EE(EP), O/o CE(E), KEZ, BGL
Office of the Chief Engineer (Elect.), BSNL , Karnataka Electrical Zone, 1st Floor, WMS Compound , 47th Cross, 9th Main, 5th Block, Jayanagar, Bengaluru - 560041
Instn of 2x2TR AC Unit at BB Room ist floor of CDOT TE Tumkur
2024_BSNL_192283_1
20/CEE/KEZ/2023-2024
Open Tender
Electrical Works
Item Rate
30 days
CDOT TE Tumkur
Please refer Tender documents.
2 documents required · 2 mandatory
₹177
AO (CASH), HQ,BSNL,BGTD
₹1,073
29 Apr 2024
23 Mar 2024
10 Apr 2024
23 Mar 2024
8 Apr 2024
23 Mar 2024
Amount
Installation of 1 No Pace Maker Make 2 x 2TR AC Unit
Installation, Testing and commissioning of 2x 2 TR High Precision split AC unit along with the existing copper piping and the existing copper wire including gas charging, insulation flexible PVC pipes and making opening in wall and making good the damages etc., as required.
Supplying and fixing copper Refrigerant pipes both hot gas and liquid line of size 5/8 inch and 1/4 inch including cutting, brazing, providing all accessories such as bends collars and foam insulation etc., as required.
Supplying and fixing 4 Core 4 Sq.mm PVC insulated, PVC sheathed flexible copper cable for indoor Unit to Outdoor Unit connection including interconnection, testing, commissioning etc., as required.
S&F of 50mm dia PVC pipe of 6 Kg/Sq.cm pressure with bends for protection of copper tubing etc complete as reqd.
Providing and fixing 20mm dia rigid PVC pipe with accessories for drain water arrangement for the above AC units including bends, Elbows complete as required.
S&F of 50mm dia PVC pipe of 6 Kg/Sq.cm pressure with bends for protection of copper tubing etc complete as reqd.
Supplying and filling the R22 refrigerant gas in the refrigerant circuit including transportation of gas cylinder etc., as required.
Conducting pressure testing of the refrigerant circuit both hot gas and liquid line by pressurising the same with nitrogen gas to a certain and checking for retention of the pressure for 24hours i/c checking for any leakages and arresting the same if any etc., as required.
Providing / Fixing suitable MS frame work for split AC outdoor unit made out of solid angles/flat i/c cutting, welding, drilling, painted with suitable colour etc., as reqd.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required a) 6 x 4 sq. mm
b) 3 x 4 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. a) 20mm PVC
b) 25mm PVC
b) 32 mm PVC
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 amps “C” curve, SP, MCB in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Dismantling of 1.5TR Faulty/life expired split AC unit complete with indoor unit, outdoor unit, drain pipe, storing at specified location etc complete as reqd.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .