Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.8 LAccepted-AOC 20 JAIN BAZAR JAMMU 180003 J K | JAMMU | JAMMU | J K | 180003 | ₹37.8 L Quoted ₹38.9 L | L1 | Accepted-AOC L1 |
| 2 | L2₹39.5 L+₹63,078 (1.62%)Rejected-Finance RAM SHIV COLONY GALI NO 2 NAIKA CHATNAG ROAD JHUNSI PRAYAGRAJ UP 211019 | PRAYAGRAJ | UTTAR PRADESH | 211019 | ₹39.5 L+₹63,078 (1.62%) | L2 | Rejected-Finance OTHER THAN L1 |
| 3 | L3₹53.6 L+₹14.7 L (37.7%)Rejected-Finance R O WARD NO 08 H NO 108 DHAR ROAD UDHAMPUR TEHSIL DISTT UDHAMPUR 182101 | UDHAMPUR | UDHAMPUR | JAMMU KASHMIR | 182101 | ₹53.6 L+₹14.7 L (37.7%) | L3 | Rejected-Finance OTHER THAN L1 |
Tender Value
₹50.0 L
EMD Value
₹99,980
Closing Date
14 Jun 2025, 6:00 pmClosed
GE (Utilities) Udhampur
GE (Utilities) Udhampur, PO-Garhi, Pin-182121
Repair/Maintenance of DG sets of various capacities and allied system and Repair/Maintenance of Highmast lights, Streetlights and other connected items at water supply installations under GE (Utilities) Udhampur
2025_MES_708688_1
GE/U-28/2025-26
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (Utilities) Udhampur
As per NIT
8 documents required · 8 mandatory
₹500
GE (Utilities) Udhampur
₹99,980
18 Jul 2025
17 May 2025
16 Jun 2025
17 May 2025
14 Jun 2025
31 May 2025
Amount
Servicing of diesel engine generating set of capacity 500 KVA/600KVA of any make, including the following works are as under: - (a) Servicing of Engine (i) Re-greasing all grease points. (ii) Tighten the nuts, bolts of pipe lines of fuel oil, lubricating oil, water and check for leakages and examine the all main connections. (iii) Check water/coolant level in radiator. (iv) Check crank case oil level. (v) Clean/replaced lubrication oil filters. (vi) Clean/replaced air filters. (vii) Check that lubricating oil contains no water. Examine lubricating oil and renew if needed (viii) Check tappet clearance and all nuts for tightness. (ix) Wash felt pads of fuel filter. (x) Drain air receiver. (xi) Grease valve stems. (xii) Check all wiring, battery water level, gravity of battery, inspect all bushes and bush holder, cleaning of surface of commutators.
(b) Servicing of alternators (i) Check temp rise of bearings. (ii) Check bushes on exciter commutator and the alternator slip rings run without chattering or sparking. (iii) Check if bushes freely slide in holder and whether bush springs are in order. (iv) Check if oil rings are freely rotating in the bearings. (v) Check oil level in bearings. (vi) Wipe clean the alternator and exciter. (vii) Check all wiring and rectify any defect with new wiring. (viii) Surface and clean the commutator. (ix) Take insulation and earth test on alternator and exciter and if defective investigate cause and remedy. (x) Check joints, clamping and bolting in all the wiring including control panels and rectify any defects. (xi) Check greases in all roller and ball bearings and make up if inadequate. (xii) Check the degree of wear of commutator bushes and renew if necessary. (xiii) Tighten all nuts in the rotors of alternator and exciter. (xiv) Check air gaps between starters and rotors and clean off any projections on the rotor. (C) M&L for repairing of door of sound proof canopy of DG Sets by replacing of door hinges and any type of welding work for smooth functioning of all doors of DG Sets . Note for item No. 1 to 4 : Items to be replaced will be measured and paid separately, as supply only and labour for fixing deemed to be include as part of servicing.
All as per item No.1 here- in- before but 250 KVA to 320 KVA as per existing Make, Complete all as specified and directed by Engr-in-Charge.
All as per item No.1 here- in- before but 200 KVA as per existing Make. Complete all as specified and directed by Engr-in-Charge.
All as per item No.1 here- in- before but 62.5 KVA to 100 KVA as per existing Make, Complete all as specified and directed by Engr-in-Charge.
Supply & Fix fuel filter primary & secondary. (Set of Two) suitable of existing make & specification for 500/600 KVA DG set, complete all as specified and directed by Engr-in-Charge.
Supply & Fix fuel filter primary & secondary. (Set of Two) suitable of existing make & specification for 250 KVA to 320 KVA DG set, complete all as specified and directed by Engr-in-Charge.
Supply & Fix fuel filter primary & secondary. (Set of Two) suitable of existing make & specification for 200 KVA DG set complete all as specified and directed by Engr-in-Charge.
Supply & Fix fuel filter primary & secondary. (Set of Two) suitable of existing make & specification for 62.5 KVA to 100 KVA DG set complete all as specified and directed by Engr-in-Charge.
Supply & Fix Oil filter element suitable (in replacement) of existing make & specification for 500/600 KVA DG set, complete all as specified and directed by Engr-in-Charge.
Supply & Fix Oil filter element suitable (in replacement)of existing make & specification for 250KVA to 320 KVA DG set, complete all as specified and directed by Engr-in-Charge.
Supply & Fix oil filter element suitable (in replacement)of existing make & specification for 200 KVA DG set, complete all as specified and directed by Engr-in-Change.
Supply & Fix oil filter element suitable (in replacement)of existing make & specification for 62.5 KVA to 100 KVA DG set, Complete all as specified and directed by Engr-in-Charge.
Supply & Fix air cleaner filter element including outer and inner element suitable (in replacement) of existing make & specification for 500/600 KVA set, complete all as specified and directed by Engr-in-Charge.
Supply & Fix air cleaner filter including outer and inner element suitable of existing make & specification for 250 KVA to 320 KVA set, complete all as specified and directed by Engr-in-Charge.
Supply & Fix air cleaner filter including outer and inner element suitable of existing make & specification for 200 KVA set, complete all as specified and directed by Engr-in-Charge.
Supply & Fix air cleaner filter including outer and inner element suitable (in replacement)of existing make & specification for 62.5 KVA to 100 KVA set, complete all as specified and directed by Engr-in-Charge.
Supply & Fix ‘V' belt for dynamo A-49/50 or suitable of existing make & specification for 62.5 KVA to 600 KVA set, complete all as specified and directed by Engr-in-Chrge.
Supply & Fix flexible pipe for fuel pump to PT pump with banjo, banjo washer and nut, bolts suitable of existing make & specification for 500/600 KVA set,Complete all as specified and directed by Engr-in-Charge.
Supply & Fix flexible pipe for fuel pump to PT pump with banjo, banjo washer and nut, bolts suitable of existing make & specification for 250 to 320 KVA set, Complete all as specified and directed by Engr-in-Charge.
Supply & Fix flexible pipe for fuel pump to PT pump with banjo, banjo washer and nut, bolts suitable of existing make & specification for 62.5 to 100 KVA set, complete all as specified and directed by Engr-in-Charge.
Repair/replacement and calibration of FIP of capacity 500/600 KVA DG Sets including replacement of plunger, manifold washer, etc all as required other minor items and testing after re-fixing on engine and setting the rated RPM, complete all as specified and directed by Engr-in-Charge.
All as per item No.21 here- in- before but 250 KVA to 320 KVA as per existing Make.
All as per item No.21 here- in- before but 200 KVA as per existing Make.
All as per item No.21 here- in- before but 62.5 KVA to100 KVA as per existing Make.
Dismantling and taking out of self-starter from mounting and to carryout complete servicing/overhauling of the same with carbon brush, armature coil, field coil, solenoid switch, bush and pinion and other related components of DG set capacity 500/600 KVA suitable of existing make & specification.
All as per item No.25 here- in- before but 250 KVA to 320 KVA.
All as per item No.25 here- in- before but 200 KVA.
All as per item No.25 here- in- before but 62.5 KVA to100 KVA.
Repair/Replacement and callibration of injector assy including replacement injector cups barrel, nozzles,o rings screen filter and setting the oil pressure with suitable for 500/600 Kva DG sets as per existing Make, Complete all as specified and as directed by Engr-in-Charege.
All as per item No.29 here- in- before but 250 KVA to 320 KVA .
All as per item No.29 here- in- before but 200 KVA .
All as per item No.29 here- in- before but 62.5 KVA to100 KVA .
Repair/servicing and overhauling of unserviceable dynamo by dismantling the same from DG set after taking down the fan belt and pulley. Repair of the same with armature coil, carbon (1 set) field coil, clutch bearing etc and other related items and duly re-assembling all the dismantled items and refixing the same on mountings and testing complete of DG set capacity 500/600 KVA suitable of existing make & specification.
All as per item No.33 here- in- before but 250 KVA to 320 KVA.
All as per item No.33 here- in- before 200 KVA.
All as per item No.33 here- in- before but 62.5 KVA to100 KVA.
Supply & fix automatic voltage regulator, Diode forward and reverse rotating rectifier assembly complete including taking down unserviceable AVR of DG set capacity 500/600 KVA suitable of existing make & specification.
All as per item No.37 here- in- before but 250 KVA to 320 KVA.
All as per item No.37 here- in- before but 200 KVA.
All as per item No.37 here- in- before but 62.5 KVA to100 KVA.
Supply and fixing in repalcement of battery cable lead (copper) positive terminal size 35 Sqmm (198cm long) or as per sample, Complete all as specified and as per directed by Engr-in-Charge.
Supply and fixing in repalcement of battery cable lead (copper) -ve terminal size 35 Sqmm (198cm long) or as per sample, Complete all as specified and as per directed by Engr-in-Charge.
Supply and fixing in repalcement of inter connection battery cable lead (copper) with terminal size 35 sqmm (30cm long) or as per sample, Complete all as specified and as per directed by Engr-in-Charge.
Supply and top up Engine Oil SAE 20W/40 Make: HP/Indian oil/Castrol or its equivalent , Complete all as specified and as per directed by Engr-in-Charge.
Supply and top up Engine Oil SAE 15W/40 Make: HP/Indian oil/Castrol or its equivalent , Complete all as specified and as per directed by Engr-in-Charge.
Supply and top up DAFC 50% Make: HP/Indian oil/Castrol or its equivalent , Complete all as specified and as per directed by Engr-in-Charge.
Battery terminal +ve and -ve with bolt & nuts, complete all as specified and directed by Engr-in-Charge.
Fan belt A-44, A-42, A-41, A-40 or as existing size & make suitable for DG sets of capacity 62.5 KVA to 600 KVA, Complete all as specified and directed by Engr-in-Charge.
Material and labour in replacment of 180 AH 12 Volts batteries for DG sets 62.5 to 600 KVA DG sets, Complete all as specified and directed by Engr-in-Charge.
Repair and overhauling of Diesel Engine driven generating set 6 cylinder of cap 82.5 KVA installed at Sansar Chand Pump house complete with the following works and replacement of spare parts. (a) Disconnecting the electric connection of the alternator, decoupling from engine and disconnecting unsv/serviceable parts for repair/ replacement such as inlet/outlet manifold, turbocharger, FIP, air cleaner, fuel injectors, cylinder head, tappet cover, cylinder linner, piston assy, connecting rod assy, exhaust valve seat, insert valve seat, fuel pump, L.O. pump, oil pump, piston assy, crank shaft etc. at site and cleaning the reusable parts with Keroscene oil for reuse , Complete all as specified and as per directed by Engr-in-Charge. (b) Transportation of unserviceable parts such as cylinder block, cylinder head, oil pump , FIP, L.O. pump, oil pump, injector nozzles, crank shaft etc. obtain from the above DG sets at site i.e. MT Pump house Udhampur to Kirloskar company or Kirloskar authorised Work shop at Jammu for repair, rectification of defects and retransportation of repaired parts/assembled engine from workshop to installation complete.
(c) Computarised checking of cylinder block for its defects/ leakage in oil and rectification of the same by X ray welding or otherwise as per manufacturer's specification. (d) Grinding, polishing & facing of cylinder heads in and including replacement of seats and minor repair to cylinder head all as directed by Engr-in-Charge. (e) Re-assembling the Engine and alternator complete and connecting the alternator and coupling with engine complete after repair/ replacement of serviceable/unsv spare parts incl spray painting of DG Set of existing colors with testing and commissioning of DG set on full load upto desired satisfaction of Engr-in-Charge complete. Note:- (i) The major spare parts required for overhauling of engine shall be measured and paid separately under relevant items. (ii) Minor spare parts such as plain machined washer, set screw, joint, set bolt, O rings, washer, spring dowel, dowel pin, bolts, pins, nuts, banjo bolts, copper washer etc for proper functioning of DG sets deemed to be included in the item rate.
Supply of spare parts for 82.5 KVA DG sets as mentioned in item no 66 and replacement as under
Set Main bearing
Bearing connecting rod
Bushing connecting rod
Cylinder liner assy
Kit piston engine (Piston, piston pin, Piston ring)
Valve exhaust
Valve inlet
Valve guide stem
Inlet & exhaust valve seat
Gasket cylinder
Thrust washer
Push rod
water sealing
Baffle breather
Screen Breather
Bushing camshaft
Set of water hose
Set of fuel fleixible pipe , Manifold fuel pipe.
High pressure pipe ,Manifold fuel pipe.
Gasket kit (Upper and lower)
Main oil seal
Fuel filter
Oil filter
Air cleaner filter
Calbiration of injector assembly including replacement of injector cups, barrel,nozzles, O-rings screen filter and setting the oil pressure with testing suitable for 82.5 KVA DG Set as per existing make Kirloskar complete all as directed by Engr-in-Charge.
Repair and overhauling of Diesel Engine driven generating set 6 cylinder of cap 200 KVA installed at Jib water pump complete with the following works and replacement of spare parts. (a) Disconnecting the electric connection of the alternator, decoupling from engine and disconnecting unsv/serviceable parts for repair/ replacement such as inlet/outlet manifold, turbocharger, FIP, air cleaner, fuel injectors, cylinder head, tappet cover, cylinder linner, piston assy, connecting rod assy, exhaust valve seat, insert valve seat, fuel pump, L.O. pump, oil pump, piston assy, crank shaft etc. at site and cleaning the reusable parts with Keroscene oil for reuse all as specified and directed by Engr-in-charge. (b) Transportation of unserviceable parts such as cylinder block, cylinder head, oil pump , FIP, L.O. pump, oil pump, injector nozzles, crank shaft etc. obtain from the above DG sets at site i.e. Jib filter point Udhampur to Kirloskar company or Kirloskar authorised Work shop at Jammu for repair, rectification of defects and retransportation of repaired parts/assembled engine from workshop to installation complete.
(c) Computarised checking of cylinder block for its defects/ leakage in oil and rectification of the same by X ray welding or otherwise as per manufacturer's specification. (d) Grinding, polishing & facing of cylinder heads in and including replacement of seats and minor repair to cylinder head all as directed by Engr-in-Charge. (e) Re-assembling the Engine and alternator complete and connecting the alternator and coupling with engine complete after repair/ replacement of serviceable/unsv spare parts incl spray painting of DG Set of existing colors with testing and commissioning of DG set on full load upto desired satisfaction of Engr-in-Charge complete. Note:- (i) The major spare parts required for overhauling of engine shall be measured and paid separately under relevant items. (ii) Minor spare parts such as plain machined washer, set screw, joint, set bolt, O rings, washer, spring dowel, dowel pin, bolts, pins, nuts, banjo bolts, copper washer etc for proper functioning of DG sets deemed to be included in the item rate.
Supply of spare parts for 200 KVA DG sets as mentioned in item no 52 and replacement as under
(a) Set Main bearing
(b) Bearing connecting rod
(c) Bushing connecting rod
(d) Cylinder liner assy
(e) Kit piston engine (Piston, piston pin, Piston ring)
(f) Valve exhaust
(g) Valve inlet
(h) Valve guide stem
(j) Inlet & exhaust valve seat
(k) Gasket cylinder
(l) Thrust washer
(m) Push rod
(n) water sealing
(o) Baffle breather
(p) Screen Breather
(q) Bushing camshaft
(r) Set of water hose
(s) Set of fuel fleixible pipe , Manifold fuel pipe.
(t) High pressure pipe ,Manifold fuel pipe.
(u) Gasket kit (Upper and lower)
(v) Main oil seal
(w) Fuel filter
(x) Oil filter
(y) Air cleaner filter
Calbiration of injector assembly including replacement of injector cups, barrel,nozzles, O-rings screen filter and setting the oil pressure with testing suitable for 200 KVA DG Set as per existing make Kirloskar, Complete all as specified and as per directed by Engr-in-Charge.
Excavation in trenches for Taking out / Laying HT/LT U/G Cable in any type of hard/ dense soil not exceeding 1.5 m wide and not exceeding 1.5m in depth and getting out , Complete all as specified and as per directed by Engr-in-Charge.
M&L for dry sand cushioning to underground cable provided with layer of 8cms thick before laying the cable and 15cms thick after laying and stretching the cable and punned to 18 cm thick , Complete all as specified and as per directed by Engr-in-Charge. Note: Only punned thickness shall be measured for payment purpose.
Supply and lay PCC cable cover class LV type 2 flat size 250 mm x 150mm x 40mm, complete all as specified and directed by Engr-in-Charge.
Returning, filling, levelling, spreading, watering and well ramming in layers not exc. 25 cm thick, complete all as specified and directed by Engr-in-Charge.
Removing surplus soil not exc 50m and depositing where directed at a level not exc 1.5m above the starting point, complete all as specified and directed by Engr-in-Charge.
Supply, laying, jointing & testing XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 10 sqmm 2 core as laid in trenches, passing through pipes, ducts, Complete all as specified and directed by Engr-in-Charge.
All as per Item No 59 here-in-before but cross sectional area 16 sqmm, 4 core
All as per Item No 59 here-in-before but cross sectional area 25 sqmm, 3.5 core
Supply, fabricate, erect , connect, test and commissoning of factory made, CPRI approved, cubical type, indoor type LT panal board totally enclosed , dust, weather and vermin proof 1100 Volt grade , 50Hz, AC supply made out by 3.15mm thick CRCA sheet steel for load bearing and 2 mm thick for non load bearing, fully compartmentalised, with IP 65 protection all as per conferming to IS 2417 of 1962 complete including the following accessories housed in , Complete all as specified and as per directed by Engr-in-Charge. (a) ACB 4 Pole, 415 V, Manual Drawout typewith microprocessor release of capacity 1600 Amps( Incomer). (b) Indicator (RYB) I set. (c) MCCB 630 Amp -02( Out going) (d) Bus bar 1200 Amp with CT&P voltage&Amp meter
Supply, fabricate, erect , connect, test and commissoning of factory made, CPRI approved, cubical type, indoor type LT panal board totally enclosed , dust, weather and vermin proof 1100 Volt grade , 50Hz, AC supply made out by 3.15mm thick CRCA sheet steel for load bearing and 2 mm thick for non load bearing, fully compartmentalised, with IP 65 protection all as per conferming to IS 2417 of 1962 complete including the following accessories housed , Complete all as specified and as per directed by Engr-in-Charge. (a) MCCB 4 Pole 400 Amps, 415 V, 35 ka ( Incomer). (b) Indicator (RYB) I set. (c) MCCB 200 Amp -04 ( Out going) (d) Bus bar 400 Amp with CT&PT.voltage&Amp meter
M&L for replacement on/off load change over switch 630 Amps 4 pole 415 Volt AC 50 Hz conforming to IS:13947, open execution as per existing panel board size including taking down old unserviceable one, complete all as specified and directed by Engr-in-Charge. Make: Cat Part No IHCNFO0630 of Havells or equivalent make approved by GE
M&L for replacement on/off load change over switch 800 Amps 4 pole 415 Volt AC 50 Hz conforming to IS:13947, open execution as per existing panel board size including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. Make: Cat Part No IHCNFO0800 of Havells or equivalent make approved by GE
M&L for replacement on/off load change over switch 400 Amps 4 pole 415 Volt AC 50 Hz conforming to IS:13947, open execution as per existing panel board size including taking down old unserviceable one, complete all as specified and directed by Engr-in-Charge. Make: Cat Part No IHCNFO0400 of Havells or equivalent make approved by GE
M&L for old u/s earthing complete including taking out old earthing with galvanised earth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 25x4 mm GI strip earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GI protection pipe (light grade), funnel, wire mesh, cast iron cover and frame etc, complete, all as specified or indicated and as directed including testing on completion, Complete all as specified and as per directed by Engr-in-Charge. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2Ώ the earthing will be redone at no extra cost
Taking out UNSV UG cable of any sizes/ capacity, complete all specified & directed by Engr-in-Charge.
Supply and laying or fixing or passing through pipe, PVC insulated heavy duty industrial cables 5 core copper conductor(flexible) PVC insulated cable 1100 volt nominal area of conductor 4 sqmm (in replacement) making connections of street light fittings with overhead lines/UG Cable including taking out old cable , Complete all as specified and as per directed by Engr-in-Charge. Note :Excavation, earthwork, Pipe for cable protection, etc to be measured and paid for separately
All as per Srl item No 69 here-in-before but cross sectional area 2.5 sqmm, 3 core.
Supply and laying Double walled corrugated pipe (DWC) of size 40 mm conforming to IS:14930(part-II)/IS 16205 Part II with necessary snap fit coupler for cable protection in trenches, along wall/pole etc, complete all as specified & directed by Engr-in-Charge.
Painting to RCC /steel tubular poles 9/12 metre long at surface of any description over 10 CM grith or width ,not otherwise described,prepare old or new untreated surface,old painted surfaces including priming cement based paints plaster with synthetic enambled paint coat and plastic emulsion coat over surface with two coats of aluminium paint including brackets, clamps, nuts bolts, washer etc. including making yellow and black strips alternatively (30 cm width each) on pole upto 1.5 metre from the ground level and marking of pole Nos with black paint having back ground yellow as per existing complete all as specified and directed.
Replacement of old unserviceable rusted GI tubing brackets, 40mm bore, light grade with new GI tubing bracket, 40mm bore, light grade, 1.20 metre length ,made to shape including MS clamp with nuts, bolts and washers etc complete all as specified & directed by Engr-in-Charge.
S&F in replacement Terminal box made out of SMC with hinged door and locking arrangements of size 140x140x95mm including Backlite 4 way connector,M.S. Clamps suitable for pole ,PCC/MS/GI/rail etc. with bolt, nut and washer ,electrical connections including MCB SP 6-32 Amps complete all as specified and as directed by Engr-in-Charge.
Supply and Fix insulation tape 25 mm wide 6 Mtr long ISI mark of Red-Yellow-Blue-Black-Green colour complete all specified & directed by Engr-in-Charge. Make: Steel grip
LED flood light, 200 watt, 230 V, AC outdoor type with thermal management in multiple optics, powder coated, pressure die cast aluminium body with toughened glass visor, and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp,CCT 5700K, lumen efficacy not less than 110 lumen/watts (in repair) complete all as specified and directed by Engr-in-Charge. Make-Bajaj Cat Part No. PRAZE F 240L WH NB-A5 TG SD/Philips / Crompton/Havells, Wipro. Note: (a) MS clamp,Brackets required for fixing of fitting are inclusive of rate quoted. (b) Connection & erection of the same on pole shall deemed to be included in quoted rate.
LED flood light, 50 watt, 230 V, AC outdoor type with thermal management in multiple optics, powder coated, pressure die cast aluminium body with toughened glass visor, and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp,CCT 5700K, lumen efficacy not less than 110 lumen/watts (in repair) complete all as specified and directed by Engr-in-Charge. Make-Bajaj Cat Part No. GLATT F 50L WH PO PC SD/Philips / Crompton/Havells, Wipro. Note: (a) MS clamp,Brackets required for fixing of fitting are inclusive of rate quoted. (b) Connection & erection of the same on high mast pole shall deemed to be included in quoted rate.
LED street light fitting 60 Watt , 230 V, AC outdoor type with high pressure die cast aluminum hosing and heat resistant (in repair) complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP-66 protection, CCT 5700K, lumen efficacy not less than 110 lumen/watts complete all as specified and directed by Engr-in-Charge. Make-Bajaj Cat Part No. ZELA P 36L WH PO PC SD MT/Philips / Crompton/Havells, Wipro. Note: (a) MS clamp,Brackets required for fixing of fitting are inclusive of rate quoted. (b) Connection & erection of the same on pole shall deemed to be included in quoted rate.
LED street light fitting 30 Watt , 230 V, AC outdoor type with high pressure die cast aluminum hosing and heat resistant (in repair) complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP-66 protection, CCT 5700K, lumen efficacy not less than 110 lumen/watts complete all as specified and directed by Engr-in-Charge. Make-Bajaj Cat Part No. ENXT P 36L WH PO PC SD MT/Philips / Crompton. Note: (a) MS clamp,Brackets required for fixing of fitting are inclusive of rate quoted. (b) Connection & erection of the same on pole shall deemed to be included in quoted rate.
S &F LED Tiranga Rop light 18 Mtr,IP 65,Input Power 10W/meter,Input Voltage 220-240 VAC Input frequency 50 Hzs,Input current 0.045 Amp/Mtr,Power factor 0.95,Width of strip(+/- 0.1 mm) 8 mm length/reel-18 mtrs,No of led per mtr 120 LED,LED Beam angle 120 degree ,Rope light per Colours length 6 mtr orange, 6 mtr white ,6 mtr Green,Fixing method silicone clip ,Ingrass Protection -IP -65, Ingrass protection method silicone tube ,silicone tube dimention 11.5x5.5 mm+/- 0.5 mm,working temp range-20 degree celcius to + 45 degree celcious ,working humidity range 10-90 RH, including driver for each cut piece complete all as specified and directed by Engr-in-charge. Make Wipro/Philips/Crompton.
S&F Weather proof Street light Junction Box with Pole Clamp, Enclosure: 140 x 190 x 100 mm IP65 IP67 Water Proof and IK08 Impact Resistance & Ineffability as per IS13360. Top Cover and Bottom is made with Virgin grade ABS Material. Cable Outlet: PG 29 PVC Cable Gland (2x) and PG 13.5 PVC Cable Gland (1). Terminal: 63A 4 Way TPN Terminal Bar with nuts, Pole Mounting: Nylon 6 30% Glass filled heavy clamp with Stainless steel Hose Clamp up to 4inch Dia Pole complete all as specified and directed by Engr-in-charge.
MCB TPN -63 Amp, 230V, 50Hz, 10 KA (in replacement) complete all as specified & directed by Engr-in-Charge.
MCB TPN -40 Amp, 230V, 50Hz, 10 KA (in replacement) complete all as specified & directed by Engr-in-Charge.
MCB TP -63 Amp, 230V, 50Hz, 10 KA (in replacement) complete all as specified & directed by Engr-in-Charge.
MCB TP -40 Amp, 230V, 50Hz, 10 KA (in replacement) complete all as specified & directed by Engr-in-Charge.
MCB DP-63 Amp, 230V, 50Hz, 10 KA, (in replacement) complete all as specified & directed by Engr-in-Charge.
MCB DP-40 Amp, 230V, 50Hz, 10 KA, (in replacement) complete all as specified & directed by Engr-in-Charge.
MCB SP-63 Amp, 230V, 50Hz, 10 KA, (in replacement) complete all as specified & directed by Engr-in-Charge.
MCB SP-40 Amp, 230V, 50Hz, 10 KA, (in replacement) complete all as specified & directed by Engr-in-Charge.
MCB SP-25 Amp, 230V, 50Hz, 10 KA, (in replacement) complete all as specified & directed by Engr-in-Charge.
Supply and erecting steel tubular swaged poles erected to truly vertical or planted as strut complete with 6mm thick mild steel base plate(300mmx300mm), welded to pole, finial taper plug, bolts, nuts, and screws. Poles made out of ERW MS tubing conforming to IS-2713 Part-II Type 410 SP-37, 9.0mtr long including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bitumenous paint internally and portion embedded in concrete, making five black & white bands at lower portion of pole each 300mm wide alternately upto the height of 1.5 m and marking pole No. with black paint at suitable height including making two nos holes of suitable size in steel tubular pole by gas welding for passing PVC cable connection from junction box to security lights through pole where junction box to be fitted in pole complete all as specified and directed by Engineer-in-Charge. Note: - (i) Excavation, Earth Work and PCC in foundation shall be included in quoted rate. (ii) Uprooting of old pole including in quoted rate.
Plain cement concrete M- 7.5, (1:4:8), type D-2 (using 40mm graded crushed stone aggregates) as in foundation complete all as specified and directed by Engr-in-Charge.
Plain cement concrete, M-15, type B-0 (using 20 mm graded crushed stone aggregates) as in coping complete all as specified and directed by Engr-in-Charge.
S&F in replacement of automatic street light control Panel three phase with ingress protection IP-65 made of 14 SWG CRCA sheet metal(850 mm HeightX500mm Breath X 400 Depth), self supporting, Floor mounted, dust, vermin and weather proof for outdoor use shall be supplied for locally/automatically switching’ ON/OFF of luminaries (100 W/60 W x 10-20 Nos) having protection IP-66 using Infrared sensor based Nature Switch for automatic switching of street light. Nature switch operation should be based on Natural Light Lux*level. Reqd illuminance level also have part night operation facility for min 4 hrs to max 12 hrs. The sensor along with suitable rating power contractor (s), one Incoming and required no of Outgoing MCBs rating of 63/40 Amps & main load circuit wiring (copper) of min 10 sqmm. The circuit should be also have provision for manual operation (i.e. sensor by pass option) complete all as specified and directed by Engr-in-charge. Note: Panel should be placed on PCC foundation & M&L for foundation included in quoted rate.
S & F LED Highbay light with lens , 60 watt, 230 V, AC outdoor type with thermal management in multiple optics, powder coated, pressure die cast aluminium body with toughened glass visor, and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp,CCT 5700K, lumen efficacy not less than 130 lumen/watts (in repair) complete all as specified and directed by Engr-in-Charge. Make-Bajaj Cat Part No. PRAZE F 240L WH NB-A5 TG SD of Philips/Crompton.
Opening, maintenance and general servicing of arrangement of base compartment with SGDD Type Winch of highmast light & Control gear box including removal of dust, tightening of all nut bolts, cleaning, checking and servicing of winch gear box, power tool, Mast Door, SS wire rope, wire rope clamp and bobbin arrangement, handle for manual operation, mechanical torque limitor, Three-six Pully system, winch suspension system and other allied electrical components complete all as specified and directed by Engr-in-charge. Note : (i) Shifting of winch from AOR of AGE Water supply to workshop (Tro/ Fro) shall deemed to be included in quoted rate. (ii) Repairing/rewinding of Power tool motor 1/1.5 HP shall deemed to be included in quoted rate.
S&F in replacement Double dome LED type aviation obstruction light provided on top of Highmast. Led lamp 2nos x 100watt aviation obstruction light fitted in a weather- proof box on body unit of Aluminium alloy including taking down old complete all as specified and directed by Engr-in-charge. Note:- (i) Connection & erection of the same on high mast pole shall deemed to be included in quoted rate. (ii) All extra fittings like clamps, Nut bolts, washers required to install the light shall deemed to be included in quoted rate.
Lockable feeder pillar box with ingress protection IP-65 made of 14 SWG CRCA sheet metal(850 mm HeightX500mm Breath X 400 Depth), self supporting, Floor mounted, dust, vermin and weather proof for outdoor use shall be supplied for locally/automatically switching’ ON/OFF of luminaries (200 W x 06 Nos) & operation of winch motor. The control panel comprises the following: a) 63 Amps, 4 Pole MCCB for incomer power, Make: ABB/L&T/Siemens/SCHNEIDER. b) 32Amps TPN fuse switch unit as isolator for motor, Make: ABB/L&T/Siemens/SCHNEIDER. c) Earth leakage Relay with core balance transformer, Sensitivity: 30 MA to 2A, Time delay: 0 – 2 sec., Make: SCHNEIDER/ MDS Legrand/L&T/SIEMENS/ABB. d) 32 Amps triple pole AC 3 duty power contactor for lighting circuit, coil Voltage: 230VAC+/-10%,
e) Start/Stop push button for locally switching ON/OFF the luminaries – 1 set. NS type fuses carrier and base for control circuit. (Start/stop PB make:- Schneider Electric, L&T,Siemens and Fuse carrier and Fuse make:- GE,L&T,Siemens,CGL) f) Automatic lighting Switch with digital time switch of rail mounting suitable for astronomical calculations of sun rise and sun set by setting date, time and positions of longitude and latitude, asrto time –switch, 230V AC, 50HZ. g) 2Nos hoisting duty contactor for forward and reversing operation of motor along with Push buttons, LED indication lamps, other requisite switchgears for motor operation. (Contactor Make:- ABB/L&T/Siemens/SCHNEIDER) h) Detachable gland plate and nut-bolt type terminal blocks for incoming and outgoing cable connections. i) Feeder Pillar box to be painted with by 2 coats of primer followed by epoxy grey paint of shade RAL-7035. j) Push button for raising and lowering the mobile part shall operate on "Dead man principal" i.e. action shall cease as soon as the button is released. k) Single line diagram of electrical circuit to be shown on inner surface of the door of Feeder pillar box. Note: Panel should be placed on PCC foundation & M&L for foundation included in quoted rate.
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required), complete all as specified and directed by Engr-in-charge.
TARA ENTERPRISES (BID ID -3323073)
slathia construction works (BID ID -3316318)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .