| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 LAccepted-AOC | L1 | Accepted-AOC 60 percentage Qty of works | |
| 2 | L2₹2.3 L−₹1.1 L (33.3%)Accepted-AOC | L2 | Accepted-AOC 40 percentage Qty of works |
| Sl No | Description | Qty | Unit | MEERA ELECTRICALS L2 | M/S PRACHI ELECTRICALS L1 |
|---|---|---|---|---|---|
| 1.00 | Attending to break down calls, physical inspection of Transformer, Substation accessories, overhead lines, feeder panels, meter box etc. to find out the faults and taking corrective measures for restoration of power supply including rectification of minor faults such as replacement of pin/Disc/post insulators/LAs, jumper wires, LT side cable, LT side switch gears, meter boxes/TPN boxes and generation of Reports thereof as per the prescribed format etc. as required. (Materials are not in the scope of this item) (BA Head quarter shall be considered as base station while determining the distance) | - | - | - | - |
| 1.10 | For sites distance up to and including 50 KMs | 1 | Job | 2,100 ₹2,100 Lowest | 2,123 ₹2,123 |
| 1.20 | For sites distance above 50 KM and up to and including 100 KMs | 2 | Job | 2,150 ₹4,300 Lowest | 2,720 ₹5,440 |
| 1.30 | For sites distance above 100 KM and up to and including 150 KMs | 2 | Job | 2,900 ₹5,800 | 2,800 ₹5,600 Lowest |
| 1.40 | For sites distance above 150 KM and up to and including 200 KMs | 1 | Job | 3,000 ₹3,000 | 2,900 ₹2,900 Lowest |
| 2.00 | Liaison with different units of the supply authority i.e. Division/Sub Division/Section offices/MRT office/E & MR office and field staff etc. for obtaining shut down of 11KV line/LT Line, breaking of meter seal if required to carry out the repairing and maintenance works of the Sub Station and re-energization, testing etc. as required. | - | - | - | - |
| 2.10 | To carry out minor repairing works such as fixing/post insulators/LAs, jumper wires, LT side cable, LT side switch gears, etc. | 2 | Job | 2,300 ₹4,600 Lowest | 2,889 ₹5,778 |
| 2.20 | To carry out major repairing works such as rewinding/ replacement/ repairing & overhauling of Transformer, AB switch, DO fuse unit, replacement of HT cable and its end terminations or any other major repairing works of the DP structure & associated overhead lines. | 2 | Job | 4,300 ₹8,600 Lowest | 4,321 ₹8,642 |
| 3.00 | Thorough servicing of AB Switch, adjustment of bearings, male/female contacts, lubricating of moving items i/c replacement of minor defective parts like nuts, bolts, clamps, wire braided copper strips and checking the functional operation, etc. as required. | 2 | Job | 2,200 ₹4,400 Lowest | 2,315 ₹4,630 |
| 4.00 | Replacement of the following defective spare parts of the transformer substation by new one i/c fitting, connection etc. as reqd. | - | - | - | - |
Tender Value
₹5.8 L
EMD Value
₹11,594
Closing Date
15 Jul 2025, 3:00 pmClosed
Executive Engineer (E), BSNL, Bhubaneswar
Door Sanchar Bhawan, Unit-IX, Bhubaneswar-751022
S.H- Zone-2-Area under the Jurisdiction of DGM, Rural
2025_BSNL_240655_1
NIT No- 04/BSNL-EDB/ET/2025-26
Open Tender
Electrical Works
Item Rate
180 days
Bhubaneswar BA Rural
3 documents required · 3 mandatory
₹590
A O (Cash), BSNL, O/o GMTD, Bhubaneswar.
₹11,594
Yes
25 Sept 2025
8 Jul 2025
16 Jul 2025
8 Jul 2025
15 Jul 2025
8 Jul 2025
8 Jul 2025 - 12 Jul 2025
Amount
Attending to break down calls, physical inspection of Transformer, Substation accessories, overhead lines, feeder panels, meter box etc. to find out the faults and taking corrective measures for restoration of power supply including rectification of minor faults such as replacement of pin/Disc/post insulators/LAs, jumper wires, LT side cable, LT side switch gears, meter boxes/TPN boxes and generation of Reports thereof as per the prescribed format etc. as required. (Materials are not in the scope of this item) (BA Head quarter shall be considered as base station while determining the distance)
For sites distance up to and including 50 KMs
For sites distance above 50 KM and up to and including 100 KMs
For sites distance above 100 KM and up to and including 150 KMs
For sites distance above 150 KM and up to and including 200 KMs
Liaison with different units of the supply authority i.e. Division/Sub Division/Section offices/MRT office/E & MR office and field staff etc. for obtaining shut down of 11KV line/LT Line, breaking of meter seal if required to carry out the repairing and maintenance works of the Sub Station and re-energization, testing etc. as required.
To carry out minor repairing works such as fixing/post insulators/LAs, jumper wires, LT side cable, LT side switch gears, etc.
To carry out major repairing works such as rewinding/ replacement/ repairing & overhauling of Transformer, AB switch, DO fuse unit, replacement of HT cable and its end terminations or any other major repairing works of the DP structure & associated overhead lines.
Thorough servicing of AB Switch, adjustment of bearings, male/female contacts, lubricating of moving items i/c replacement of minor defective parts like nuts, bolts, clamps, wire braided copper strips and checking the functional operation, etc. as required.
Replacement of the following defective spare parts of the transformer substation by new one i/c fitting, connection etc. as reqd.
Male contact and Female contacts made of hard drawn copper for 200 Amps air break switch with wire braided strip etc. comprising of 3nos per set.
Rotor mechanism for 200 Amps air break switch.
Square/round bar for AB switch (Horizontal unit)
Porcelain Post Insulator with minimum creepage distance 25mm per KV minimum tensile strength 15KN for 200Amps 11KV AB switch/ HG fuse unit/DO fuse units with all accessories.
Polymer Post Insulator with minimum creepage distance 320mm and minimum tensile strength 5KN for 200Amps 11KV AB switch/ HG fuse unit/DO fuse (Polymer type) with all accessories.
Operating Handle made of 25/32mm Medium class GI pipe with wire braided copper strip
Heavy duty operating pipe for air break switch i/c fabrication etc. as required.
Replacement of damaged breather for 25 KVA 11KV/0.433KV transformer by a new one with dry silica gel etc. as required.
Replacement of faulty/damaged pin insulators by new one of the following types for 11KV HT line poles and DP structure etc. complete as required.
Porcelain Pin insulator- 11KV 5KN having minimum creepage distance 320mm with large steel head G.I. pin, nuts, washers etc. as per specifications.
Polymeric composite Pin Insulator- 11 kV 24mm dia, 5KN having minimum creepage distance 320mm with all accessories as per specifications.
Replacement of faulty / damaged disc insulators by new one of following types for 11KV HT line poles and DP structure etc. complete as required.
Porcelain Disc insulator- 11KV, 45KN Ball and Socket type, 255mm dia with galvanized all hardware fittings etc. complete as required as per specifications.
Polymeric Disc insulator- 11KV, 70KN Ball and Socket type, minimum creepage distance 320mm with all hardware fittings etc. complete as required as per specifications.
Replacement of faulty Lightening arrestors by new ones of following types with galvanized clamping arrangement, G.I. bolts, nuts, washers etc. as required (comprising 3nos per set).
Porcelain Lightening Arrester- Distribution type, 11KV/12KV (Nominal System Voltage / Highest System Voltage), Rated voltage 9KV rms, Nominal discharge current rating (8/20 micro sec wave) - 5KA with mounting bracket, nuts and bolts etc. complete as required as per specifications.
Polymeric Lightening Arrester- Metal Oxide Gapless Cage type with Polymeric housing Distribution type, 11KV/12KV (Nominal System Voltage / Highest System Voltage), Rated voltage 11KV rms, Maximum Continuous Operating Voltage (M.C.O.V)-9.0KV rms, Nominal discharge current rating (8/20 micro sec wave) - 5KA with mounting bracket, stainless steel nuts and bolts etc. complete as required as per specifications.
Replacement of damaged and unserviceable AB switch by new one of following type, 11 KV, off load, single break, triple pole, horizontal rotating type, air break switch having 2 nos. post insulator per phase complete with galvanized channel iron base, arcing horns, 32 mm dia. 6mtr / 7mtr. long GI pipe, tinned copper wire braided flexible earthing wire & operating handle with locking arrangement etc. complete as required.
Having Porcelain post insulator, 200A rated outdoor type AB switch, service voltage /rated voltage -11KV rms/12KV rms, 50 Hz, rated short time current 16KA for 1 sec. as per specifications.
Having Polymeric post insulator, 200A rated outdoor type AB switch, service voltage /rated voltage -11KV rms/12KV rms, 50 Hz, rated short time current 16KA for 1 sec. as per specifications.
Dismantling of faulty and damaged AB switch from the DP structure i/c cutting the base channels/bolts etc. complete as required. (The dismantled faulty & damaged AB switch may be retained by the agency)
Replacement of damaged and unserviceable DO/HG fuse units by new one of 3 phase, 11 KV outdoor type Horn Gap Fuse unit having 2 nos. 11 KV post type insulator (5KN) per phase complete with channel, cu-wire etc. as required (one set comprising 3 units) as per the following type.
Horn Gap Fuse unit with porcelain Insulators-continuous rated current 100A, 50Hz, Service voltage/Rated voltage- 11KV / 12KV rms, minimum creepage distance of insulators 320mm as per the specifications.
Horn Gap Fuse unit with polymer Insulators-continuous rated current 200A, 50Hz, Service voltage/Rated voltage- 11KV / 12KV rms, minimum creepage distance of insulators 320mm as per the specifications.
Dismantling of faulty and damaged DO Fuse / HG fuse unit set from the DP structure i/c cutting the base channels/bolts etc. complete as required. (The dismantled faulty & damaged DO/HG fuse units may be retained by the agency)
Supply & drawing of 55 sqmm. AAA conductor for overhead line and DP structures i/c binding with insulators etc. complete as required.
Replacement of faulty/burnt out HT cable by supply of new 3 core, 35sqmm HT XLPE insulated Cable of 6.6 KV (UE)/11KV (E), Stranded compact circular aluminium conductor, conductor screen with extruded semiconducting compound, XLPE insulated, insulation screening with extruded semi conducting compound in combination with copper tape (0.3 KA for 1 sec), cores laid up, inner sheath of PVC tape, galvanized flat steel strip armoured and overall PVC sheathed confirming to IS 7098/PART-II-1985 with latest amendments. (Make- Polycab/Havells/Equivalent)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11KV grade of size up 120sqmm in the following manner:
Direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
In the existing RCC/ HUME/ METAL pipe as required.
In the existing masonry open duct as required.
On air i/c supply & binding with 1no 55sqmm AAA Conductor.
Replacement of faulty 11KV outdoor type cable end terminations by new one of heat shrinkable type complete with all accessories including lugs suitable for 3 core, 35 sqmm, XLPE aluminium conductor cable of 11 KV grade as required. (Make-Raychem/3M)
Replacement of faulty/burnt out straight through cable joints by new one of outdoor type heat shrinkable type complete with all accessories including lugs suitable for 3 core, 35 sqmm, XLPE aluminium conductor cable of 11 KV grade as required. (Make-Raychem/3M)
Rewiring of the DP structure of Transformer Sub Station with 50sqmm insulated Al.conductor stranded cable with al. Lugs/sockets, binding with post insulators etc. complete as required.
Replacement of faulty/burnt out cables by new one of following sizes PVC insulated & PVC sheathed Aluminium conductor armoured cable 650/1100 V. grade confirming to IS: 7098 (Part-1) 1988 i/c transportation to respective sites etc. as required.
4 core 16sqmm
4 core 25sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size Up to 35sqmm direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size Up to 35sqmm in the existing RCC/ HUME/ METAL pipe as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size Up to 35sqmm in the existing Duct/Air as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size Up to 35 sq. mm (clamped with 1mm thick saddle) on wall surface as required.
Replacement of damaged MV cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4 X 16 sq. mm (28mm)
4 X 25 sq. mm (28mm)
Replacement of the defective parts / components by new ones of following sizes & ratings aluminium/copper sockets/lugs for PVC sheathed / XLPE aluminium/copper conductor cable of 1.1 KV grade i/c fixing/crimping etc. as required.
16/25sqmm Al socket.
35sqmm Al socket.
55sqmm Al socket.
Replacement of faulty MCBs/SDFUs/Change over switches by new ones of following ratings after dismantling the old defective ones, fixing, connection & testing etc. as required.
63 Amps 415 volts TPN SDFU with Din type HRC fuses (open execution type). (Make: LK-FN63TPN/ FP-CE/ Equivalent of Siemens/Havells) .
63 Amps 415 volts TPN SDFU with Spacious Sheet Steel Enclosure, Terminal Shrouds on both sides and Phase Barriers included, Separate cable gland box not required, Door interlock & padlock facility, Suitable for Cylindrical/DIN fuse-link Conforms to IEC 60947-3, IS/IEC 60947-3 with HRC fuse links. (Make: LK-FN63TPN/ FP-CE/ Equivalent of Siemens/Havells).
100 Amps 415 volts TPN SDFU with Spacious Sheet Steel Enclosure, Terminal Shrouds on both sides and Phase Barriers included, Separate cable gland box not required, Door interlock & padlock facility, Suitable for Cylindrical/DIN fuse-link Conforms to IEC 60947-3, IS/IEC 60947-3 with HRC fuse links. (Make: LK-FN100TPN/ FP/ Equivalent of Siemens/Havells).
63Amp 4-pole on load change over switch open execution type with extended handle (Make: LK/HPL Socomec /Havells) .
63Amp 4-pole on load change over switch, front handle operated type with Spacious Sheet Steel Enclosure, Terminal Shrouds on both sides and Phase Barriers included, Separate cable gland box not required, Suitable for horizontal as well as vertical mounting etc. Conforms to IEC 60947-3 , IS/IEC 60947-3 (Make: LK, model CO10630OSOO / Equivalent model of HPL Socomec /Havells / Siemens) .
63Amps 415 volts 4 pole MCB (Class-C) (Make- Legrand/Siemens/Havells/LK)
6-32A SP MCB (Class-C). (Make- Legrand/Siemens/Havells/LK)
100 Amp porcelain fuse unit with base & carrier. (Make- Havells model-IHKKDN4100 / Equivalent of Standard/Anchor)
Dismantling the following ratings faulty transformer from the existing D.P. structure/Plinth & installation of standby/repaired transformer i/c testing and commissioning, recording the required parameters etc. by qualified staff, arranging required tools & plant with proper precautionary measures etc. as required.
25 KVA, 11KV/0.433KV, 50 Hz Aluminium wound oil cooled Transformer
63 KVA, 11KV/0.433KV, 50 Hz Aluminium wound oil cooled Transformer
Repairing of 25/63 KVA Aluminium/copper wounded transformer at factory/workshop by dismantling the faulty transformer, re-insulating the windings, heating, reassembling i/c replacement of gaskets, nuts & bolts, washers, carry out factory tests etc. complete as required. (Rewinding of Transformer is not in the scope of this item)
Repairing of 25 /63 KVA Aluminium/ copper wounded transformer at site i/c opening top cover, checking the bush, inter connections wires/strips from bushings to transformer windings, tightening the connections, etc. as required. (Rewinding of Transformer is not in the scope of this item)
Rewinding of the HT windings of the following ratings Oil immersed Distribution class Transformer with superior grade and suitable size Double paper covered Transformer winding conductor , providing re-insulation of LT winding etc. including dismantling the transformer parts i.e. conservator tank, terminal boxes, bushings, removing the core and windings from the tank, draining of transformer oil, cleaning of tank, reassembling the core & windings and all the aforesaid parts after rewinding/repairing, replacement of gaskets, worn out nuts, bolts and washers/cork washers etc, heating in heat chamber, carry out factory tests and submission of test reports etc. complete as required. (The dismantled aluminium winding and other materials can be retained by the agency and credit for the same to be given in the quoted rate of this item)
25 KVA, 11KV/0.433KV, 50 Hz Aluminium wound oil cooled Transformer
63 KVA, 11KV/0.433KV, 50 Hz Aluminium wound oil cooled Transformer
Supplying and pouring of transformer oil (IS:325) of suitable make & grade for topping up/replacement of old deteriorated oil etc. complete as required.
Filtration and de-hydration of existing Transformer oil at factory / work shop/ at site (In case of rewinding/repairing of Transformer at factory / workshop/site) as per the following i/c testing of BDV and submission of oil testing report etc. as required.
At Transformer repairing Workshop / Factory
At installation site (TE/BTS/Bldg) of Transformer i/c arrangement of oil filtration machine at site etc. complete as required.
Replacement of the following defective spare parts of the transformer by new one i/c fitting, connection etc. as reqd.
HV Bushings
LV Bushings
Painting of the transformer body with primer & two coats of weather proof synthetic enamel paints after scrapping the rust etc complete as reqd.
Providing 25 KVA/63 KVA 11KV/0.433 KV Distribution class star rated Transformer on hiring basis as a stop gap arrangement etc. as required. (BSNL will not be held responsible for occurrence of any faults in the hired Transformer while working at site or any damage or loss occurred to the said Transformer during transportation, loading, unloading and negligence of the agency etc.). (Commencement date shall be the date of energization and commissioning at site)
Making arrangements for inspection and testing of the re-winded transformer by the designated inspector of supply company at factory / workshop and obtaining test certificates and clearance for re-installation and energization of the said transformer etc. complete as required.
Transportation of spare /new / repaired / standby 25/63 KVA transformer from BSNL office /factory /workshop to respective sites and faulty Transformer from sites to back by using suitable transportation medium including loading and unloading at both ends etc. complete as required. (The rate should be inclusive of toll gate fee/charges wherever applicable, nothing extra will be paid. Distance will be on shortest route only).
Distance up to and including 50 KMs (Charges for Up and Down)
Distance above 50 KM and up to and including 100 KMs (Charges for Up and Down)
Distance above 100 KM and up to and including 150 KMs (Charges for Up and Down)
Distance above 150 KM and up to and including 200 KMs (Charges for Up and Down)
MEERA ELECTRICALS (BID ID -872097)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .