| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.2 LAccepted-AOC | L1 | Accepted-AOC Being overall reasonable | |
| 2 | L2₹36.5 L+₹1.5 L (4.27%)Rejected-Finance OFFICE NO 101 MALAN PLAZA NEXT TO ESSAR PETROL PUMP NEAR GODAMBLE CORNER RAHATNI PIMPRI DP ROAD RAHATANI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | L2 | Rejected-Finance Not lowest bidder | |
| 3 | L3₹36.7 L+₹1.7 L (4.76%)Rejected-Finance | L3 | Rejected-Finance Not lowest bidder | |
| 4 | L4₹38.8 L+₹3.8 L (10.9%)Rejected-Finance | L4 | Rejected-Finance Not lowest bidder | |
| 5 | L5₹39.2 L+₹4.3 L (12.1%)Rejected-Finance | L5 | Rejected-Finance Not lowest bidder |
Tender Value
₹45.5 L
EMD Value
₹91,100
Closing Date
8 Feb 2021, 6:00 pmClosed
GE CENTRAL KIRKEE
GE CENTRAL KIRKEE RANGE HILLS ROAD PUNE-411003
REPAIR MAINT OF CERTAIN INTERNAL WIRING DISTRIBUTION BOARDS, AND REPLACEMENT OF CONVENTIONAL HIGH BAY LIGHTS WITH LED HIGH BAY LIGHTS AND CONNECTED REPAIRS IN SSS SHED IN A PARK AND MISC BLDG UNDER AGE EM II IN GE CENTRAL KIRKEE
2021_MES_414626_1
8440/E8 OF 2020-2021
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
KIRKEE
AS PER NIT
7 documents required · 7 mandatory
₹500
Yes
GE CENTRAL KIRKEE
₹91,100
Yes
6 Mar 2021
20 Jan 2021
9 Feb 2021
20 Jan 2021
8 Feb 2021
3 Feb 2021
20 Jan 2021 - 2 Feb 2021
Amount
Taking down carefully existing unserviceable aluminum / copper point wiring of any description & in any position with and including existing steel conduit / PVC Conduit / Casing caping fixed on surface/wall/angle/gardder and including all fitting, accessories & fixtures such as switches, ceiling roses, pendants, regulators, sockets, etc including sunken boxes/junction boxes and making good the disturbed surface of walls, floors, ceiling etc to match with the existing surfaces complete all as specified and directed.
M&L for point wiring in non metallic PVC coduit of suitable size but not less than 20mm including all fittings such as elbow, bends, junction boxes, saddles, etc. on surface with and including ISI marked two runs of PVC insulated unsheathed multistranded copper conductor cable (FRLSH) 1.5 sqmm nominal cross sectional area, 1100 volts grade and including one run of 1.5 sqmm (green colour) ISI marked PVC insulated unsheathed multistranded (FRLSH) copper conductor cable as earth wire to be terminated in and incl PVC rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover for one light point or one fan point controlled by one switch including making good the disturbed wall and painting the same with matching to existing wall all as specified and directed by Engineer in charge.
All as per Srl item No 2 above but point wiring for 5 pin socket outlet, 5 Amps on same board with other switches.
All as per Srl item No 2 above but point wiring for 5 pin socket outlet, 5 Amps on independent board.
All as per Srl item No 2 above but point wiring for one five pin socket outlet, 15 Amps & 5 Amp on independent board using 2.5 sqmm two run and one run 2.5 sqmm (nominal area) stranded copper conductor cable.
M&L for point wiring in non metallic white coloured PVC casing & caping of suitable size but not less than 20mm including all fittings such as elbow, bends, junction boxes, saddles, etc. on surface with and including ISI marked two runs of PVC insulated unsheathed multistranded copper conductor cable (FRLSH) 1.5 sqmm nominal cross sectional area, 1100 volts grade and including one run of 1.5 sqmm (green colour) ISI marked PVC insulated unsheathed multistranded (FRLSH) copper conductor cable as earth wire to be terminated in and incl PVC rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover for one light point or one fan point controlled by one switch including making good the disturbed wall and painting the same with matching to existing wall all as specified and directed by Engineer in charge.
All as per Srl item No 6 above but One bell/buzzer point controlled by one push button on the same board with other switches or independent with cables1.5 sq.mm. Size.
All as per Srl item No 6 above but point wiring for 5 pin socket outlet, 5 Amps on same board with other switches.
All as per Srl item No 6 above but point wiring for 5 pin socket outlet, 5 Amps on independent board.
All as per Srl item No 6 above but point wiring for one five pin socket outlet, 15 Amps & 5 Amp on independent board using 2.5 sqmm two run and one run 2.5 sqmm (nominal area) stranded copper conductor cable.
Material and labour for point wiring for one light/ fan/ bell point controlled by one switch in and including steel conduit with and including all steel enamelled fittings such as elbow bends, junction boxes, supporting clamps for proper hanging arregements made out from 20x1mm flat aluminium patti including nuts, bolts and bending to shape etc. of appropriate size but not less than 20mm on surface with two run of PVC insulated unsheathed multistranded copper conductor cable (FRLSH) 1.5 Sqmm nominal cross sectional area 1100 volts grade and including one run of 1.5 sqmm (green colour) PVC insulated unsheathed multistranded (FRLSH) copper conductor cable as earth wire incl. suitable size sunken type Galvanised pressed sheet steel 1.6 mm thick terminal box of suitable size with 3 mm thick laminated hylum sheet for mounting switches, sockets etc. and making good the disturbed wall and painting the same with matching colour of the existing wall, incld material all as specified and directed.
All as per Srl item No 11 above but point wiring for 5 pin socket outlet, 5 Amps on same board with other switches.
All as per Srl item No 11 above but point wiring for 5 pin socket outlet, 5 Amps on independent board.
All a s per Srl item No 11 above but point wiring for one five pin switch socket outlet combination, 15 Amps & 5 Amp (independent) with using 2.5 sqmm two run and one run 2.5 sqmm (nominal area) stranded copper conductor .
Supplying & fixing switch flush type, 5 Amps, single pole, one way , 230 volts AC circuit complete all as specified & directed
Supplying & fixing switch flush type, 5 Amps, Bell push , flush type , 230 volts AC circuit complete all as specified & directed
Supplying & fixing socket outlet, five pin, 5 Amps, flush type, multipurpose, 230 volts AC circuit complete all as specified & directed
Supplying & fixing switch flush type, 15 Amps, single pole, one way , 230 volts AC circuit complete all as specified & directed
Supplying & fixing Socket outlet 2 in 1, 3 pin, 5 and 15 amp flush type , flush type, 230 volts AC circuit complete all as specified & directed
Supplying & fixing ceiling rose PVC/polycarbonate, isolated body, three terminals, complete all as specified & directed .
Supply and fixing in replacement Stepped type electronic fan regulator flush type suitable for ceiling fans, prewired 230 volts AC 50Hz supply 100Watt complete all as specified & directed.
Supply, fixing, connecting and testing in replacement Industrial Earth Plug & socket with sheet metal enclosure of IP44 rating electric driven single phase including MCB 'C' series SP 20 Amps and supplied with neutral links complete all as specified and directed.
Supply, fixing, connecting and testing in replacement Industrial Earth Plug & socket with sheet metal enclosure of IP44 rating electric driven three phase including MCB 'C' series TP 20 Amps and supplied with neutral links complete all as specified and directed.
Dismantling and Taking out old unserviceable copper/aluminium sub main wiring/aluminium armoured cable (used as Sub main wiring) from any height of any Size and Core with all connecting accessories incld. conduit or casing caping and incld. making good to the disturbed wall and painting the same with matching paint as of existing wall incld material all as specified and directed by Engineer in charge.
Material & Labour for Sub main wiring at any height with 2 single core PVC insulated, multi stranded copper conductor cable (FRLSH), unsheathed, 1.5 sqmm, 1100 volt grade drawn through and including New suitable size steel conduit and including one single core PVC insulated multi stranded unsheathed copper conductor cable, 1.5 sqmm, ISI marked, FRLSH type in green colour as continuous earth wire including all accessories and fixing arrengements, supporting clamps, bends, sockets and connecting items etc. all as specified and directed. Note - (a). Two runs of 2.5 Sqmm wiring cable and one run of 2.5 sqmm earth continuity wire with steel conduit shall be measured as as one length.
Material & Labour for Sub main wiring at any height with 2 single core PVC insulated, multi stranded copper conductor cable (FRLSH), unsheathed, 2.5 sqmm, 1100 volt grade drawn through and including New suitable size steel conduit and including one single core PVC insulated multi stranded unsheathed copper conductor cable, 2.5 sqmm, ISI marked, FRLSH type in green colour as continuous earth wire including all accessories and fixing arrengements, supporting clamps, bends, sockets and connecting items etc. all as specified and directed. Note - (a). Two runs of 2.5 Sqmm wiring cable and one run of 2.5 sqmm earth continuity wire with steel conduit shall be measured as as one length.
Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including New suitable size steel conduit including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 4.0 sqmm, 1100 Volts grade, ISI marked, as earth contuinity wire all as specified and directed by Engineer in charge. (Note:- (i) Two runs of cables & continuous earth wire in new PVC casing and caping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 6.0 Sqmm, 1100 volts grade, drawn through and including New suitable size steel conduit including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 6.0 sqmm, 1100 Volts grade, ISI marked, as earth contuinity wire all as specified and directed by Engineer in charge. (Note:- (i) Two runs of cables & continuous earth wire in new PVC casing and caping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including PVC casing caping including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 4.0 sqmm, 1100 Volts grade, ISI marked, as earth contuinity wire all as specified and directed by Engineer in charge. (Note:- (i) Two runs of cables & continuous earth wire in new PVC casing and caping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including PVC conduit including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 4.0 sqmm, 1100 Volts grade, ISI marked, as earth contuinity wire all as specified and directed by Engineer in charge. (Note:- (i) Two runs of cables & continuous earth wire in new PVC casing and caping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 6.0 Sqmm, 1100 volts grade, drawn through and including PVC conduit including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 6.0 sqmm, 1100 Volts grade, ISI marked, as earth contuinity wire all as specified and directed by Engineer in charge. (Note:- (i) Two runs of cables & continuous earth wire in new PVC casing and caping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material and labour for Sub main wiring at any height and surface with and including four single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including New suitable size PVC conduit including connected accessories and two single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 4.0 sqmm, 1100 Volts grade, ISI marked, as earth contuinity wire all as specified and directed by Engineer in charge. Note:- (i) four runs of cables & continuous earth wire in new PVC casing and caping / PVC non metallic conduit will be measured as one length of sub main wiring.
Material and labour for Sub main wiring at any height and surface with and including four single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 6.0 Sqmm, 1100 volts grade, drawn through and including New suitable size PVC conduit including connected accessories and two single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 6.0 sqmm, 1100 Volts grade, ISI marked, as earth contuinity wire all as specified and directed by Engineer in charge.Note:- (i) Four runs of cables & continuous earth wire in new PVC casing and caping / PVC non metallic conduit will be measured as one length of sub main wiring.
Material and labour Sub main wiring at any height including using two single core PVC insulated copper conductor cable (FRLSH) of size 1.5 sqmm 1100 volt gradeand drawn through existing steel conduit/ PVC conduit including 1.5 sqmm. PVC multi stranded copper conductor cable (FRLSH) in green colour for continuous earthing all as specified and directed. Note - (a). Two runs of 1.5 Sqmm cable and one run of earth continuity wire shall be measured as one length.
Material and labour Sub main wiring at any height including using two single core PVC insulated copper conductor cable (FRLSH) of size 2.5 sqmm 1100 volt grade drawn through existing Steel/ PVC conduit including 2.5 sqmm. PVC multi stranded copper conductor cable (FRLSH) in green colour for continuous earthing all as specified and directed. Note - (a). Two runs of 2.5 Sqmm cable and one run of earth continuity wire shall be measured as one length.
Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, ISI marked, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through existing PVC/ steel conduit including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, ISI marked, FRLSH type, 4.0 sqmm, 1100 Volts grade, ISI marked, as earth contuinity wire all as specified and directed by Engineer in charge. (Note:- (i) Two runs of cables & continuous earth wire in new PVC casing and caping / PVC non metallic conduit will be measured as one length of sub main wiring).
Material and Labour for Sub main wiring at any height with four single core PVC insulated copper conductor cable (FRLSH) of size 6 sqmm 1100 volt grade drawn through Existing Steel / PVC conduit including two single core 6.0 sqmm PVC multi stranded copper conductor cable (FRLSH) in green colour for continuous earthing all as specified and directed. Note - (a). Four runs of 6 Sqmm wiring cable and two runs of earth continuity wire shall be measured as one length.
M & L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending colt or hot, drilling holes for bolts, at any height, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint for mounting Air Circulator / Exhaust Fan / Ceiling Fan/highbay fittings etc for fixing arrangements complete.
Disconnecting and taking down old existing damaged metallic rigid steel conduit of any size and any type from any height with all fittings complete.
Supply & fixing hot galvanised rigid steel conduit 25 mm dia, light grade, at any height with and incld. of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks, screws, clips, plugs, clamps etc. for securing cables, battens, conduits etc. to walls, steel joists etc. complete to be fixed on wall/ceiling/MS angles all as directed by Engr-in-Charge. Make - Jindal/Kalinga/ BEC.
Supply & fixing hot galvanised rigid steel conduit 20 mm dia, light grade, at any height with and incld. of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks, screws, clips, plugs, clamps etc. for securing cables, battens, conduits etc. to walls, steel joists etc. complete to be fixed on wall/ceiling/MS angles all as directed by Engr-in-Charge. Make - Jindal/Kalinga/ BEC.
Dismantling and Taking down unserviceable existing light fittings 1X 40 Watt / 2X 40 Watt of any size and capacity from any location/height after disconnecting of electrical connection complete including all connected accessories all as directed by Engr-in-Charge.
Supplying, fixing, connecting up to existing/new ceiling rose and testing surface mounting LED Tube Light Batten Fitting having extruded CRCA housing (heat sink) provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver suitable for 1x20 Watt 4 feet white colour tube lamp including connecting with 23/0.0076 copper conductor flexible twisted two core cable with all accessories (mounting SS clips) and fixing arrangement on wall / steel trusses / false ceiling with 2 Nos. 19 mm dia rigid stove enamelled black steel conduit with bell mouth threaded sockets complete all as specified & directed including dismantling of old fittings. Make Polycab/Jaguar/crompton Greaves or equivalent.
Supplying, fixing, connecting in at any height up to existing/new ceiling rose and testing LED luminarie made up of precoated CRCA housing provided with cum reflector finished in white powder coating, completely prewired with accessories up to terminal block suiatble for 2x20 W LED tube 4' long including 02 Nos.20 W LED tubes with 23/0.0076 copper conductor flexible twisted two core cable and fixing arrangement on steel trusses / false ceiling/ ceiling suspended by 2 nos. Ø19/20 mm rigid stove enamelled black steel conduit with bell mouth threaded sockets or with chains complete including dismantling of old fittings all as specified & directed. Note for item No 43 and 44 -1 ; Stove enamelled black steel conduit or casing only will be measured and paid under relevant items of this schedule. 2 ; Quoted rate is deemed to be inclusive of conduit fittings and bell mouthed threaded sockets.complete all as specified & directed. 3 ; Quoted rate is deemed to be inclusive any misc materials required for fixing new luminaries. Make Polycab/Jaguar/crompton Greaves or equivalent.
Supplying, fixing, connecting in at any height up to existing/new ceiling rose and testing LED batten with 20 W LED light source in integral module with polycarbonate/Acrylic diffuser more than 85%efficiency of light with LED lamp efficay as 100 Lum/W THD ≤15% with operating voltage range 100-300V, driver efficency >85%, surge voltage withstand 2.5 KV , power factor ≥0.9, and connecting with 23/0.0076 copper conductor flexible twisted three/ two core cable fittings conection complete all as specified & directed all Make Polycab/Bajaj /Phillips. NOTE - Quoted rate is deemed to be inclusive of any misc materials required for fixing new luminaries. Make Polycab/Jaguar/crompton Greaves or equivalent.
dismantling and taking down Highbay fittings 250/400W HPMV/MH/SV from a height upto 15 meters, replacing burnt/worn out accessories like holder, lamps, wires, ignitor, ballast, etc. complete at site.
Supply and fixing at 12 to 15 mtr height - 150W Industrial LED Highbay luminaire with >120 Lm/Watt ,Powder coated PDC Aluminium body & PC Optical Lenses. complete all accessories having IP 66 degree of protection, power factor >0.95,THD<10%,Internal Surge Protection-5KV & External Surge Protection-10KV,LED Source including connection with and including 1.5 sqmm three core cable from connector or ceiling rose to light fitting complete all as specified and directed by Engineer-in-Charge. Make Polycab/Jaguar/crompton Greaves or equivalent NOTE :- The quoted rates are deemed to be included the cost of Nut-bolts washars or clamps required to be replaced if old one are found unserviciable or of diferant size/shape for completion of work.
Disconnecting and taking down old switch fuse type distribution Box with MCB/fuse grip TPN/SPN DB 2 Way to 12 Way old type DB including taking out all cable connections of any description and in any position and making good the disturbed surface of walls, to match with the existing surfaces complete all as specified and directed by Engineer in charge.
Supply, fixing, connecting & testing of VTPN MCCB DBs 12 way suitable for MCCB as incomer, 415 volts IP 43 protection,including MCCB 160A 36 KA, with steel door having copper bus bars suitable for 200 Amps rating per phase and separate neutral, door earthing including taking down old DBs and making good the surface.Make - Legrand/ABB/L&T
Supply, fixing, connecting & testing of VTPN MCCB DBs 8 way suitable for MCCB as incomer, 415 volts IP 43 protection,including MCCB 160A 36 KA, with steel door having copper bus bars suitable for 200 Amps rating per phase and separate neutral, door earthing including taking down old DBs and making good the surface.Make - Legrand/ABB/L&T
Supply, fixing, connecting & testing of VTPN MCCB DBs 4 way suitable for MCCB as incomer, 415 volts IP 43 protection,including MCCB 160A 36 KA, with steel door having copper bus bars suitable for 200 Amps rating per phase and separate neutral, door earthing including taking down old DBs and making good the surface.Make - Legrand/ABB/L&T
Supply, fixing, connecting & testing of SPN DBs suitable for single pole and neutral, 12 way, 240 volts IP 43 protection, with steel door having copper bus bars suitable for 100 Amps rating per phase and separate neutral, door earthing including taking down old DBs and making good the surface.Make - Legrand/ABB/L&T
Supply, fixing, connecting & testing of SPN DBs suitable for single pole and neutral, 8 way, 240 volts IP 43 protection, with steel door having copper bus bars suitable for 100 Amps rating per phase and separate neutral, door earthing including taking down old DBs and making good the surface.Make - Legrand/ABB/L&T
Supplying & fixing in replacement MCB 6 to 32 Amps, single pole, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand/ABB/L&T
Supplying & fixing in replacement MCB 6 to 32 Amps, single pole and neutral, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand/ABB/L&T
Supplying & fixing in replacement MCB 6 to 32 Amps, triple pole, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand/ABB/L&T
Supplying & fixing in replacement MCB 40 to 63 Amps, triple pole, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand/ABB/L&T
Supplying & fixing in replacement MCCB 63 Amps, four pole, Icu=25 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand cat no. 420053 or equivalent
Supplying & fixing in replacement MCCB 100 Amps, four pole, Icu=36 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand cat no. 420093 or equivalent
Supplying & fixing in replacement MCCB 125 Amps, four pole, Icu=36 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, biconnect lower terminals, IP 20 protected terminals, sliding shutters complete all as specified and directed. Make - Legrand cat no. 420096 or equivalent
M&L for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm thick burried directly in ground, earth pit not less than 2.25 meters deep below ground level with top edge of the plate not less than 1.5mtr below GL connected to and including 32x6 mm GI strip upto 7.5 m long by means of GI bolts, nuts, check nuts & washers and connected to earthing test point & earth dolly all as shown in electrical plate No 3 of SSR part I- (2009), earth lead protected with and including 40 mm bore GI pipe light grade and 20 mm bore medium grade watering pipe and testing on completion including excavation & earth work in any type of strata , PCC (1:3:6) type C-I chamber, precast slab 50mm thick in cement concrete (1:2:4) type B1 (reinforced with welded steel wire fabric of XPM, weight not less than 4 Kg /Sqm) with cast iron frame ,funnel with water pipe , wire mesh and lugs etc complete all as specified and directed by engr-in-charge.
S&F earth continuity conductor or main earthing lead of size 32x6 mm GI strip fixed to wall drawn in conduit/pipe or any other indicated situation for loop earthing etc. incl removal of old as required all as specified and directed
Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release four pole 25 KA 63 Amps Make Legrand Cat No 420053 /L&T /ABB with one way metal inclosure Cat No 5078 01 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed.
Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release four pole 25 KA 100 Amps Make Legrand Cat No 420055 /L&T /ABB with one way metal inclosure Cat No 5078 01 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed.
Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release four pole 25 KA 160 Amps Make Legrand Cat No 420057 /L&T /ABB with one way metal inclosure Cat No 5078 01 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed.
Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix Industrial plug and socket board TP 32 Amps including plug top and MCB "C" curve 10 KA 32 Amps Make Legrand Cat No 5078 18 and 4086 58 /L&T /ABB including making good the disturbed suface of wall including material complate all as specifide and directed.
Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix one way metal inclosure Cat No 5077 93 /L&T/ and MCB "C" curve TPN 10 KA 32Amps Make Legrand Cat No 4086 80 /L&Tincluding making good the disturbed suface of wall including material complate all as specifide and directed.
Supply and fixing New LED Flood Light Fitting 100 watt energy efficient >100 lumen per watt with poweder quoted Aluminium body & toughened glass visor all as per Make POLYCAB cat part No PCGLF T1 01 100 or equivalent in M/S Crompton Greaves//Bajaj/Philips and including PVC insulated FRLSH multistranded copper conductor cable 1.5 Sqmm - 03 core upto 2 RM complete all as specified and directed by Engineer-in-Charge.
Supply and fixing New LED Flood Light Fitting 120 watt energy efficient >100 lumen per watt with poweder quoted Aluminium body & toughened glass visor all as per Make POLYCAB cat part No PCGLF T1 01 120 or equivalent in M/S Crompton Greaves//Bajaj/Philips and including PVC insulated FRLSH multistranded copper conductor cable 1.5 Sqmm - 03 core upto 2 RM complete all as specified and directed by Engineer-in-Charge.
M/S. Niksun Electro-Infra Private Limited
AN-ICON Engineering Technologies And Infrastructure Developments Pvt. Ltd
Sachin Electricals
Om Construction
M/S. OM ENTERPRISES
Adinath Technical Services
UNIQUE INDIA CONSTRUCTIONS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .