetic protection, Indication lamps BUS BAR : 2000 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.6 sq. mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. OUT GOINGS : 1800 AMP 4P 50kA ACB with INDICATION LAMPS complete panel as above make adlec, vidhut control & tricolite complete in all respect.
HT Panel 630A for main supply from HT meter cubical make adlec, vidhut control & tricolite complete in all respect.
PART- B : AHU, Insulation Supply, installation, testing and commissioning of Verticle/Horizontal Floor Mounted/Ceiling suspended Airhandling units having following specifications: Frame Structure shall consist of 48mm Extruded Aluminium thermal break profile. Panel: 46mm thick double skin sandwich panels with PUF insulation of density 40 kg/cum. The sheet thickness shall be minimum 0.8 mm for the outer skin and 0.6 mm thickness for the inner skin of GI and it consist of following sections with Mixing Box Filtration Section shall be provided with first stage pre-filter (MERV 8) of 90% efficiency down to 10 micron and secondary stage ESP filter (MERV-14) of 99% efficency down to 3 micron. Megnehelic gauge to be provided for pre and ESP filters. Coil Section: Chilled water coil multi row deep constructed with Aluminium fins of minimum 0.11mm thickness and copper tubes of minimum 29Guage thickness. Copper tube shall be 9.6mm or 12.5mm diameter. All air handling units to be provided with minimum 6 row deep LT Coil & 6 Row deep HT Coil . All TFA/AHU shall be accompany with two set of cooling coil (Primary cooling coil & secondary de-humidification coil). Following size:-- The coil face velocity shall not exceed 2.5m/sec. Drain Pan: Condensate drain pan shall be fabricated from 18 G SS 304 powder coated, insulated with 19 mm thick closed cell elastomeric insulation. Each Air Handling Units, shall be complete with direct driven Plug Fan airfoil design blades suitable for static pressure as detailed below, Squirrel cage induction motor , cooling coils (Copper tubes and Aluminium fins), pre-filter, ESp filter, drain pan, Volume control dampers at outlets (GSS Construction) fireproof double canvass connection, mixing box, flange joint, and other accessories as per specifications (except water shut off valves, drain piping and pressure gauges which are covered under separate item).Motor shall be suitable for 415 ± 10% volts, 50 cycle, 3 Phase AC supply as indicated below ( Make Zeco, System Air, Edgtech for AHU complete in all respect. )
7000 FM 6 Row Deep (8TR LT/11.5TR HT) , 65mm S.P., 5.5 KW
3000 CS (1LT/4.5HT) 6 Row Deep , 50mm S.P., 2.2 KW
1200 CS (1LT/2HT) 6 Row Deep , 50mm S.P., 1.1 KW
1200 CS (0.5LT/2HT) 6 Row Deep , 50mm S.P., 1.1 KW
7500 FM (8.5LT/12.5HT) 6 Row Deep , 65mm S.P., 5.5 KW
12000 FM (7.5LT/20.5HT) 6 Row Deep , 65mm S.P., 7.5 KW
8000 FM (7.5LT/13.5HT) 6 Row Deep , 65mm S.P., 5.5 KW
6000 CS 6 Row Deep (3.5LT/9.5HT) , 50mm S.P., 5.5 KW
4500 CS 6 Row Deep (2.5LT/7.5HT) , 50mm S.P., 3.7 KW
9000 FM (9LT/15HT) 6 Row Deep , 65mm S.P., 7.5 KW
11500 FM (7LT/18HT) 6 Row Deep , 65mm S.P., 7.5 KW
3000 CS (6LT/4HT) 6 Row Deep , 50mm S.P., 2.2 KW
1500 CS (1LT/2.5HT) 6 Row Deep , 50mm S.P., 1.5 KW
1500 CS (2LT/0HT) 6 Row Deep , 50mm S.P., 1.5 KW
2000 CS (1LT/3.5HT) 6 Row Deep , 50mm S.P., 1.5 KW
Supply, installation testing & commissioning of 1.5 TR 5-star inverter split AC (Copper piping, dual filterration with HD and PM 2.5 auto cleanser) Carrier, Daiken or equivalent with stand etc as required at site ( Make Zeco, System Air, Edgtech for AHU complete in all respect.)
Supply, installation, testing & commissioning of suitable size copper pipe and power/communication cable for 1.5TR split AC from outdoor unit to indoor unit complete as required. ( Make Zeco, System Air, Edgtech for AHU complete in all respect.)
Providing and fixing 50 mm thick FR Expanded polystyrene rigid insulation board of required size under deck on ceiling surface, complying with ISO 4898:2008 & ASTM C 578-08b - type VI, having thermal conductivity of 0.0289 W/m K as per ASTM C 578 (measured as per IS 3346), compressive strength of > 350 kPa listed as per ASTM D 1621, density of 34-36 kg/cum as per ASTM D 1622, water absorptions ≤ 1% by volume as per ASTM D 2842, oxygen index of 24.1 to 28.1 listed as per ASTM D 2863, cell size 0.4 mm of dia (max) as per ASTM D 3576. Fixed with suitable water based adhesive and fastener, complete in all respect as per the direction of Engineer-in-Charge ( Make Zeco, System Air, Edgtech for AHU complete in all respect.)
PART- C : CABLES Supply of following 1.1 KV grade Multicore aluminium conductor XLPE FRLS power cable insulated armored cable conforming to IS:7098 Part-1 complete with all amendment ete and should be NABL certified ( Make Havells, Poly Cab, KEI complete in all respect. )
400 sqmm 4 core AL XLPE armored
400 sqmm 3.5 core AL XLPE armored
300 sqmm 3.5 core AL XLPE armored
120 sqmm 4 core AL XLPE armored
95 sqmm 4 core AL XLPE armored
Supply of following size of 11 KV grade Multicore aluminium conductor XLPE FRLS power HT cable insulated armored cable conforming to IS:7098 Part-1 complete with all amendment ete and should be NABL certified 300 SQMM 3 Core armored ( Make Havells, Poly Cab, KEI complete in all respect. )
PART- D : UPS Suppply installation testing and commissioning of Uniline Make 100 KVA Online UPS with Inbuilt Isolation Transformer operating in parallel redundancy Model – Tripower TP 100 3 phase input – 3 phase output •MS rack, Interlinks, UPS to battery Cable, Battery Isolator •Modbus card •Parallel Kit
12v 100 AH x 44 Nos VRLA SMF Batteries to provide 15 mins backup Make – HBL/ Leoch / U Plus
UNIVASTU BOOTES INFRA LLP
M/s S S Sathe
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.37 MB
BOQ_445869.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid